Page | 5
The draught must range between 12 and 15 pascals. When burning normally and can drop to 5 pascals when
operating at a slow rate. When burning normally, if the draught drops below 12 pascals the unit may function
incorrectly (poorly).
If the cross section of the fireplace is too large, the volume to be heated is too big and the draught won’t be able
to reach satisfactory levels. In such cases, the chimney shall require internal piping with tubes adapted to wood
fires. The pipes diameter should in no case be inferior to 153mm.
Other units and extractors operating in the same area can generate draught disturbances.
Never obstruct the heater air intake.
These appliances are not to be connected to multiple conduits.
If the spigot is assembled at the rear of the unit, it can be connected directly to the chimney with a horizontal
flue.
It is recommended that an air tight cleaning trap is provided for approximately 50cm below the flue outlet at the
rear of the heater. This would make cleaning and serving of the flue/heater easier.
Installation by a qualified installer is recommended. All material specifications and local rules should be
respected.
Lastly, before connecting the fireplace to its chimney, make sure that the chimney or pipe is perfectly clean. If
necessary have the chimney cleaned.
Important:
The flue pipes gets hot, make sure that they are away from any combustible materials. If the floor is made of
combustible material, it will be necessary to protect the floor with an insulted plate made of non-flammable
material. The protection must extend at least 40cm beyond the unit.
Use flue pipes of the stipulated diameter and preferably enamel, as they are less corrosive. The rear wall should
not be made of flammable materials. It would be necessary to protect the wall accordingly. The wall on the left
and right hand side need to be a minimum of 50cm from the unit, and made of non flammable materials.
The ceiling needs to be at least 80cm above the unit.
Please keep all children, animals and furniture at a sufficient distance way from the fireplace to avoid accidents.
Connection to the chimney:
The connection to the chimney conduit to be done preferably with an enamel flue of 153 diameter.
General information:
When operating the unit, do not open the door by hand, use the operating tool or the glove for
operation.
While the heater is burning, keep the door closed.
Load the unit from the front door.
The regulation of the combustion is done by sliding the air control at the base of the door from left to
right (closed and open). When lighting the fire, the air control would be fully open and during normal
operation, it would be in the middle – varying from house to house.
For normal functioning 3 to 8 logs of 6cm diameter could be used on a bed of coals.