- SIL 3 Switch/Proximity Interface 

 

 

 

 

 

 

 

 

G.M. International ISM0113-7 

SIL 3 Switch/Proximity Interface 

DIN-Rail and Termination Board 

Models D5034S, D5034D 

 

D5034S - D5034D 

INSTRUCTION & SAFETY MANUAL 

Содержание D5034S

Страница 1: ...D5034 SIL 3 Switch Proximity Interface G M International ISM0113 7 SIL 3 Switch Proximity Interface DIN Rail and Termination Board Models D5034S D5034D D5034S D5034D INSTRUCTION SAFETY MANUAL...

Страница 2: ...to max supply change Load influence 0 05 of full scale for a 0 to 100 load resistance change Temperature influence 0 03 of full scale on zero and span for a 1 C change Compatibility CE mark compliant...

Страница 3: ...TR n 898 NEPSI T V Certifications T V Functional Safety Certification Type Approval Certificate DNV and KR for maritime applications High Density two channels per unit Simplified installation using s...

Страница 4: ...ve group See parameters indicated in the table below D5034 Terminals Ch1 Ch2 7 8 9 10 Ch1 Ch2 7 8 9 10 Io Isc 15 mA Ch1 Ch2 7 8 9 10 Po Po 39 mW Ii Imax Pi Pi D5034 Terminals D5034 Associated Apparatu...

Страница 5: ...ector Power Bus PLC In 1 Proximity voltage free Contact In 2 Proximity voltage free Contact voltage free Contact voltage free Contact R1 R2 R1 R2 MODEL D5034S 5 6 1 2 7 8 mA Out SIL 3 RL PLC Terminati...

Страница 6: ...at causes the output signal to go above 7 mA as short circuit of input Assuming that the application program in the safety logic solver is configured to detect High failure and does not automatically...

Страница 7: ...field in order to go to open connection condition equivalent to line breakage and verify that the output current of the repeater reaches low current value 0 35 mA This tests for possible quiescent cur...

Страница 8: ...ew terminal blocks which can be plugged in out into a powered unit without suffering or causing any damage for Zone 2 installations check the area to be nonhazardous before servicing The wiring cables...