- SIL 3 Repeater Power Supply
G.M. International ISM0103-3
When used with separate powered intrinsically safe devices, check that maximum allowable voltage, current (Ui/Vmax, Ii/Imax) of the D5014 Associated Apparatus are not exceeded by
the safety parameters (Uo/Voc, Io/Isc) of the Intrinsically Safe device, indicated in the table below:
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable),
then 50 % of Co and Lo parameters are applicable and shall not be exceeded
(50 % of the Co and Lo become the limits which must include the cable such that
Ci C cable
≤
50 % of Co and Li L cable
≤
50 % of Lo).
If the cable parameters are unknown, the following value may be used: Capacitance 180pF per meter (60pF per foot), Inductance 0.60µH per meter (0.20µH per foot).
Must
be
Hazardous Area/
Hazardous Locations
Device Parameters
D5014 Associated
Apparatus Parameters
Ui / Vmax = 30 V
Uo / Voc
D5014 Terminals
Ch1
Ch2
8 - 11
10 - 12
li / Imax = 128 mA
Ch1
Ch2
8 - 11
10 - 12
≥
Io / Isc
≥
Ci = 0 nF, Li= 0 nH
Ch1
Ch2
8 - 11
10 - 12
Function Diagram
HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC
SAFE AREA, ZONE 2 GROUP IIC T4
=
=
=
5 +
6 -
1
2
RL
mA
+
-
HHT
Source I
Out 1 (SIL 3)
3
4
RL
mA
+
-
Source I
Out 2 (SIL 3)
HHT
7
11
+
-
HHT
2 Wire Tx
I
?
+
-
External
Powered Tx
In 1
10
12
+
-
2 Wire Tx
+
-
External
Powered Tx
In 2
HHT
I
?
8
9
MODEL D5014D
+
-
Termination
board
connector
Power Bus
=
=
=
=
=
=
=
Supply 24 Vdc
mA
+
V
Source V
Sink I
+
-
+
-
RL
mA
+
V
Source V
Sink I
+
-
+
-
RL
=
=
=
5 +
6 -
1
2
RL
mA
+
-
HHT
Source I
Out (SIL 3)
Supply 24 Vdc
7
11
+
-
HHT
2 Wire Tx
I
?
+
-
External
Powered Tx
In
8
MODEL D5014S
=
=
+
-
Termination
board
connector
Power Bus
mA
+
V
Source V
Sink I
+
-
+
-
RL