D1072 

- SIL 2 Temperature Signal Converter, Duplicator, Adder/Subtractor 

G.M. International ISM0018-13 

Non-incendive field wiring is not recognized by the Canadian Electrical Code, installation is permitted in the US only. 
For installation of the unit in a Class I, Division 2 or Class I, Zone 2 location, the wiring between the control equipment and the D1072 associated apparatus shall be accomplished 
via conduit connections or another acceptable Division 2, Zone 2 wiring method according to the NEC and the CEC. 
Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground. 
D1072 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards 
(e.g. IEC/EN60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165, 
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/ NFPA 70 Section 504 and 505, 
Canadian Electrical Code CEC) following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones. 
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area/Hazardous Locations or 
unless area is known to be nonhazardous. 

Warning: substitution of components may impair Intrinsic Safety and suitability for Division 2, Zone 2. 
Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous. 

Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. 
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. 
Any unauthorized modification must be avoided. 

 

Warning 

D1072 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN Rail located in Safe Area/ Non Hazardous Locations or Zone 2, Group IIC, 
Temperature Classification T4, Class I, Division 2, Groups A, B, C, D, Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA Temperature Code T4 Hazardous Area/Hazardous 
Locations (according to EN/IEC60079-15, FM Class No. 3611, CSA-C22.2 No. 213-M1987, CSA-E60079-15) within the specified operating temperature limits Tamb -20 to +60 °C, 
and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. 

Operation 

 

Input channel of D1072 accepts a signal from Hazardous Area/Hazardous Locations (thermocouple, resistance thermometer, transmitting potentiometer) and converts the signal to a 
0/4-20 mA or 0/1-5 V or 0/2-10 V floating output to drive a load in Safe Area/Non Hazardous Locations. Presence of supply power is displayed by a green signaling LED, integrity of field 
sensor and connecting line can be monitored by a configurable burnout circuit which, if enabled, can drive output signal to upscale or downscale limit. 
Burnout detection is also signaled by a red LED on the front panel and by an optocoupled transistor in common with power supply. Type D1072S has a single input and output channel, 
type D1072D has double input and output channel; type D1072D can also be programmed to interface a single input and obtain dual output channel (duplicator) or configurable output 
channel (outputs can repeat the corresponding inputs or be proportional to the sum or difference of the two input process variables or with low/high selector function). 

 

D1072 Associated Apparatus

FM Approved

under Entity Concept

and non-incendive field wiring

Unclassified Locations or

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D, T-Code T4

Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4

FM Approved under Entity Concept,

or third party approval

Hazardous (Classified) Locations

Class I, Division 1, Groups A, B, C, D

Class II, Division 1, Groups E, F, G

Class III, Division 1

Class I, Zone 0, Group IIC, IIB, IIA

Intrinsically 

Safe Equipment

Must not use or generate

more than 250 Vrms or Vdc

Control 

Equipment

Unclassified Locations

Unclassified Locations or

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D, T-Code T4

Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D

Class II, Division 2, Groups E, F, G

Class III, Division 2

Class I, Zone 2, Group IIC, IIB, IIA

FM Approved under non-incendive field

wiring (permitted only for US installations),

or third party approval

Non-incendive 

Equipment

Unclassified Locations

13
14

1
2

+

-

-

+

Power Supply

3
4

Must not use or generate

more than 250 Vrms or Vdc

15

-

+

Control 

Equipment

6

5

10

11

9

12

16

Intrinsically 

Safe Equipment

-

+

-

-

+

+

Control 

Equipment

Control 

Equipment

Power Supply

D1072 Associated Apparatus

FM Approved

under Entity Concept

and non-incendive field wiring

14

10

12

11

16

9

15

13

2

6

3
4

5

1

Non-incendive 

Equipment

Содержание D1072D

Страница 1: ... Temperature Signal Converter Duplicator Adder Subtractor ISM0018 13 D1072S D1072D INSTRUCTION MANUAL INSTRUCTION MANUAL SIL 2 Temperature Signal Converter Duplicator Adder Subtractor Din Rail Models D1072S D1072D ...

Страница 2: ...ammed to detect burnout condition with downscale or highscale forcing Burnout condition signalled by red front panel LED Output 0 4 to 20 mA on max 600 Ω load source mode current limited at 22 mA or 0 1 to 5 V or 0 2 to 10 V signal limited at 11 V Resolution 2 µA current output or 1 mV voltage output Transfer characteristic linear or reverse on mV or transmitting potentiometer temperature linear o...

Страница 3: ...l Common burnout detection available when using Power Bus enclosure High Accuracy µP controlled A D converter Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 Fully programmable operating parameters ATEX IECEx UL C UL FM FM C Russian and Ukrainian Certifications Type Approval Certificate DNV and KR for marine applications High Reliability SMD components High De...

Страница 4: ...13 14 15 16 Ch1 9 10 11 12 Ch2 13 14 15 16 Ch1 9 10 11 12 Ch2 13 14 15 16 Ch1 9 10 11 12 Ch2 NOTE for USA and Canada IIC equal to Gas Groups A B C D E F and G IIB equal to Gas Groups C D E F and G IIA equal to Gas Groups D E F and G When used with separate powered intrinsically safe devices check that maximum allowable voltage Ui Vmax of the D1072 Associated Apparatus are not exceeded by the safet...

Страница 5: ...C T4 MODEL D1072D 3 4 1 2 RL mA V Supply 12 24 Vdc Source I Source V Out 1 13 14 15 In 2 16 5 6 RL mA V Source I Source V Out 2 9 10 11 12 TC Reference Junction Compensator Option 91 TC In 1 TC Reference Junction Compensator Option 91 TC MODEL D1072D 3 4 1 2 RL mA V Supply 12 24 Vdc Source I Source V Out 1 13 14 15 16 5 6 RL mA V Source I Source V Out 2 9 10 11 12 In 1 3 wire RTD 4 wire RTD Pot 3 ...

Страница 6: ...ource I Source V Out 1 A 13 14 15 16 5 6 RL mA V Source I Source V Out 1 B In 1 3 wire RTD 4 wire RTD Pot MODEL D1072D 3 4 1 2 RL mA V Supply 12 24 Vdc Source I Source V Out 1 13 14 15 In B 16 5 6 RL mA V Source I Source V Out 2 9 10 11 12 TC Reference Junction Compensator Option 91 TC In A TC Reference Junction Compensator Option 91 TC Adder Subtractor Low High Selector Output repeats input A B A...

Страница 7: ... GROUPS E F G CLASS III DIVISION 1 CLASS I ZONE 0 GROUP IIC SAFE AREA ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1072S 3 4 1 2 RL mA V Supply 12 24 Vdc Source I Source V Out 1 13 14 15 16 In 1 TC Reference Junction Compensator Option 91 TC MODEL D1072S 3 4 1 2 RL mA V Supply 12 24 Vdc Source I Source V Out 1 13 14 15 1...

Страница 8: ... FM Class No 3611 CSA C22 2 No 213 M1987 CSA E60079 15 within the specified operating temperature limits Tamb 20 to 60 C and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms Operation Input channel of D1072 accepts a signal from Hazardous Area Hazardous Locations thermocouple resistance thermometer transmitting potentiometer and converts the signal to a 0 4 20 mA or 0...

Страница 9: ...temperature input connect thermometer wire A at terminal 16 B and C interconnected wires at terminals 14 and 13 for channel 1 and at terminals 12 10 9 for channel 2 Note that for a correct line resistance compensation in case of 3 wire sensor wire A and B should have the same resistance Intrinsically Safe conductors must be identified and segregated from non I S and wired in accordance to the rele...

Страница 10: ...y Voltage V Power Dissipated into the input output loads Analog signal isolators have higher dissipation than digital signal isolators in addition 2 channels barriers D1072D have higher dissipation than single channel units D1072S In analog signal isolators each transmitter requires and dissipates 15 V 0 02 A 0 3 W Usually the loads outside the isolator dissipate 1 3 of the total power used Isolat...

Страница 11: ... the Select key to the next menu level item or Up key to return to second level If you pressed Enter key you can choose between 2 different sensor connection type press Select key to change the input connection and then the Enter key to confirm the choice The input connection types are 3 ter 3 wire connection type thermoresistance 4 ter 4 wire connection type thermoresistance 7 CJ Typ 3 Level Menu...

Страница 12: ...voltage output range from 0 to 10 V Burnout analog output burnout state None burnout function is disabled analog output represents the input measure as configured Downscale analog output is forced at mA Burnout or V Burnout lower value Upscale analog output is forced at mA Burnout or V Burnout higher value Function analog output function Ch A analog output represents input of first channel Ch B an...

Отзывы: