background image

 

D5098 

- 5 A SIL 3 Relay Out Module for NE Load 

G.M. International ISM0305-2 

 

 

 

Technical Data 

Characteristics 

Input: 

24 Vdc nom (21.6 to 27.6 Vdc) reverse polarity protected, ripple within voltage limits 

 5 Vpp. 

Current consumption @ 24 V:

 45 mA for D5098S, 25 mA/channel D5098D typical (D5098D could be incompatible with PLC/DCS DO cards, requiring a load impedance below 1 k

). 

Power dissipation @ 24 V:

 1.1 W for D5098S, 0.6 W/channel for D5098D typical. 

Isolation (Test Voltage): 

Output/Input 1.5 KV; Input/Input 500 V; Output/Output 1.5 KV 

Outputs: 

1 voltage free SPDT relay contact identified with outputs: Out 1 (NO contact) terminals 7-8 and Service Load Out 1 (NC contact) terminals 7-11; 

   

 1 voltage free SPDT relay contact identified with outputs Out 2 (NO contact) terminals 9-10 and Service Load Out 2 (NC contact) terminals 9-12 (only for D5098D). 

  Terminals 7-8 (Out 1) and 9-10 (Out 2, only for D5098D) are open when relay is de-energized , closed in energized relay condition.  

Service load outputs (not SIL) at terminals 7-11 and 9-12 (only for D5098D) are normally closed when relay is de-energized, open in energized relay condition.

 

Contact material: 

Ag Alloy (Cd free), gold plated. 

Contact rating: 

5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W (resistive load). Min.switching current 1 mA. 

Contact inrush current: 

6 A at 24 Vdc, 250 Vac. 

DC and AC Load breaking capacity: 

Mechanical / Electrical life: 

5 * 10

6

 / 3 * 10

4

 operation, typical. 

Operate / Release time: 

30 ms / 30 ms typical. 

Frequency response: 

10 Hz maximum.

 

Compatibility: 

 

CE mark compliant, conforms to Directives: 2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS. 

Environmental conditions: 

Operating:

 temperature limits – 40 to + 70 °C, relative humidity 95 %, up to 55 °C. 

Storage:

 temperature limits - 45 to + 80 °C. 

Safety Description: 

ATEX:

 II 3G Ex nA nC IIC T4 Gc.  

IECEx:

 Ex nA nC IIC T4 Gc 

non-sparking electrical equipment. -40 °C 

 Ta 

 70 °C. 

Approvals:  

IMQ 17 ATEX 009 X conforms to EN60079-0, EN60079-15. 
IECEx IMQ 17.0006X conforms to IEC60079-0, IEC60079-15. 
TÜV Certificate No. C-IS-272994-01 SIL 3 conforms to IEC61508:2010 Ed.2 . 
TÜV Certificate No. C-IS-236198-09, SIL 3  Functional Safety Certificate conforms to IEC61508:2010 Ed.2, for Management of Functional Safety. 

Mounting: 

T35 DIN-Rail according to EN50022 or on customized Termination Board. 

Weight:

 about 150 g D5098D, about 110 g D5098S. 

Connection:

 by polarized plug-in disconnect screw terminal blocks to accommodate 

terminations up to 2.5 mm

2

Location:

 installation in Safe Area or Zone 2, Group IIC T4 

Protection class:

 IP20. 

Dimensions: 

Width 12.5 mm, Depth 123 mm, Height 120 mm. 

General Description: 

The single and dual channel D5098S and D5098D Relay Output modules are suitable for the switching of safety related circuits, up to SIL 3 level according to IEC 61508:2010 Ed.2, 
for high risk industries. 
They provide isolation between input and output contacts. 
D5098S provides one NO contact for normally energized loads and one NC contact for service purposes. 
D5098D provides two NO contacts for two normally energized loads and two NC contact for service purposes. 
Mounting on standard DIN-Rail or on customized Termination Boards, in Safe Area or in Zone 2. 

 

Functional Safety Management Certification: 

G.M. International is certified by TUV to conform to IEC61508:2010  
part 1 clauses 5-6 for safety related systems up to and included SIL3. 

FSM

SIL 3

0.2

0.0

V (V)

I (A)

10

20

30

40

50

100

0.3 0.4 0.5

1

2

3

Resistive

Load

200

4

300
250

0.1

5

6

DC

resistive

AC

Resistive

Содержание D5098S

Страница 1: ...D5098 5 A SIL 3 Relay Out Module for NE Load G M International ISM0305 2 5 A SIL 3 Relay Output Module for NE Load DIN Rail and Termination Board Models D5098S D5098D D5098S D5098D INSTRUCTION MANUAL ...

Страница 2: ...ating temperature limits 40 to 70 C relative humidity 95 up to 55 C Storage temperature limits 45 to 80 C Safety Description ATEX II 3G Ex nA nC IIC T4 Gc IECEx Ex nA nC IIC T4 Gc non sparking electrical equipment 40 C Ta 70 C Approvals IMQ 17 ATEX 009 X conforms to EN60079 0 EN60079 15 IECEx IMQ 17 0006X conforms to IEC60079 0 IEC60079 15 TÜV Certificate No C IS 272994 01 SIL 3 conforms to IEC615...

Страница 3: ...safety system ATEX IECEx TÜV Certifications TÜV Functional Safety Certification Simplified installation using standard DIN Rail and plug in terminal blocks or customized Termination Boards DIN Rail accessories Cover and fix MCHP196 Terminal block male MOR017 Terminal block female MOR022 Terminal block connections CM1 1st pole of Out 1 NO contact for NE Load or NC contact for Service SAFE AREA NO1 ...

Страница 4: ...open terminals 7 11 and 9 12 are closed To prevent relay contacts from damaging connect an external protection fuse or similar chosen according to the relay breaking capacity diagram MODEL D5098D Out 1 NO contact NO1 8 CM1 7 In 1 1 2 Service Load Out 1 Termination board connector Not SIL NC1 11 Out 2 NO contact NO2 10 CM2 9 In 2 3 4 Service Load Out 2 Not SIL NC2 12 SIL 3 SIL 3 2 Inputs 2 Loads ...

Страница 5: ...ilar chosen according to the relay breaking capacity diagram MODEL D5098S Out 1 NO contact NO1 8 CM1 7 In 1 1 2 Service Load Out 1 Termination board connector Not SIL NC1 11 SIL 3 MODEL D5098D Out 1 NO contact NO1 8 CM1 7 In 1 1 2 Service Load Out 1 Termination board connector Not SIL NC1 11 Out 2 NO contact NO2 10 CM2 9 3 4 Service Load Out 2 Not SIL NC2 12 SIL 3 SIL 3 Relay contacts shown in de ...

Страница 6: ...to the relay breaking capacity diagram on data sheet The enclosure provides according to EN60529 an IP20 minimum degree of protection or similar to NEMA Standard 250 type 1 For non hazardous location the unit shall be installed in an area of not more than pollution degree 2 For hazardous location the unit shall be installed in a certified Ex enclosure with a minimum ingress protection of at least ...

Отзывы: