24

221045A

4   R e p l a c e m e n t   o f   P a r t s

Diagram 4.15

Diagram 4.16

4.18 Thermistor - Heating

Release the water pressure and drain the heating circuit
of the boiler, refer to Sections 1.3 and 1.6.

Gain access by removing the piezo bracket, see
diagram 4.3.

Disconnect the cables from the thermistor, see
diagram 4.14.

Remove the thermistor, complete with its “O” ring.

The polarity of the electrical connections is
not important.

4.19 Thermistor - Domestic Hot Water

The replacement of this part can be done within the
limits of the minimum clearances.  Should there be a
side clearance of 150mm or more then the pump need
not be removed.

Remove the pump, refer to Section 4.9.

Release the water pressure and drain the domestic hot
water circuit of the boiler, refer to Section 1.3. and 1.6.

Disconnect the cables from the thermistor, see
diagram 4.14.

Remove the thermistor complete with its “O” ring.

The polarity of the electrical connections is not
important.

4.20 Safety Valve

Release the water pressure and drain the central heating
circuit of the boiler, refer to Section 1.3 and 1.6.

Remove the pressure gauge, refer to Section 4.12.

Disconnect the union nuts to release the safety valve, see
diagram 4.15.

4.21 Water Inlet Filter

Refer to the appropriate parts of Section 4.17.

4.22 Domestic Hot Water Throttle

Release the water pressure and drain the domestic hot
water circuit of the boiler, refer to Section 1.3 and 1.6.

Refer to Section 4.17 to gain access to the throttle.

Remove the cap nut and carefully remove the throttle
adjuster, by unscrewing, it may be necessary to push the
throttle adjuster out from the rear, see diagram 4.16.

Clean if necessary, taking care not to damage the
throttle body.

Reset the domestic hot water flow rate refer to Section
11.7 in the Installation Instructions.

MINI EXPANSION
VESSEL

Diagram 4.17

SAFETY
VALVE

CAP NUT

THROTTLE
ADJUSTER

‘O’ RING

SEALING
WASHER

PRESSURE
GAUGE
CONNECTION

SEALING
WASHER

UNION
NUT

DISCHARGE
PIPE

2794

4600

4601

Содержание SwiftFlow 120

Страница 1: ...13 One Contact Total Service Hepworth Heating Ltd Nottingham Road Belper Derbyshire DE56 1JT General Sales enquiries Tel 01773 824141 Fax 01773 820569 Fanned Flue Combination Boiler This is a Cat I 2...

Страница 2: ...f the Laws of the Member States relating to appliances burning gaseous fuels 2 Directive 73 23 EEC on the harmonization of the Laws of the Member States relating to electrical equipment designed for u...

Страница 3: ...four screws see diagram 1 3 1 6 System Pressures and Draining WARNING All parts containing water of the central heating circuit within the boiler are under the system pressure Before any parts of this...

Страница 4: ...Remove the fan securing screws Pull the fan forwards at the bottom and rotate to disengage the fan outlet to flue elbow and rear bracket Take care not to damage the seal Tilt the fan and withdraw Rem...

Страница 5: ...ct the condition of all seals and joints renewing them as necessary Check the condition of the combustion chamber insulation Check that the spark gap is as shown in diagram 2 1 2 7 Note Reassembly Mak...

Страница 6: ...s co Tel 0161 620 6677 6 221045A 2 S e r v i c i n g Diagram 2 5 STEP 1 STEP 3 STEP 2 STEP 4 SECURING SCREW WING NUT BURNER BRACKET WING NUT BURNER BRACKET BURNER GUIDE BURNER SIDE GUIDES MAIN INJECTO...

Страница 7: ...al heating selector switched Off see diagram 3 2 check that the domestic water supply is available and water flows freely from the hot taps Close the taps 7 With the boiler central heating selector sw...

Страница 8: ...piezo unit button is there a spark across electrode gap Undo tubing nut at pilot outlet of mulitfunctional control Press multifunctional control knob Does gas flow freely Rectify blockage in pilot inj...

Страница 9: ...Test continuity of thermocouple between inner connection point D and point E Is there continuity Thermocouple and boiler overheat circuit satisfactory Faulty cutoff connectors into multifunctional co...

Страница 10: ...utlined in a Multimeter Instruction book are the first checks to be carried out during a fault finding procedure Isolate the boiler from the electrical supply refer to Section 1 3 Gain access to the b...

Страница 11: ...ULTIFUNCTIONAL CONTROL SOLENOID DHW CUT OFF CONTROL WATER PRESSURE SWITCH SHOWN IN PRESSURISED STATE 240V 26V TRANS FORMER TO REMOTE HEATING CONTROL 5 WAY PLUG SOCKET DHW FLOW SWITCH SELECTOR SWITCH C...

Страница 12: ...that the remote controls are not calling for duty and there is no domestic hot water demand Replace CN6 With no demand to the boiler Restore power Does the mains Orange LED come on Does the boiler lig...

Страница 13: ...Faulty APS Replace NO YES Isolate supply Reconnect CN6 restore power supply YES Faulty main PCB Replace NO YES YES NO Open DHW tap at full rate Does burner pressure go to 13 1mb YES Is the burner pres...

Страница 14: ...the resistance between 8K and 11K Faulty flow switch Replace NO YES Turn the DHW flow off Turn on the CH Does pump run Faulty main PCB Replace YES Faulty DHW O H stat Replace Is there continuity acro...

Страница 15: ...er if no central heating refer to main fault finding YES Isolate the boiler from electrical supply remove outer case YES Diagram 3 9 DIGITAL CLOCK TIMER STYLE 1 and 2 FAULT FINDING ELECTRO MECHANICAL...

Страница 16: ...4 2 Main Burner Refer to the appropriate parts of Section 2 2 Note There is no need to remove the fan or flue collector assemblies 4 3 Main Injector Refer to the appropriate parts of Section 2 2 Note...

Страница 17: ...ctors from the multifunctional control see diagram 4 2 Remove the boiler overheat cutoff secured with two screws see diagram 4 2 Use the heat sink compound supplied between the mounting plate and the...

Страница 18: ...ection 11 10 in the Installation Instructions Note Should the pump fail to operate refer to diagram 3 8 If all is in order but the pump still does not operate remove the end screw see diagram 4 5 then...

Страница 19: ...mbly as shown in diagram 4 1 Lift the control housing cover to gain access to the board Disconnect all multipin connectors see diagram 4 8 Remove the control board from the support posts To reconnect...

Страница 20: ...ove the control housing cover and disconnect the electrical connectors from the transformer see diagram 4 8 Remove the transformer securing screws 2 off from beneath the control housing remove the tra...

Страница 21: ...ANENT MAINS SUPPLY FUSED AT 3A CHASSIS EARTH PUMP 1 2 N L v gry r screened screened r w gry b y g p r w gry b y g p p p g y b br r r bk L N g y or y p gry w g y g y CN1 CN7 CN6 CN3 CN4 CN5 N L N L 230...

Страница 22: ...Control Remove the four left hand extended hexagon screws from the multifunctional control Discard the O rings and fit the new ones supplied Check and adjust the main burner gas pressure in both the...

Страница 23: ...ntrol air ratio unit assembly need not be removed Isolate the domestic hot water inlet and drain refer to Sections 1 3 and 1 6 When replacing the flow switch it is recommended that the water inlet fil...

Страница 24: ...rmistor complete with its O ring The polarity of the electrical connections is not important 4 20 Safety Valve Release the water pressure and drain the central heating circuit of the boiler refer to S...

Страница 25: ...t water circuits refer to Section 1 3 and 1 6 Remove the fan from the flue collector refer to Section 2 2 Remove the flue collector refer to Section 2 2 Remove the main burner refer to Section 2 2 Rem...

Страница 26: ...ont insulation secured with a clip see diagram 4 20 Slide out both side insulation pieces Remove the burner as in Section 2 2 Pull the lower rear insulation forward then slide the upper rear insulatio...

Страница 27: ...nion nuts at the front of the isolating valves see diagram 1 1 Disconnect the gas service cock union Disconnect the safety valve discharge pipe from the boiler see diagram 1 1 Separate the two parts o...

Страница 28: ...tubes from the switch Remove the air pressure switch secured with two screws When replacing the tubes to the air pressure switch make sure that the forward clear tube from the air pressure switch con...

Страница 29: ...d Digital clock timer Style 2 Release the mounting bracket securing screws see diagram 4 26 Disconnect electrical cables release securing clip to remove the clock timer and spacer see diagram 4 27 Dia...

Страница 30: ...56 6 202435 Thermocouple 378 204 7 432869 Boiler over heat cut off assy 376 988 8 432868 DHW high limit control assy 313 024 9 900501 Piezo unit 382 585 9 900501 Piezo unit 384 146 10 800134 Pressure...

Страница 31: ...Supplied By www heating spares co Tel 0161 620 6677 31 221045A Diagram 5 1 9 20 23 19 11 10 22 18 2 21 14 26 24 15 6 16 12 5 3 4 8 7 13 17A 17B 5 S p a r e P a r t s 1 4610...

Страница 32: ...us to health The adhesives and sealants used in this appliance are cured and give no known hazard in this state INSULATION PADS CERAMIC FIBRE These can cause irritation to skin eyes and the respirator...

Отзывы: