D1049 

- SIL 3 Digital Output Driver NE Loads Bus Powered 

G.M. International ISM0097-9 

Functional Safety Manual and Application 

Application of D1049S for NE load

 

 

Failure category

 

Failure rates (FIT)

 

λ

dd

 = Total Dangerous Detected failures 

0.00 

λ

du

 = Total Dangerous Undetected failures 

1.90 

λ

sd

 = Total Safe Detected failures 

0.00 

λ

su

 = Total Safe Undetected failures 

170.63 

λ

tot safe

 = Total Failure Rate (Safety Function) = 

λ

dd

 + 

λ

du

 + 

λ

sd

 + 

λ

su

 

172.53

 

MTBF (safety function, single channel) = (1 / 

λ

tot safe

) + MTTR (8 hours)

 

661 years

 

λ

no effect

 = “No effect” failures 

271.27 

λ

not part

 = “Not Part” failures 

31.60 

λ

tot device

 = Total Failure Rate (Device) = 

λ

tot safe

 + 

λ

no effect

 + 

λ

not part

 

475.40

 

MTBF (device, single channel) = (1 / 

λ

tot device

) + MTTR (8 hours)

 

240 years

 

λ

sd

 

λ

su

 

λ

dd

 

λ

du

 

SFF

 

0.0 FIT 

170.63 FIT 

0.00 FIT 

1.90 FIT 

98.90% 

Failure rates table according to IEC 61508:2010 Ed.2 : 

Failure rate table:

 

Safety Function and Failure behavior:

  

D1049S is considered to be operating in Low Demand mode, as a Type A module, having Hardware Fault Tolerance (HFT) = 0. 

The failure behaviour of D1049S for NE loads is described by the following definitions: 

 Fail-Safe State: it is defined as the output being de-energized; 

 Fail Safe: failure mode that causes the module / (sub)system to go to the defined fail-safe state without a demand from the process; 

 Fail Dangerous: failure mode that does not respond to a demand from the process (i.e. being unable to go to the defined fail-safe state), so that the output remains energized

 

 Fail “No Effect”: failure mode of a component that plays a part in implementing the safety function but that is neither a safe failure nor a dangerous failure.  

When calculating the SFF, this failure mode is not taken into account. 

□ 

Fail “Not part”: failure mode of a component that is not part of the safety function but part of the circuit diagram and is listed for completeness.  

When calculating the SFF, this failure mode is not taken into account. 

    Failure rate data: taken from Siemens Standard SN29500. 

Description:

  

The D1049S is a single channel digital output drivers, Bus powered for NE (Normally Energized) loads. The Safety PLC or DCS control signal enables the field devices through the 
single channel digital output driver D1049S  (1 intrinsic safety channel, Bus Powered), which provides the electrical isolation between Supply - Input and Output. The presence of the 
input control signal is also indicated by a yellow LED on the front panel.

 

In order to interface the majority of field devices available on the market, two basic output circuits with different safety parameters (outputs A, B and C) are provided for channel.  
The selection among the three output characteristics is obtained by connecting the field devices to a different couple of terminal blocks. 
The field line and load fault detection is enabled, the override input is disabled and direct In / Out operation is selected, setting the internal DIP-switches in the following modes:

 

 
 
 
 

The module is powered by connecting 24 Vdc power supply to Pins 3 (+ positive) and 4 (- negative).  
The Control signal from Safety PLC Outputs is applied to Pins 5 - 6.  
The Output NE load is applied to Pins 13 - 16 or 14 - 16 or 15-16.

 

The following table describes the state (energized or de-energized) of the output when the Loop Control signal is in the High (20 to 30 Vdc) or Low (0 Vdc) state. 

Operation 

Input Signal State  

Pins 5 - 6 

Output State  

Pins 13-16 (Out A) or 14-16 (Out B) or 15-16 (Out C)

 

 

Normal 

High (20 to 30 Vdc) 

Energized  

Trip 

Low (0 Vdc) 

De-energized (as safe state condition) 

De-energized to trip operation

 

D1049S 

 

13 

14 

 

Out 1 

 

15 

Solenoid 

Valve 

16 

Out C 

Normal  state operation

 

Output is de-energized 

 

Out B 

 

Out A 

Solenoid 

Valve 

Solenoid 

Valve 

1 +  

2 - 

In 1 

  20 Vdc 

 

7 +  

8 - 

Must not be used 

because disabled 

Fault Output 

Not used for  

functional  

safety purpose 

D1049S 

 

1 +  

2 - 

13 

14 

 

Out 1 

 

15 

Solenoid 

Valve 

16 

Out C 

In 1 = 0 Vdc 

 

Output is energized 

 

Out B 

 

Out A 

Solenoid 

Valve 

Solenoid 

Valve 

7 +  

8 - 

Fault Output 

Not used for  

functional  

safety purpose 

SW1 Dip-switch position

 

ON / OFF state

 ON 

SW2 Dip-switch position

 

ON / OFF state

 ON 

OFF 

Must not be used 

because disabled 

 

3 + 

4 - 

Supply 24 Vdc 

Control Signal from 

Safety PLC Output 

5 + 

6 - 

 

3 + 

4 - 

Supply 24 Vdc 

Control Signal from 

Safety PLC Output 

5 + 

6 - 

T[Proof] = 1 year

 

T[Proof] = 12 years

 

PFDavg = 8.32 E-06

 

Valid for 

SIL 3

  PFDavg = 9.98 E-05

 

Valid for 

SIL 3

 

PFDavg vs T[Proof] table 

(assuming Proof Test coverage of 99%), with determination of SIL supposing module contributes >10% of total SIF dangerous failures: 

PFDavg vs T[Proof] table

 (assuming Proof Test coverage of 99%), with determination of SIL supposing module contributes 

10%  of total SIF dangerous failures: 

T[Proof] = 20 years

 

PFDavg = 1.66 E-04

 

Valid for 

SIL 3

 

Systematic capability SIL 3

 

Содержание D1049S

Страница 1: ...D1049 SIL 3 Digital Output Driver NE Loads Bus Powered ISM0097 9 D1049S INSTRUCTION SAFETY MANUAL SIL 3 Digital Output Driver NE Loads Bus Powered DIN Rail Model D1049S ...

Страница 2: ...ent consumption 24 V 5 mA Output 45 mA at 13 0 V 21 0 V no load 174 Ω series resistance at terminals 13 16 Out A 45 mA at 10 2 V 21 0 V no load 236 Ω series resistance at terminals 14 16 Out B 45 mA at 8 5 V 21 0 V no load 275 Ω series resistance at terminals 15 16 Out C Short circuit current 50 mA 55 mA typical Response time 10 ms Frequency response 50 Hz Fault detection field device and wiring o...

Страница 3: ...t limited Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 EN61326 1 In field programmability by DIP Switch ATEX IECEx FM FM C INMETRO EAC EX UKR TR n 898 TÜV Certifications TÜV Functional Safety Certification Type Approval Certificate DNV for maritime applications High Reliability SMD components Simplified installation using standard DIN Rail and plug in termi...

Страница 4: ...evice Cable Parameters D1049 Terminals D1049 Associated Apparatus Parameters Ci Ci device C cable Li Li device L cable Lo La 1 65 mH Lo La 6 63 mH Lo La 13 2 mH IIB C IIA D IIC A B Lo La 2 9 mH Lo La 11 8 mH Lo La 23 6 mH IIB C IIA D IIC A B Lo La 4 19 mH Lo La 16 7 mH Lo La 33 5 mH IIB C IIA D IIC A B Out C 15 16 Io Isc 147 mA Ii Imax Out A 13 16 Out B 14 16 Io Isc 110 mA Out C 15 16 Io Isc 93 mA...

Страница 5: ...ly examined in combination as a system when the above conditions are respected For Division 1 and Zone 0 installations the configuration of Intrinsically Safe Equipment must be FM approved under Entity Concept or third party approved for Division 2 installations the configuration of Intrinsically Safe Equipment must be FM approved under non incendive field wiring or Entity Concept or third party a...

Страница 6: ...wered which provides the electrical isolation between Supply Input and Output The presence of the input control signal is also indicated by a yellow LED on the front panel In order to interface the majority of field devices available on the market two basic output circuits with different safety parameters outputs A B and C are provided for channel The selection among the three output characteristi...

Страница 7: ...detection Replace the series connection of a 1 kΩ load resistor and an ammeter with a current calibrator set to 45 mA This current generator and a voltmeter are connected in parallel to one of the module outputs starting with Out A then going on with Out B and finally proceeding with Out C Supply the D5049S or D1049S mod ule at 24 Vdc and apply a 24 Vdc ON control signal to the module input channe...

Страница 8: ...horts Turn on power the power on green led must be lit status led and fault led must were in accordance with condition of the corresponding output line If possible change the status of driving signal and connection line one at time checking the corresponding status and fault leds condition as well as output to be correct The single channel DIN Rail Bus Powered Digital Output Isolator D1049S is sui...

Страница 9: ...t used SW1 Field line and load fault detection 1 OFF 1 ON Disabled Enabled 1 1 ON SW2 IN OUT Operation Used for SIL applications Input high 24 Vdc output energized or Input low 0 Vdc output de energized Input high 24 Vdc output de energized or Input low 0 Vdc output energized Override control input Disabled Enabled 4 4 ON OFF OFF SW2 dip switch configuration 1 2 3 4 ON Not Used SW1 factory setting...

Отзывы: