4 Replacement of Parts
6369
SECURING
SCREW
(4+4)
Diagram 4.12
IGNITION UNIT SECURING
SCREW
IGNITION UNIT
SENSING
ELECTRODE
LEAD
IGNITION (CVI)
UNIT
SECURING
SCREW
EARTH
ELECTRODE
LEAD
SPARK
ELECTRODE
LEAD
SECURING
SCREW (2)
5288
Diagram 4.13
GAS VALVE
CONNECTOR
SENSING
TUBES
4.16 Gas Valve
Remove control box housing, see diagram 4.1.
Remove the user control switch bracket, see diagram 4.3.
Remove the ignition unit securing screws, see diagram 4.12.
Remove ignition unit.
Disconnect sensing tubes noting which way they fit.
Remove the four extended hexagon screws at the right hand side
of the gas valve,
Support the gas valve, disconnect the union nut at the gas service
cock and remove the valve complete with the inlet pipe.
Separate the valve from the pipe, noting the fitted position.
Discard the “O” rings and fit the new ones supplied.
Fit gas valve cables. The polarity is not important.
Check and adjust the main burner gas pressure in the hot water
and central heating modes, refer to “Commissioning” in the
Installation Instructions.
4.17 Ignition unit
Remove control box housing, see diagram 4.1.
Remove the user control switch bracket, see diagram 4.3.
Remove the ignition unit securing screws. see diagram 4.13.
Disconnect the electrical connector and the three electrode leads.
Remove ignition unit.
Note: when re-fitting make sure the electrode leads are fitted to the
correct terminals, see diagram 4.13.
4.18 Domestic Hot Water Flow Sensor
Before commencing refer to Section 1.1
Isolate the boiler from the electrical supply, refer to Section 1.3.
Remove the outer case, refer to Section 1.4.
Isolate the domestic hot water inlet, release the domestic water
pressure and drain, refer to Section 1.3 and 1.6.
Remove the control housing, refer to Section 4.14.
Remove the user control switch bracket, see diagram 4.14.
Remove the pressure gauge bracket, see diagram 4.7.
Disconnect the flow sensor cables at the inline connectors.
Remove the flow sensor by disconnecting the union nuts, see
diagram 4.15, noting the fitted position.
Slacken or remove the clip securing the isolating valve, to ease
removal.
Discard the sealing washers and use the new ones supplied.
It is recommended that the water inlet filter is cleaned or renewed
at this stage.
Make sure that the sensor is positioned correctly, with the flow
arrow pointing upwards.
ELECTRICAL
CONNECTORS
SELECTOR
SWITCH
CONTROL
RESET BUTTON
Diagram 4.14
5027