3
D5098
- 5 A SIL 3 Relay Out Module for NE Load
G.M. International ISM0305-2
Ordering information
Front Panel and Features
SIL 3 (low demand mode of operation) for NE Load according to IEC 61508:2010 Ed.2, with Tproof = 14 / 20 yrs (10 / 20 % of total SIF) and
PFDavg (1 year) = 7.02 E-06, SFF = 98.71 %.
SIL 3 (high demand mode of operation) for NE Load according to IEC 61508:2010 Ed.2, with PFH = 1.60 E-09 h
-1
.
Systematic capability SIL 3.
Installation in Zone 2.
Compatible with DCS/PLC pulse testing.
SIL 3 contact for NE Load and contact for service purposes.
6 A inrush current at 24 Vdc / 250 Vac.
Input/Output isolation.
EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system.
ATEX, IECEx, TÜV Certifications.
TÜV Functional Safety Certification.
Simplified installation using standard DIN-Rail and plug-in terminal blocks or customized Termination Boards.
DIN-Rail accessories: Cover and fix MCHP196
Terminal block male MOR017
Terminal block female MOR022
Terminal block connections
(CM1) 1st pole of Out 1 (NO contact) for NE Load or (NC contact) for Service
SAFE AREA
(NO1) 2nd pole of Out 1 (NO contact) for NE Load
(CM2) 1st pole of Out 2 (NO contact) for NE Load or (NC contact) for Service
7
8
9
+ Input
1
- Input
2
+ Input (only for D5098D)
3
- Input (only for D5098D)
4
(NO2) 2nd pole of Out 2 (NO contact) for NE Load
10
(NC1) 2nd pole of Out 1 (NC contact) for Service load
(NC2) 2nd pole of Out 2 (NC contact) for Service load
11
12
Not used
5
Not used
6
D
2 channels
S
1 channel
Model:
D5098
7 8
9 10
11 12
1
2
3
4
D5098
7 8
1 2
SIL 3
9 10
STS 1
11 12
3 4
STS 2