SmartBox
®
1 / SmartBox
®
2 / SmartBox
®
3
6 / 16
Part No. 28 100 57 e
PROGRAMMING
Menu
Input function
Input value
0.Exit
Press [Enter] to return to display mode
1.Measure
probe
Select probe measuring range (see type label of the
probe) - default value is 250 mbar
________mbar
Standard probe
max. Tank height for
heating oil
water
100mbar
1.20 m
1.00 m
150mbar
1.80 m
1.50 m
160mbar
1.90 m
1.60 m
200mbar
2.40 m
2.00 m
250mbar
2.90 m
2.50 m
400mbar
4.70 m
4.00 m
500mbar
6.00 m
5.00 m
1.000mbar
12.00 m
10.00 m
2.000mbar
24.00 m
20.00 m
3.000mbar
36.00 m
30.00 m
5.000mbar
60.00 m
50.00 m
Set mbar
by
Calibration
Is only indicated if item 10. Set h
or 11. Set V has been activated
2.Liquid
Select the
medium
_______kg/m³
Medium
Measuring range kg/m³ (15 °C)
Heat. oil
Measuring range kg/m³ (15 °C)
Water
845 kg/m³ - default setting
Diesel
999 kg/m³
Biodiesel
830 kg/m³
RME, FAME
880 kg/m³
Rape oil
880 kg/m³
Palm oil
915 kg/m³
Motor oil
910 kg/m³
AdBlue
865 kg/m³
Regular
gasoline
1090 kg/m³
Premium
gasoline
743 kg/m³
Density valve
750 kg/m³
by
Calibration
Entry of a specific probe with
different measuring range
If the density of the stored medium is unknown, the reference height can be entered in menu
item “10.Trim height” To do this, determine the current fill level in mm,
deduct 1.0 cm
from it
and enter the resulting value - click YES to confirm the entry.
Should the current fill level be less than 75%, we urgently recommend that you adjust the
value after the next refuelling to achieve good measuring accuracy.