Leak detector type LAG 2000 A
part no. 15 071 53 e
19 / 28
Figure 5: Electrical power connection of the display unit
Electrical potential!
Electric shock risk
.
Switch off the power supply and make sure that it cannot be switched on again
inadvertently.
A1
Light "Operation"
A2
Button "Alarm sound"
A3
Light “Alarm“
A4
Alarm buzzer
A5
Button
Test
A6
Nipple for cable lead-through
A
Terminal for "power supply"
B
Terminal for additional "alarm"
C
Terminal for sensor cable
Via terminal "Power" „
A
“.
AC voltage 230V/ 50Hz.
Use only a fixed connection, not a pug
or switch.
Insert the cable through the nipple.
Connect the cable according to the
terminal block designation.
Connect the sensor unit
Connect – direct
Connect – indirect
Fig. 6
: display unit can be connected directly
Fig 7
: display unit can be connected in directly
If the display unit and the LDL tank
are installed beside each other, the sensor
cable can be connected directly with the
display unit
If the display unit and the LDL tank are
in different rooms or more than 0.4 m apart,
the sensor cable must be extended.