Warning Message
Explanation
Action
Bus-Start-Warning
DC bus soft start is over time.
Wait until the controller has re-stabilized.
Bus-Low-Warning
DC bus voltage is too low.
Wait until the controller has re-stabilized.
Bus-High-Warning
DC bus voltage is too high.
Wait until the controller has re-stabilized.
ENS-Fac-Warning
Different value between master
and slave for grid frequency.
Check system frequency and line voltage.
Service if system frequency is within normal
range.
Boost-Curr-
Warning
Boost current is over the
tolerable value.
Acknowledge error.
EEPROM-Warning
EEPROM cannot be read or
written.
Wait until the controller has re-stabilized.
Boost-Start-Warning
Time limit exceeded of DC bus
soft-start.
Acknowledge error. Contact the service if the
error occurs repeatedly.
DC Over Power
DC power over maximum limit
Acknowledge error.
Fan-Lock Warning
Fan lock
Acknowledge error. Contact the service if the
error occurs repeatedly.
Over-voltage of battery
packs
The battery voltage is too high.
Acknowledge error. Contact the service if the
error occurs repeatedly.
Low battery voltage
The battery voltage is too low.
Check voltage of battery packs Contact the
service if the error occurs repeatedly.
Over-current of battery
packs
The battery current is higher
than the upper limit.
Check battery packs Contact the service if the
error occurs repeatedly.
Low battery energy
The battery energy is too low.
Check battery packs Contact the service if the
error occurs repeatedly.