D1072 

- SIL 2 Temperature Signal Converter, Duplicator, Adder/Subtractor 

G.M. International ISM0018-13 

Parameters Table 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Device Parameters 

D1072 Associated 

Apparatus Parameters 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Cable Parameters 

Uo / Voc = 10.8 V 

Ui / Vmax 

In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check 
its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded 
by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D1072 Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that 
added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas 
group. See parameters on

 

enclosure side and the ones indicated in the table below:

 

D1072 Terminals 

13 - 14 - 15 - 16 

 

D1072 Terminals 

D1072 Associated 

Apparatus Parameters 

Ci / Ci  C cable 

 

(IIC-A, B) 

Co / Ca = 2.134 µF 

Co / Ca = 14.994 µF 
Co / Ca = 65.994 µF 

(IIB-C) 
(IIA-D) 

Ch1 

9 - 10 - 11 - 12 

Ch2 

(IIC-A, B) 

Lo / La = 468 mH 

Lo / La = 1874 mH 
Lo / La = 3749 mH 

(IIB-C) 
(IIA-D) 

 

Li / Li L cable 

(IIC-A, B) 

Lo / Ro = 1510 µH/

 

Lo / Ro = 6050 µH/

 

Lo / Ro = 12100 µH/

 

(IIB-C) 
(IIA-D) 

 

Li / Ri device and 

L cable / R cable 

Io / Isc = 9 mA 

Ii/ Imax 

13 - 14 - 15 - 16 

 

Ch1 

9 - 10 - 11 - 12 

Ch2 

Po / Po = 24 mW 

Pi / Pi 

13 - 14 - 15 - 16 

 

Ch1 

9 - 10 - 11 - 12 

Ch2 

13 - 14 - 15 - 16 

Ch1 

9 - 10 - 11 - 12 

Ch2 

13 - 14 - 15 - 16 

Ch1 

9 - 10 - 11 - 12 

Ch2 

13 - 14 - 15 - 16 

Ch1 

9 - 10 - 11 - 12 

Ch2 

NOTE for USA and Canada: 

IIC equal to Gas Groups A, B, C, D, E, F and G 
IIB equal to Gas Groups C, D, E, F and G 

IIA equal to Gas Groups D, E, F and G 

When used with separate powered intrinsically safe devices, check that maximum allowable voltage (Ui/Vmax) of the D1072 Associated Apparatus are not exceeded by the safety 
parameters (Uo/Voc) of the Intrinsically Safe device, indicated in the table below: 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Device Parameters 

D1072 Associated 

Apparatus Parameters 

Ui / Vmax = 18 V 

Uo / Voc 

D1072 Terminals 

Ch1 

Ch2 

13 - 14 - 15 - 16 

9 - 10 - 11 - 12 

 

Ci = 6 nF, Li= 0 nH 

Ch1 

Ch2 

13 - 14 - 15 - 16 

9 - 10 - 11 - 12 

 

For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable), 
then 50 % of Co and Lo parameters are applicable and shall not be exceeded 

(50 % of the Co and Lo become the limits which must include the cable such that 

Ci C cable 

 50 % of Co and Li  L cable 

 50 % of Lo). 

If the cable parameters are unknown, the following value may be used: Capacitance 60pF per foot (180pF per meter), Inductance 0.20µH per foot (0.60µH per meter). 
The Intrinsic Safety Entity Concept allows the interconnection of Intrinsically Safe devices approved with entity parameters not specifically examined in combination as a system 
when the above conditions are respected. 
For Division 1 and Zone 0 installations, the configuration of Intrinsically Safe Equipment must be FM approved under Entity Concept (or third party approved); 
for Division 2 installations, the configuration of Intrinsically Safe Equipment must be FM approved under non-incendive field wiring or Entity Concept (or third party approved). 

Содержание D1072D

Страница 1: ... Temperature Signal Converter Duplicator Adder Subtractor ISM0018 13 D1072S D1072D INSTRUCTION MANUAL INSTRUCTION MANUAL SIL 2 Temperature Signal Converter Duplicator Adder Subtractor Din Rail Models D1072S D1072D ...

Страница 2: ...ammed to detect burnout condition with downscale or highscale forcing Burnout condition signalled by red front panel LED Output 0 4 to 20 mA on max 600 Ω load source mode current limited at 22 mA or 0 1 to 5 V or 0 2 to 10 V signal limited at 11 V Resolution 2 µA current output or 1 mV voltage output Transfer characteristic linear or reverse on mV or transmitting potentiometer temperature linear o...

Страница 3: ...l Common burnout detection available when using Power Bus enclosure High Accuracy µP controlled A D converter Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 Fully programmable operating parameters ATEX IECEx UL C UL FM FM C Russian and Ukrainian Certifications Type Approval Certificate DNV and KR for marine applications High Reliability SMD components High De...

Страница 4: ...13 14 15 16 Ch1 9 10 11 12 Ch2 13 14 15 16 Ch1 9 10 11 12 Ch2 13 14 15 16 Ch1 9 10 11 12 Ch2 NOTE for USA and Canada IIC equal to Gas Groups A B C D E F and G IIB equal to Gas Groups C D E F and G IIA equal to Gas Groups D E F and G When used with separate powered intrinsically safe devices check that maximum allowable voltage Ui Vmax of the D1072 Associated Apparatus are not exceeded by the safet...

Страница 5: ...C T4 MODEL D1072D 3 4 1 2 RL mA V Supply 12 24 Vdc Source I Source V Out 1 13 14 15 In 2 16 5 6 RL mA V Source I Source V Out 2 9 10 11 12 TC Reference Junction Compensator Option 91 TC In 1 TC Reference Junction Compensator Option 91 TC MODEL D1072D 3 4 1 2 RL mA V Supply 12 24 Vdc Source I Source V Out 1 13 14 15 16 5 6 RL mA V Source I Source V Out 2 9 10 11 12 In 1 3 wire RTD 4 wire RTD Pot 3 ...

Страница 6: ...ource I Source V Out 1 A 13 14 15 16 5 6 RL mA V Source I Source V Out 1 B In 1 3 wire RTD 4 wire RTD Pot MODEL D1072D 3 4 1 2 RL mA V Supply 12 24 Vdc Source I Source V Out 1 13 14 15 In B 16 5 6 RL mA V Source I Source V Out 2 9 10 11 12 TC Reference Junction Compensator Option 91 TC In A TC Reference Junction Compensator Option 91 TC Adder Subtractor Low High Selector Output repeats input A B A...

Страница 7: ... GROUPS E F G CLASS III DIVISION 1 CLASS I ZONE 0 GROUP IIC SAFE AREA ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1072S 3 4 1 2 RL mA V Supply 12 24 Vdc Source I Source V Out 1 13 14 15 16 In 1 TC Reference Junction Compensator Option 91 TC MODEL D1072S 3 4 1 2 RL mA V Supply 12 24 Vdc Source I Source V Out 1 13 14 15 1...

Страница 8: ... FM Class No 3611 CSA C22 2 No 213 M1987 CSA E60079 15 within the specified operating temperature limits Tamb 20 to 60 C and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms Operation Input channel of D1072 accepts a signal from Hazardous Area Hazardous Locations thermocouple resistance thermometer transmitting potentiometer and converts the signal to a 0 4 20 mA or 0...

Страница 9: ...temperature input connect thermometer wire A at terminal 16 B and C interconnected wires at terminals 14 and 13 for channel 1 and at terminals 12 10 9 for channel 2 Note that for a correct line resistance compensation in case of 3 wire sensor wire A and B should have the same resistance Intrinsically Safe conductors must be identified and segregated from non I S and wired in accordance to the rele...

Страница 10: ...y Voltage V Power Dissipated into the input output loads Analog signal isolators have higher dissipation than digital signal isolators in addition 2 channels barriers D1072D have higher dissipation than single channel units D1072S In analog signal isolators each transmitter requires and dissipates 15 V 0 02 A 0 3 W Usually the loads outside the isolator dissipate 1 3 of the total power used Isolat...

Страница 11: ... the Select key to the next menu level item or Up key to return to second level If you pressed Enter key you can choose between 2 different sensor connection type press Select key to change the input connection and then the Enter key to confirm the choice The input connection types are 3 ter 3 wire connection type thermoresistance 4 ter 4 wire connection type thermoresistance 7 CJ Typ 3 Level Menu...

Страница 12: ...voltage output range from 0 to 10 V Burnout analog output burnout state None burnout function is disabled analog output represents the input measure as configured Downscale analog output is forced at mA Burnout or V Burnout lower value Upscale analog output is forced at mA Burnout or V Burnout higher value Function analog output function Ch A analog output represents input of first channel Ch B an...

Отзывы: