background image

24

221129A

1 1   C o m m i s s i o n i n g

11.5 Burner Pressure - Hot Water -
Honeywell

The burner pressure is factory preset and no adjustment
should be required.

Connect the electrical supply; the pump and fan will
operate for about 30 seconds, then the fan will reduce
speed and the pump stop.

Relight the pilot burner.

Fully open the largest hot water draw off tap whereby
the main burner will light, the flames gradually
increasing to the maximum.

Check the soundness of the boiler gas joints, with the
main burner on, using a leak detection fluid.  Take care
not to splash any of the electrical components.

Fully open the hot water throttle, (clockwise), see
diagram 11.5.  Check that the water flow rate is not less
than 9Litre/min. (2.0gall/min) to prevent any modulation
of the gas pressure.  This is equivalent to 6.7 seconds to
fill a 1Litre container (3.8 seconds for 1pint).

To achieve this flow rate a water pressure of at least
0.8bar is required during commissioning, although
subsequently the appliance will work at a minimum
pressure of 0.5bar.

This flow rate should prevent any modulation of the
gas pressure.

Check the burner pressure is /-0.35mbar
(+/-0.14in wg). of 15.7mbar (6.3in wg), the hot water
burner pressure.  If this is incorrect, the burner pressure
may be adjusted to the correct setting by turning the hot
water gas pressure adjuster (potentiometer), using an
insulated screwdriver, see diagram 11.6.  Gain access to
the adjusters on the control board by removing the
control housing cover, see diagram 10.1.  Turn the
adjuster slowly, always making adjustment by reducing
below the required pressure then increasing up to the
required setting, (turn clockwise to increase).

Close the hot water draw off.

If the maximum pressure cannot be obtained, check that
the gas supply of adequate size, refer to Section 1.8.

11.5 Burner Pressure - Hot Water - SIT

The burner pressure is factory preset and no adjustment
should be required.

Connect the electrical supply.

Relight the pilot.

Turn gas control knob “D” to “

 “, main burner

position.

Fully open the largest hot water draw off tap whereby
the main burner will light, the flames gradually
increasing to the maximum.

Check the soundness of the boiler gas joints, with the
burner lit, using a suitable leak detection fluid.  Take
care not to splash any of the electrical components.

Fully open the hot water throttle, (clockwise), see
diagram 11.5.  Check that the water flow rate is not less
than 9Litre/min (2.0gall/min) to prevent any modulation
of the gas pressure.  This is equivalent to 6.7 seconds to
fill a 1Litre container (3.8 seconds for 1pint).

To achieve this flow rate a water pressure of at least
0.8bar is required during commissioning, although
subsequently the appliance will work at a minimum
pressure of 0.5bar.

This flow rate should prevent any modulation of the gas
pressure.

Check that the burner pressure is 16.1mbar +/- 0.35mbar
(6.5in wg +/- 0.14wg)  If this is incorrect, the burner
pressure may be adjusted by turning the larger brass
adjusting nut of the modulator, anti-clockwise to
decrease, after removing the cap, see diagram 11.2.

Fine adjustment may be achieved by turning the hot
water gas pressure adjuster (potentiometer), using an
insulated screwdriver, see diagram 11.6.  Gain access to
the adjusters on the control board by removing the
control housing, see diagram 10.1.

Turn the adjuster slowly, always making adjustments by
reducing below the required pressure then increasing up
to the required setting, turn clockwise to increase.

Close the hot water draw off.

If the maximum pressure cannot be obtained, check that
the gas supply is of adequate size, refer to Section 1.7.

Содержание swift flow 75

Страница 1: ...I2H Appliance Hepworth Heating Ltd Nottingham Road Belper Derbyshire DE56 1JT General Sales enquiries Tel 01773 824141 Fax 01773 820569 One Contact Total Service Customer Services Tel 01773 828100 Fax...

Страница 2: ...E Diagram 1 2 C H MAX D H W MAX MIN NOMINAL kW HEAT INPUT Btu h NOMINAL kW HEAT OUTPUT Btu h BURNER mbar PRESSURE in wg APPROX m3 h GAS RATE ft3 h TABLE 1 18 2 62 030 27 5 93 750 10 6 36 167 16 1 55 0...

Страница 3: ...n voltage limits 3 Directive 89 336 EEC on the approximation of the Laws of the Member States relating to electromagnetic compatibility This boiler will be fitted with either a Honeywell or SIT Gas Va...

Страница 4: ...be used provided they are not used in a room containing a bath or shower The mains supply cable and other cables connected to the boiler must be the PVC flexible type of at least 0 75mm2 24 0 20mm 2 1...

Страница 5: ...ssible directions Rearward left or right The standard flue is able to provide the duct length range shown in diagram 3 1 for a rear flue or diagram 3 2 for a side flue If a longer flue duct is require...

Страница 6: ...38130 2 off 1 off 1 off MAX FLUE LENGTH X Y Z 600mm Diagram 3 5 230 MIN 194 MIN Part No 448468 1 off Part No 448491 FLUE KIT 1m 1 off Part No 448490 FLUE BEND KIT FLUE KIT 2m ELBOW TERMINAL PACK Part...

Страница 7: ...minal or the terminal could be subject to damage If a terminal guard is required it must be positioned to provide a minimum of 50mm clearance from any part of the terminal and be central over the term...

Страница 8: ...FERENTIAL AT VARIOUS SYSTEM HEATING LOADS M 4 H e a t i n g S y s t e m Diagram 4 1 Diagram 4 1A 5947 5948 GRUNDFOS WILO AVAILABLE PUMP HEAD SYSTEM DIFFERENTIAL TEMPERATURE SYSTEM HEATING LOAD 0 5 10...

Страница 9: ...m the required system differential temperature axis to intersect the curve In the example 11o C 19 8o F has been chosen shown At the point of intersection draw a vertical line to cross the pump curve...

Страница 10: ...imum The bypass must have a lockable valve B in diagram 4 2 incorporated in a position so that inadvertent closure or unauthorised interference is not possible The bypass MUST be fitted before any sys...

Страница 11: ...ler whether or not adding an inhibitor 4 11 Draining A draining tap must be provided at the lowest points of the system which will allow the entire system to be drained An additional draining tap MUST...

Страница 12: ...e diagram 6 1 Remove the two screws securing the outer case and then lift it at the top and pull it forwards and off Remove the cover of the inner case secured with four screws see diagram 6 2 Disconn...

Страница 13: ...ternal corner where the flue is required to exit to outside Mark the position of the circular hole on the flue exit wall using the dimensions given in diagram 6 5 From the flue position marks check th...

Страница 14: ...iagram 3 3 for a 1 2 or 3metre flue system For a side flue measure the distance from the outside wall face to the side of the boiler mounting frame Check that the flue length will be suitable see diag...

Страница 15: ...ect distance from the outside wall face see diagram 7 1 and appropriate diagram 7 2 or 7 3 Drill a hole diameter as shown in diagram 7 4 in each side of the air duct through the holes in the flue elbo...

Страница 16: ...iler mounting frame will clear the expansion vessels If necessary temporarily fit the boiler refer to Section 10 1 Mounting the Boiler Flush out the domestic water and heating system before connecting...

Страница 17: ...ON It is ESSENTIAL to make sure that the polarity is correct 9 2 Heating System Controls CAUTION To prevent an induced current from switching the central heating on when not required it is important t...

Страница 18: ...STAT 3 L N 2 1 3 AMP FUSE L N 240V 50Hz PERMANENT MAINS SUPPLY POTENTIAL FREE ROOM STAT NO FROST STAT TO BOILER RED LINK REMOVE WHEN CONNECTING SYSTEM CONTROLS 5 POLE CONNECTOR ON MOUNTING FRAME POTE...

Страница 19: ...e of the base using one of the securing screws see diagram 10 1 Fit the short discharge pipe to the safety valve using the nut and olive supplied loose see diagram 10 2 Extend the discharge pipe using...

Страница 20: ...de Fit the flue elbow to the top of the boiler see diagram 10 6 using the four screws supplied loose To assist with the location of the flue elbow into the fan outlet loosen the two wing nuts on the f...

Страница 21: ...illing the Heating System It is essential that a bypass is fitted in all installations 22mm o d minimum The bypass must have a lockable valves B in diagram 4 2 incorporated in a position so that inadv...

Страница 22: ...ensure that water flows through all parts of the boiler and air is not trapped in the boiler internal bypass Pressurise the system until the pressure is 1 5bar 21 5lbf in2 Check the heating system and...

Страница 23: ...the electrical supply the pilot flame may go out If this should happen wait four minutes then relight the pilot burner following the above lighting instructions but with the electrical supply connecte...

Страница 24: ...he maximum pressure cannot be obtained check that the gas supply of adequate size refer to Section 1 8 11 5 Burner Pressure Hot Water SIT The burner pressure is factory preset and no adjustment should...

Страница 25: ...tor cable and refit the cap Isolate the boiler from the electrical supply then reconnect the modulator cable and refit the cap 11 6 Gas Rate Modulation SIT The minimum gas rate is factory preset and n...

Страница 26: ...omponents SIT only Refit the piezo bracket 11 9 Temperature Settings The domestic hot water outlet and central heating flow temperatures are factory preset and sealed therefore cannot be adjusted The...

Страница 27: ...ight hand side of the clock timer Fit the outer case secure with the screws see diagram 6 1 Set the boiler and any remote heating control to the desired settings then close the door 11 12 Instruct the...

Страница 28: ...C FIBRE GLASSYARN MINERAL WOOL These can cause irritation to skin eyes and the respiratory tract If you have a history of skin complaint you may be susceptible to irritation High dust levels are usual...

Отзывы: