4

221460C

Instructions for Use

Safety Device

This appliance is fitted with a flue blockage safety device which
will shut down the appliance in the event of abnormal flue
conditions. This device is NOT a substitute for an independently
mounted Carbon Monoxide detector.

The safety device is reset, after three minutes by pushing in the
button “ F ” shown in diagram 3.

Note: The pilot will stay alight but the device must be reset.

Shut down can occur during certain climate conditions, but if it
recurs the chimney flue and air inlet into the room must be
checked and any problems found corrected by a competent
person, before the boiler is used again.

Lighting the Boiler

CAUTION

If the pilot flame goes out, either intentionally or by accident, no
attempt should be made to relight for at least three minutes.

Slide the controls cover off and clear, see diagram 2.

Make sure that the electrical supply to the boiler is switched off.

Identify the controls by referring to diagram 3.

Turn the control thermostat knob “A” fully anticlockwise to the
“OFF” position.

Push and hold in gas control knob “B”.  Push and release igniter
button “C” until the pilot burner lights, look through window “D”.
When the pilot is alight keep gas control knob “B” pushed in for
about 15 seconds and then release.

If the pilot does not light or fails to stay alight, wait three minutes
and repeat the lighting operation, only this time keep knob “B”
pushed on for a little longer.

The flue blockage safety device may also need resetting, refer
to safety  device instructions.

Make sure that the pilot is alight and stable.

Switch on the electrical supply to the boiler.

Check that all external controls are calling for heat.

Turn control thermostat knob “A” fully clockwise to “MAX” and

the main burner will light fully in about three to five seconds, look
through window “D”.

If the main burner does not light, the flue blockage safety device
may need resetting, refer to Safety Device instructions.

Adjust the control thermostat knob to the desired setting between
“MIN” and “MAX”.  “MAX” is about 82

o

C (180

o

F).

Replace controls cover.

To Turn the Boiler Off

For short periods, turn control thermostat knob “A” anticlockwise
until “O” is against the setting point.  The pilot will stay alight, to
relight the main burner turn control thermostat knob “A” clockwise
to the desired setting between “MIN” and “MAX”.

For longer periods, turn the control thermostat knob “A”
anticlockwise until “O” is against the setting point.  Slide gas
control knob “B” to left and release, the control will automatically
reset.  Switch off the electrical supply.

To relight, follow the full lighting procedure given above.

Cleaning

WARNING.  This appliance contains metal parts (components)
and care should be taken when handling and cleaning, with
particular regard to edges.

Clean the casing by wiping it over occasionally with a wet cloth
or dry polishing duster.

Do not use abrasive cleaners.

Diagram 2

CONTROLS
COVER

2391

BOILER
CONTROLS

Diagram 3

A

D

C

MODEL AND
SERIAL
NUMBER
PLATE

F

A. CONTROL THERMOSTAT KNOB
B. GAS CONTROL KNOB
C. IGNITER BUTTON
D. VIEWING WINDOW
F. FLUE BLOCKAGE SAFETY DEVICE
    RESET BUTTON

B

5354

Содержание economy plus c 30

Страница 1: ...Customer Service number 01773 828100 Our Guarantee gives you peace of mind plus valuable protection against breakdown by covering the cost of Guarantee Registration Open Flue Boiler This is a Cat I2H...

Страница 2: ...uels 2 Directive 73 23 EEC on the harmonization of the Laws of the Member States relating to the electrical equipment designed for use within certain voltage limits 3 Directive 89 336 EEC on the appro...

Страница 3: ...freezing up If an immersion heater is fitted in the domestic hot water cylinder make sure that it is switched off If you have a sealed water system you should contact your installer servicing company...

Страница 4: ...ckage safety device may also need resetting refer to safety device instructions Make sure that the pilot is alight and stable Switch on the electrical supply to the boiler Check that all external cont...

Страница 5: ...ons applicable in Scotland local Water Company Byelaws The HealthandSafetyatWorkAct ControlofSubstancesHazardous to Health The Electricity at Work Regulations and any local applicable regulations Deta...

Страница 6: ...VC flexible type to the current issue of BS6500 Table 16 not less than 0 75mm2 24 0 20mm 1 9 Draining Tap A draining tap must be provided at the lowest points of the system which will allow the entire...

Страница 7: ...moval of the boiler Where the boiler is fitted in a cupboard or compartment permanent high and low level ventilation must be provided The minimum ventilation areas required are given in Table A 2 2 Bo...

Страница 8: ...ations for the best product to use When installing a boiler in an existing system whether or not using an inhibitor take special care to drain the entire system including the radiators then thoroughly...

Страница 9: ...em that is the height of the highest point of the system above the expansion vessel The water capacity of the boiler is given in Section 1 3 7 Pressure Gauge A pressure gauge with a set pointer and co...

Страница 10: ...the domestic hot water cylinder Alternatively provision for make up can be made by using a filling loop 3 10 Filling a Sealed Water System Provision for filling the system at low level must be made T...

Страница 11: ...cable clamp When making connections make sure that the earth conductor ismadeofagreaterlengththanthecurrentcarryingconductors so that if the cable is strained the earth conductor would be the last to...

Страница 12: ...N L N BROWN BLUE GRN YEL GAS VALVE BROWN BROWN RED RED PURPLE BLUE BROWN BLUE GRN YELLOW CHASSIS EARTH POST 3 7 6 8 9 Remove Red Link between 9 and SL when fitting a time control etc If link is not re...

Страница 13: ...R BUTTON G VIEWING WINDOW H GAS RATE ADJUSTMENT SCREW UNDER COVER SCREW J GAS SERVICE COCK K PRESSURE TEST POINT L PILOT BURNER ADJUSTMENT SCREW M FLUE BLOCKAGE SAFETY DEVICE RESET SWITCH M Diagram 6...

Страница 14: ...ice or replacing parts isolate the gas and electrical supplies Unless stated otherwise all parts are replaced in the reverse order to removal 7 1 Heating Body Service Remove the controls cover by pull...

Страница 15: ...ctor manifold Diagram 7 2 ACCESS FOR SERVICING Diagram 7 3 PILOT ASSEMBLY PILOT INJECTOR ADAPTOR OLIVE PILOT TUBING NUT THERMOCOUPLE NUT IGNITION LEAD clear end ELECTRODE THERMOCOUPLE SECURING SCREWS...

Страница 16: ...ownindiagram 7 7 Check the pilot burner flame lengths are as shown in diagram 7 7 7 5 Thermocouple Generally follow the instructions given in Section 7 1 Unscrew the thermocouple nut to release from t...

Страница 17: ...ithdraw the phial see diagram 7 8 Remove the control box by undoing the two fixing screws at the front and lower the front of the box until it is clear of the cover Push the box towards the rear of th...

Страница 18: ...ew s Inset B Carefully remove phial and capillary through back of boiler Inset C Having opened control box remove the electrical connections from the flue blockage safety device the locknut and capill...

Страница 19: ...on maximum control thermostat setting Change faulty overheat cutoff device The correctly set overheat cutoff device operates prematurely There is no air in the heating body and water circulation satis...

Страница 20: ...continuity YES NO NO 8 7 Thermocouple and Overheat Cutoff Device To test the thermocouple a meter with a range of 0 to 30 mV is required Symptom The pilot burner fails to stay alight Test the thermoc...

Страница 21: ...Device if faulty repair or renew Turn ON thermostat Does main burner light Turn ON thermostat With appliance cold Is there 240V between 7 and N Turn ON thermostat Is there 240V between 7 and N MAIN T...

Страница 22: ...ONTROLS IN ORDER Faulty Cable PURPLE between thermostat and terminal block repair or renew Faulty pump inform customer Faulty thermostat renew YES YES YES NO NO NO YES Continued Continued MAIN TERMINA...

Страница 23: ...TISFACTORY Does pilot flame envelop thermocouple Check aeration If necessary Clean pilot rectify blockage in pilot injector or replace Check thermocouple circuit using Thermocouple and Boiler Overheat...

Страница 24: ...cutoff device 313 064 5 800015 Gas valve assembly inc 14 313 067 6 900000 Thermocouple 394 162 7 203415 Pilot burner inc 12 394 161 8 202600 Electrode 384 149 9 416144 Control thermostat knob 355 401...

Отзывы: