Leak detector type LAG 2000 A
12 / 28
part no. 15 071 53 e
Table 4
Storage medium
Installing the LDF tank in
Requirement
flammable
highly flammable
extremely flammable
flashpoint ≤ 55°C
potentially explosive
atmosphere zone 1
conductive connection
line
5
)
potentially explosive
atmosphere zone 2
Seal masonry opening
gastight
6
)
flammable category 3
non-flammable
(flashpoint > 55°C bis 100°C
non-hazardous areas
storing flammable, highly
flammable or extremely
flammable substances together
with non-flammable substances
If non-flammable liquids are stored in divided storage tanks
together with flammable, highly flammable or extremely
flammable liquids, the requirements for storing flammable,
highly flammable and extremely flammable liquids apply.
substances hazardous to water If other substances hazardous to water are stored, the
relevant statutory and technical requirements must be
observed.
5
)
See installation instructions for the connection line between the LDL tank and the monitoring
space of the fuel tank
6
)
Channels from connection lines that come out of the dome must be protected against the
infiltration
Installation location for the LDL tank
According to EN 13160-3, the LDL tank must be positioned so that:
•
the hydrostatic pressure of the leak detector liquid at the lowest point of the tank is at least
30mbar (= 3kPa) higher than the maximum pressure of the storage medium at the lowest
point of the tank (including working pressures) and also the maximum pressure of the
groundwater at the lowest point of the tank and
•
the pressure in the monitoring space does not exceed the nominal pressure of the
monitoring space
Remark 1: Here, the nominal pressure PN corresponds to the maximum permissible
pressure
p
s.
Remark 2: The construction standards for tanks contain only information about the test
pressure of the monitoring space
p
t,2
but none about the maximum permissible
pressure in the monitoring space
p
s,2.
•
the LDL tank must be positioned as follows
•
no surface or rainwater, dirt or windborne sand may get into the LDL tank, the sensor unit or
the cable connection fitting (accessory)
•
it must be protected against UV radiation