3
D5014
- SIL 3 Repeater Power Supply
G.M. International ISM0103-3
Ordering Information
Front Panel and Features
•
SIL 3 according to IEC 61508 for Tproof = 1 / 2 yrs (10 / 20 % of total SIF).
•
SIL 2 according to IEC 61508 for Tproof = 10 / 20 yrs (10 / 20 % of total SIF).
•
PFDavg (1 year) 9.39 E-05, SFF 93.92 %.
•
2 fully independent channels.
•
Input from Zone 0 (Zone 20), installation in Zone 2.
•
0/4-20 mA Input / Output Signal Active-Passive / Source-Sink
•
Hart compatible.
•
Input and Output short circuit proof.
•
High Accuracy.
•
Three port isolation, Input/Output/Supply.
•
EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system.
•
In-field programmability by DIP Switch.
•
ATEX, IECEx, Russian and Ukrainian Certifications.
•
High Density, two channels per unit.
•
Simplified installation using standard DIN-Rail and plug-in terminal blocks, with or without Power Bus, or customized Termination Boards.
•
250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier.
+ Input Ch 1 for 2 wires Transmitters
Terminal block connections
HAZARDOUS AREA
SAFE AREA
- Input Ch 1 for 2 wires Transmitters or
+ Input Ch 1 for External Powered Transmitters
+ Input Ch 2 for 2 wires Transmitters
- Input Ch 2 for 2 wires Transmitters or
+ Input Ch 2 for External Powered Transmitters
- Input Ch 1 for External Powered Transmitters
- Input Ch 2 for External Powered Transmitters
7
8
9
10
11
12
+ Output Ch 1
1
- Output Ch 1
2
+ Output Ch 2
3
- Output Ch 2
4
+ Power Supply 24 Vdc
5
- Power Supply 24 Vdc
6
7 8
9 10
11 12
2
1
4 3
6 5
Model:
D5014
1 channel
S
2 channels
D
Power Bus and DIN-Rail accessories:
Connector JDFT049
Cover and fix MCHP196
Terminal block male MOR017
Terminal block female MOR022
11
D5014
12
9
10
7
8
1
2
3
4
5
6
SIL 3
2
1
PWR
PWR