Combined heating oil filter breather type GS Pro-Fi
®
3
START-UP
Once leak testing is completed and the system is leak-tight, only the toggle valve of
the tank discharge fitting or, for systems without toggle valve, the shut-off safety
device must be opened. The vacuum still present in the line will suck fuel oil
immediately. If required, re-pump.
Unless specified differently in the burner/boiler manufacturer’s manual, the procedure is as
follows:
•
bleed the installed oil lines (burner supply and return
lines) and the fittings using a suction pump and fill
in fuel oil
•
open the shut-off fitting and the vent screw
•
connect the suction pump directly at the vent screw
using the supplied adapter item no. 13610-60
•
only stop the suction process once the vent tray is
filled with oil as well
•
close the vent screw in a leak-tight manner
OPERATION
During ongoing operation of the oil system, the GS Pro-Fi
®
3 does not require any operation.
The integrated shut-off fitting must be opened. For this, the rotary handle must be rotated in
the flow direction.
Due to the design of the GS Pro-Fi
®
3, the full fuel oil column without any noticeable shares of
air is available when starting the burner.
TROUBLESHOOTING
Fault cause
Action
Hose rupture in the supply or
return line
•
Burner switches to failure due to the sucked in ambient air
Restore the leak-tightness of the system
Released air in the vent tray
•
Burner switches to failure due to the sucked in ambient air
Restore the leak-tightness of the system
Strong noise generation of the
burner pump
•
Filter insert is clogged
For replacing the filter insert, see MAINTENANCE
Level in the filter tray
decreases
•
System has a leak
Restore the leak-tightness of the system
Filter tray runs empty,
•
System has a leak
Restore the leak-tightness of the system
Item No. 13 512 53
9 / 16
Содержание GS Pro-Fi 3
Страница 13: ...Heizölfilter Entlüfterkombination Typ GS Pro Fi 3 NOTIZEN Artikel Nr 13 512 50 i 13 16 ...
Страница 15: ...Heizölfilter Entlüfterkombination Typ GS Pro Fi 3 Artikel Nr 13 512 50 i 15 16 ...
Страница 29: ...Combined heating oil filter breather type GS Pro Fi 3 NOTES Item No 13 512 53 13 16 ...
Страница 31: ...Combined heating oil filter breather type GS Pro Fi 3 Item No 13 512 53 15 16 ...
Страница 63: ...Número de artículo 13 512 51 a 15 16 Combinación de filtro y purgador de gasóleo de calefacción GS Pro Fi 3 ...
Страница 78: ...Stookoliefilter ontluchtercombinatie type GS Pro FI 3 14 16 Apparaat nr 13 512 58 ...
Страница 79: ...Stookoliefilter ontluchtercombinatie type GS Pro FI 3 Apparaat nr 13 512 58 15 16 ...
Страница 95: ...Nr artykułu 13 512 52 a 15 16 Zestaw filtra oleju opałowego z odpowietrznikiem typu GS Pro Fi 3 ...