background image

 

Reducers on the air intakes are not permitted. 

 

The flue must be homogenous. 

 

Flue pipes or tubing used must be suitable for heater installations and be able to resist to 
chimney fires. The flue must be able to withstand temperatures 50⁰C higher than the 
declared smoke/fume temperature for the unit – whatever the installation method. 

 

The height of the flue should not be less than 5 metres and should exit into “free” air at least 
40cm above the crest of the roof or any higher obstacle that may be within 8 metres of the 
chimney. 

 

Any changes in the angle of the chimney must be as gentle as possible (a 45⁰ bend is highly 
preferable to a 90⁰ bend). 

 

The draw should be between 12 and 15 Pascals during normal (average) operation and 
should drop to 5 Pascals when running the unit on low. When running on a normal average 
setting the draw should not drop below 12 Pascals as the performance may be affected. 

If there is too much draw, a damper can be installed in the flue/chimney

. If there is not enough 

draw it may be that one of the points above has been disregarded. 

 

If the chimney conduit is too large, the volume of air to heat is too large to overcome and a 
normal draw cannot be established. In this case the chimney should be lined with tubing. 
The tubing used must conform to regulations and be suitable for heater installations (see 
above). 

 

Pottery chimney pots must be removed if they cause a reduction in the flue diameter. 

 

Before connecting the heater the chimney must be checked to ensure that it is clean and, if 
necessary, the chimney must be swept. 

 

The heater should be installed by a professional and all national and local regulations should 
be adhered to. 

 

An extractor operating in the same room as the heater can adversely affect the functioning 
of the heater. 

 

Other heaters operating in the same room at the same time can also cause problems with 
the draw. 

 

Never seal off incoming air vents into the room. Air vents should be situated in positions 
where it is unlikely that they would be accidentally blocked. The heater uses air that comes 
into the room in order to operate correctly – it is important that this air supply can renew 
itself from an external source. 

 

This heater is not to be connected to a chimney with multiple connections. 

 

The spigot for connection to the chimney/ flue may be attached either to the rear or top of 
the unit. Whichever position is not used must be sealed with the “blanking” plate. 

 

IMPORTANT 

 

Ensure that the floor can support the weight of the unit. If necessary a weight-bearing slab 
(cement, stone or tile) may have to support the unit. 

 

If the floor is of combustible material (wood, vinyl) it should be adequately protected with 
a material that surpasses the front of the unit by at least 40cm. 

 

Pipes that are used must be of the correct diameter and should preferably be enamelled as 
these are more resistant to corrosion. Any horizontal section must be as short as possible so 
that the hot fumes/ smoke can rapidly establish the correct operating draw for the unit. 

Содержание 660125

Страница 1: ...Insert ref 660125...

Страница 2: ...s Air control Manual Weight 180kg Output 14kW Corrected heating volume m3 200 500 Length of burn at normal rate 45 minutes Unit efficiency 72 55 Fume CO Level at 13 oxygen 0 07 Fumes CO2 Level 10 52 C...

Страница 3: ...chimney must be possible there should be no restrictions or sharp bends If there is any combustible material in the rear wall of the chimney some types of insulation this should be removed across the...

Страница 4: ...teel frame or suitable concrete lintel A false ceiling must be made of incombustible material Inspection traps Just as a trapdoor is allowed for access to your roof space it is important to allow for...

Страница 5: ...a The air intake can either be beneath the unit taking care it would not be restricted by the storage of firewood or by means of vents on the side walls either side of the insert Perforated metal plat...

Страница 6: ...h air supply for the insert A supplementary air supply must be allowed for An air intake should preferably be directly from the outside or otherwise from an adjacent well ventilated room The air disch...

Страница 7: ...on in the flue diameter Before connecting the heater the chimney must be checked to ensure that it is clean and if necessary the chimney must be swept The heater should be installed by a professional...

Страница 8: ...ng must go beyond this point INSTRUCTIONS FOR THE USER Before using the heater read the instruction manual carefully The unit must be installed in according to regulations and in accordance with the n...

Страница 9: ...te To enable proper drying of the building works after the 4 week period small moderate fires should be lit for the first 10 days The air register should not be opened fully during this period in orde...

Страница 10: ...rning material wood Do not use the unit if the glass is broken or cracked The glass should first be replaced Your installer should be contacted in order to assist you in replacing the glass for which...

Страница 11: ...HE ASH The ashtray should be emptied every 2 to 3 days depending on use of the heater This must be done carefully the ashtray should be carried using the glove provided and the operating tool should b...

Страница 12: ...egularly maintained using the black graphite paste Godin ref 0012 This is applied cold as a polish Once it has dried a soft cloth can be used to shine it up The high heat spray paint Godin ref 0001 ca...

Страница 13: ...firebox as shown below The base of the deflector plate rests on the ledge at the back of the firebox between the two support tags and the top is aligned with the support tag on the upper left inside...

Страница 14: ......

Страница 15: ...r fuel appliances 7 Boilers for central heating and cooking systems for wood coal Our appliances have been specially designed to facilitate replacing of these parts Some parts have a longer guarantee...

Страница 16: ...r s supervision or maintenance 6 Any modifications or transformations made to the unit and non compliance with installation norms Godin SA will not be responsible for any installation assembly dismant...

Отзывы: