D5014 

- SIL 3 Repeater Power Supply 

G.M. International ISM0103-3 

D5014 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4, 
Hazardous Area (according to EN/IEC60079-15) within the specified operating temperature limits Tamb –40 to +70 °C, and connected to equipment with a maximum limit for 
AC power supply Um of 250 Vrms. 
Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground. 
D5014 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. IEC/EN60079-14 
Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care 
shall be given to segregation and clear identification of I.S. conductors from non I.S. ones. 
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous. 

Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. 
Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous. 

Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. 
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. 
Any unauthorized modification must be avoided. 

 

Warning 

Operation 

 D5014 provides fully floating DC supply for energizing 2 wires 4-20 mA transmitters, or separately powered 3, 4 wires, 0/4-20 mA transmitters located in Hazardous Area, 

and repeats and converts the current to a 0/4-20 mA or 0/1-5 V floating output signal to drive a Safe Area load. 
The circuit allows bi-directional communication signal for smart transmitters, a “POWER ON” green led for each channel lits when input power is present. 

Installation 

 D5014 series are repeater power supply hart compatible housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or 
on customized Termination Board. 
D5014 unit can be mounted with any orientation over the entire ambient temperature range. 
Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without 
suffering or causing any damage 

(for Zone 2 installations check the area to be nonhazardous before servicing)

The wiring cables have to be proportionate in base to the current and the length of the cable. 
On the section “Function Diagram” and enclosure side a block diagram identifies all connections. 
Identify the number of channels of the specific card (e.g. D5014S is a single channel model and D5014D is a dual channel model), the function and location of each connection terminal 
using the wiring diagram on the corresponding section, as an example: 
Connect 24 Vdc power supply positive at terminal “5” and negative at terminal “6”. 
For Model D5014S connect positive output of channel 1 at terminal “1” and negative output at “2”. 
For Model D5014D in addition to channel 1 connections above, connect positive output of channel 2 at terminal “3” and negative output at “4”. 
For Model D5014S, in case of a 2 wires Transmitter, connect the wires at terminal “7” for positive and “8” for negative. 
For separately powered Transmitters connect input signal at terminal “8” for positive and “11” for negative. 
For Model D5014D in addition to channel 1 connections above, connect terminal “9” for positive and “10” for negative on channel 2. 
Connect input signal from separately powered Transmitters at terminals “10” for positive and “12” for negative on channel 2. 
 
Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 
Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other 
and do not produce any unintentional connection. 
The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard 250 type 1) for indoor installation, outdoor installation 
requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the effective operating environment of the specific installation. 
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. 
If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water. 

Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5014 must be cleaned only with a damp or antistatic cloth. 

Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided. 
According to EN61010, D5014 series must be connected to SELV or SELV-E supplies. 

 

 

Start-up 

 Before powering the unit check that all wires are properly connected, particularly supply conductors and their polarity, input and output wires, also check that Intrinsically Safe conductors 

and cable trays are segregated (no direct contacts with other non I.S. conductors) and identified either by color coding, preferably blue, or by marking. 
Check conductors for exposed wires that could touch each other causing dangerous unwanted shorts. Turn on power, the “power on” green leds must be lit, for 2 wires transmitter 
connection the supply voltage on each channel must be 

 14.5 V, output signal should be corresponding to the input from the transmitter. If possible change the transmitter output and 

check the corresponding Safe Area output. 

 

Содержание D5014D

Страница 1: ...D5014 SIL 3 Repeater Power Supply G M International ISM0103 3 SIL 3 Repeater Power Supply Hart DIN Rail and Termination Board Models D5014S D5014D D5014S D5014D INSTRUCTION MANUAL INSTRUCTION MANUAL ...

Страница 2: ...Vrms on 250 Ω communication load on 0 5 to 2 5 KHz band Frequency response 0 5 to 2 5 KHz bidirectional within 3 dB Hart protocol Performance Ref Conditions 24 V supply 250 Ω load 23 1 C ambient temperature Calibration accuracy 0 1 of full scale Linearity error 0 05 of full scale Supply voltage influence 0 02 of full scale for a min to max supply change Load influence 0 02 of full scale for a 0 to...

Страница 3: ...nstallation using standard DIN Rail and plug in terminal blocks with or without Power Bus or customized Termination Boards 250 Vrms Um max voltage allowed to the instruments associated with the barrier Input Ch 1 for 2 wires Transmitters Terminal block connections HAZARDOUS AREA SAFE AREA Input Ch 1 for 2 wires Transmitters or Input Ch 1 for External Powered Transmitters Input Ch 2 for 2 wires Tra...

Страница 4: ...for the effective group See parameters indicated in the table below D5014 Terminals Ch1 Ch2 7 8 9 10 Uo Voc 1 1 V Ch1 Ch2 8 11 10 12 Io Isc 92 mA Ch1 Ch2 7 8 9 10 Io Isc 56 mA Ch1 Ch2 8 11 10 12 Po Po 594 mW Ch1 Ch2 7 8 9 10 Po Po 16 mW Ch1 Ch2 8 11 10 12 Ii Imax Pi Pi D5014 Terminals Ch1 Ch2 8 11 10 12 D5014 Associated Apparatus Parameters Cenelec US Ci Ci device C cable IIC A B Co Ca 100 nF Co C...

Страница 5: ...cable parameters are unknown the following value may be used Capacitance 180pF per meter 60pF per foot Inductance 0 60µH per meter 0 20µH per foot Must be Hazardous Area Hazardous Locations Device Parameters D5014 Associated Apparatus Parameters Ui Vmax 30 V Uo Voc D5014 Terminals Ch1 Ch2 8 11 10 12 li Imax 128 mA Ch1 Ch2 8 11 10 12 Io Isc Ci 0 nF Li 0 nH Ch1 Ch2 8 11 10 12 Function Diagram HAZARD...

Страница 6: ...available for Transmitter Vtx is 14 V at 20 mA input The safety parameters must be changed in Uo Voc 27 V Io Isc 93 mA Po Po 623 mW Terminals 7 10 Uo Voc 27 V Io Isc 93 mA Po Po 623 mW IIC IIB IIA 0 090 0 705 2 330 4 1 16 6 33 2 57 0 228 3 456 6 Group Cenelec Lo Ro µH Ω Lo La mH Co Ca µF I iaD 3 750 0 705 54 5 16 6 749 1 228 3 5 6 1 2 RL mA HHT Source I Out 1 SIL 3 3 4 RL mA Source I Out 2 SIL 3 7...

Страница 7: ...µH Ω Lo La mH Co Ca µF I iaD 1000 1000 151 1 46 0 15272 7 4654 5 Connections for Duplication of Active Input Signals Restriction on specifications for external powered Transmitter The safety parameters must be changed in Uo Voc 2 2 V Io Isc 56 mA Po Po 31 mW 5 6 1 2 RL mA Source I 3 4 RL mA Source I 7 11 10 12 8 9 MODEL D5014D Duplicator Termination board connector Power Bus Supply 24 Vdc External...

Страница 8: ...nections Identify the number of channels of the specific card e g D5014S is a single channel model and D5014D is a dual channel model the function and location of each connection terminal using the wiring diagram on the corresponding section as an example Connect 24 Vdc power supply positive at terminal 5 and negative at terminal 6 For Model D5014S connect positive output of channel 1 at terminal ...

Страница 9: ...ode Ch2 1 5 V on 250 internal shunt Ch1 1 5 V on 250 internal shunt ON ON OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON OFF OFF ON ON ON ON OFF OFF OFF OFF Ω Ω Dip switch configuration An output configuration DIP Switch is located on component side of pcb This switch allows the mA sink or source mode or Volt operating mode configuration 1 2 3 4 ON 4 20 mA Source Mode 1 2 3 4 1 2 3 4 1 2 3 4 4 20 mA Si...

Страница 10: ...rent of the repeater reaches that value This tests for possible quiescent current related failures 4 Restore the loop to full operation 5 Remove the bypass from the safety related PLC or restore normal operation This test will detect approximately 99 of possible Dangerous Undetected failures in the repeater Steps Action 1 Bypass the safety related PLC or take other appropriate action to avoid a fa...

Страница 11: ... the selected fail safe state The 2 channels of D5014D module could be used to increase the hardware fault tolerance needed for a higher SIL of a certain Safety Function as they are completely independent each other not containing common components In fact the analysis results got for D5014S single channel are also valid for each channel of D5014D double channel Failure rates table Failure categor...

Отзывы: