D1010-054 / 056 / 057 

- mV to mA Converter 

G.M. International ISM0098-8 

For D1010S-054 



Set calibrator (CAL) at - 5.000 mV and verify that the output current, read by multimeter (DMM), is correspondent with a maximum deviation presented in the section “Technical Data”. 



Set calibrator (CAL) at 55.000 mV and verify that the output current, read by multimeter (DMM), is correspondent with a maximum deviation presented in the section “Technical Data”. 

If the maximum deviation is exceeded, repeat the board calibration and proceed in the following way: 



Set the calibrator (CAL) at 55.000 mV and regulate the current, read by multimeter (DMM), by turning the span trimmer of the unit (see “Configuration” section) until reading 
20.000 mA ± 5 µA value. 



Set the calibrator (CAL) at - 5.000 mV and regulate the current, read by multimeter (DMM), by turning the zero trimmer of the unit (see “Configuration” section) until reading 
4.000 mA ± 5 µA value. 



Repeat the last two steps to verify that the span trimmer’ s movement has not significantly modified the value of zero (a dragging of 1/5 exists when moving span and zero values. 



To execute a linearity test: set the calibrator (CAL) at - 5.000, 10.000, 25.000, 40.000, 55.000 mV and verify current output is correspondent at 4.000, 8.000, 12.000, 16.000, 
20.000 mA with a maximum deviation presented in the section “Technical Data”. 

For D1010S-056 



Set calibrator (CAL) at - 5.000 mV and verify that the output current, read by multimeter (DMM), is correspondent with a maximum deviation presented in the section“Technical Data”. 



Set calibrator (CAL) at 35.000 mV and verify that the output current, read by multimeter (DMM), is correspondent with a maximum deviation presented in the section “Technical Data”. 

If the maximum deviation is exceeded, repeat the board calibration and proceed in the following way: 



Set the calibrator (CAL) at 35.000 mV and regulate the current, read by multimeter (DMM), by turning the span trimmer of the unit (see “Configuration” section) until reading 
20.000 mA ± 5 µA value. 



Set the calibrator (CAL) at - 5.000 mV and regulate the current, read by multimeter (DMM), by turning the zero trimmer of the unit (see “Configuration” section) until reading 
4.000 mA ± 5 µA value. 



Repeat the last two steps to verify that the span trimmer’ s movement has not significantly modified the value of zero (a dragging of 1/5 exists when moving span and zero values. 



To execute a linearity test: set the calibrator (CAL) at - 5.000, 5.000, 15.000, 25.000, 35.000 mV and verify current output is correspondent at 4.000, 8.000, 12.000, 16.000, 
20.000 mA with a maximum deviation presented in the section “Technical Data”. 

For D1010S-057 



Set calibrator (CAL) at - 5.000 mV and verify that the output current, read by multimeter (DMM), is correspondent with a maximum deviation presented in the section “Technical Data”. 



Set calibrator (CAL) at 10.000 mV and verify that the output current, read by multimeter (DMM), is correspondent with a maximum deviation presented in the section “Technical Data”. 

If the maximum deviation is exceeded, repeat the board calibration and proceed in the following way: 



Set the calibrator (CAL) at 10.000 mV and regulate the current, read by multimeter (DMM), by turning the span trimmer of the unit (see “Configuration” section) until reading 
20.000 mA ± 5 µA value. 



Set the calibrator (CAL) at - 5.000 mV and regulate the current, read by multimeter (DMM), by turning the zero trimmer of the unit (see “Configuration” section) until reading 
4.000 mA ± 5 µA value. 



Repeat the last two steps to verify that the span trimmer’ s movement has not significantly modified the value of zero (a dragging of 1/5 exists when moving span and zero values. 



To execute a linearity test: set the calibrator (CAL) at - 5.000, - 1.250, 2.500, 6.250, 10.000 mV and verify current output is correspondent at 4.000, 8.000, 12.000, 16.000, 
20.000 mA with a maximum deviation presented in the section “Technical Data”. 

Содержание D1010S-054

Страница 1: ...D1010 054 056 057 mV to mA Converter ISM0098 8 D1010S 054 D1010S 056 D1010S 057 INSTRUCTION MANUAL mV to mA Converter DIN Rail Models D1010S 054 D1010S 056 D1010S 057...

Страница 2: ...oad 23 1 C ambient temperature Calibration accuracy 0 1 of full scale Linearity error 0 1 of full scale Supply voltage influence 0 02 of full scale for a min to max supply change Load influence 0 02 o...

Страница 3: ...gh Accuracy Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 ATEX IECEx Certifications High Reliability SMD components Simplified installation using standard DIN R...

Страница 4: ...Co Ca 100 F Co Ca 1000 F Co Ca 1000 F IIB C IIA D IIC A B Lo La 11 3 mH Lo La 45 3 mH Lo La 90 7 mH IIB C IIA D D1010 054 D1010 056 D1010 057 Associated Apparatus Parameters D1010 054 D1010 056 D1010...

Страница 5: ...mA Converter G M International ISM0098 8 Function Diagram HAZARDOUS AREA ZONE 0 ZONE 20 GROUP IIC SAFE AREA ZONE 2 GROUP IIC T4 MODELS D1010S 054 D1010S 056 D1010S 057 15 16 3 4 1 2 RL mA Supply 24 V...

Страница 6: ...10 05 must be cleaned only with a damp or antistatic cloth Any penetration of cleaning liquid must be avoided to prevent damage to the unit Any unauthorized card modification must be avoided According...

Страница 7: ...3 4 1 2 Connect the unit as shown below Set power supply PS at 24 0 V at terminals 3 and 4 the calibrator CAL in the function mV 100 mV range at terminals 15 and 16 the multimeter DMM for the reading...

Страница 8: ...35 000 mV and regulate the current read by multimeter DMM by turning the span trimmer of the unit see Configuration section until reading 20 000 mA 5 A value Set the calibrator CAL at 5 000 mV and reg...