13 Fault Finding
13.1 Preliminary fault
fi
nding
The following checks should be performed before proceeding
onto speci
fi
c diagnostics:
• Check the external electrical supply to the boiler is on and
a supply of 230V is present at the ‘L’ and ‘N’ terminals at
the installer interface.
For access remove and open the electrical cartridge, see
diagrams 10.3. and 10.1.
Test at the ‘L’ and ‘N’ terminals on the installer interface,
refer to diagrams 10.2 and 13.4.
• Check the electrical installation and appliance, carry
out tests for earth continuity, polarity, short circuit and
resistance to earth, using a suitable multimeter.
An aid to test
Remove the front casing panel, see diagram 13.1 and
hinge down the control box.
Unclip the rear cover to gain access to the main PCB.
Carry out the tests at connector plug X17, see diagram
13.2. Check chassis earth at a bare metal point on the
boiler.
• Check that there is a gas supply to the boiler and the gas
service isolation valve is turned on, see diagram 8.1.
• Check pressure at the gas service isolation valve, refer to
section
13.4.
• Check that the heating system pressure indicates at least
1mb, if not,
fi
ll and vent the system as described in section
13.2.
• Check that all external controls are on.
• Check the functional
fl
ow diagram, 13.5.
13.2 Fault Codes
Fault codes take priority over all other display functions in the
event of a fault occuring, refer to diagram 13.6.
If multiple faults occur the codes will be displayed for approx.
2 seconds, alternatively.
13.3 Fault Memory
The Fault memory stores details of the ten most recent faults.
To access this menu, refer to diagram 13.3:
a) Press and hold ‘MODE’ and ‘-’ buttons for 5 seconds.
b) The display will stop
fl
ashing and alternate between the
fault memory number and the fault code.
c) Press ‘+’ button to scroll through the fault memory
(Position 1 is most recent), see fault codes.
To exit this menu, press the ‘MODE’ button.
13.4 Diagnostic Menu
The Diagnostic Menu provides the ability to view and
change certain parameters. See diagram 14.8 for available
parameters.
13.5 Status Codes
The status codes provide information about the current
operating condition of the boiler and can be accessed through
the diagnostic display, refer to diagram 13.7.
14028
Diagram 13.3
Diagram 13.2
13845
14291
Diagram 13.1
Содержание 12hx
Страница 7: ...0020107230_04 12 14 Glow worm TECHNICAL DATA 7 14730 1 Boiler Specification ...
Страница 23: ...0020107230_04 12 14 Glow worm INSTALLATION 23 15826 Diagram 9 2 ...
Страница 34: ...0020107230_04 12 14 Glow worm MAINTENANCE 34 13917 Diagram 13 4 ...
Страница 35: ...0020107230_04 12 14 Glow worm MAINTENANCE 35 13012 Diagram 13 5 ...
Страница 50: ......
Страница 51: ......