CARE AND MAINTENANCE

INSTALLATION

Step 1. 

Install pendent sprinklers in the pendent 

position, with the centerline of the sprinkler 

perpendicular to the mounting surface.

Step 2. 

Remove the Protective Cap.

Step 3. 

With pipe-thread sealant applied to the pipe 

threads, and using the Concealed Sprinkler 

Wrench P/N 325391 (FIGURE 2), install and 

tighten the Sprinkler/Concealed Cup Assembly 

into the fitting.

Step 4. 

Replace the Protective Cap by pushing it 

upwards until it bottoms out against the Sup-

port Cup. The Protective Cap helps prevent 

damage to the Deflector and Drop Pins during 

ceiling installation and/or during application of 

the finish coating of the ceiling.

 

NOTICE: 

The system is considered Out of Service when 

the protective caps are in place.

Step 5. 

After the ceiling has been completed with the 

2-1/2” (63.2mm) diameter hole, remove and 

discard the Protective Cap and verify that the 

Deflector moves up and down freely. If the 

sprinkler has been damaged or the deflector 

does not move up and down freely, replace 

the entire sprinkler assembly. Do not attempt 

to modify or repair.

Step 6. 

Push on the Cover Plate Assembly until its 

flange contacts the ceiling. Never attempt to 

screw on the Cover Plate Assembly such that 

it lifts a ceiling panel out of its normal posi-

tion. If the Cover Plate Assembly cannot be 

engaged with the Mounting Cup or the Cover 

Plate Assembly cannot be engaged sufficient

-

ly to contact the ceiling, the Sprinkler Fitting 

must be repositioned.

Always obtain permission from the proper authorities to 

shut down the affected fire protection system and notify all 

personnel who may be affected by this action before closing 

a fire protection system main control valve for maintenance 

work on the system that it controls. Sprinklers should only 

be cleaned by means of gently dusting with a feather dust-

er; otherwise, non-operation in the event of a fire or inadver

-

tent operation may result.
When properly installed, there is a nominal 1/8” (3mm) air 

gap between the Cover Plate and the ceiling (Figure 1). This 

air gap is necessary for proper operation of the sprinkler by 

allowing heat flow from a fire to pass below and above the 

Cover Plate to help assure appropriate release of the Cover 

Plate in a fire situation. This annular “gap” must be main

-

tained and should never be sealed or caulked.
Factory painted Cover Plates must not be repainted.
In accordance with NFPA 25, Sprinklers which are found to 

be leaking or exhibiting visible signs of corrosion must be 

replaced.
Automatic sprinklers must never be painted, plated, coated, 

or otherwise altered after leaving the factory.
Care must be exercised to avoid damage to the sprinklers–

before, during, and after installation. Sprinklers damaged 

by dropping, striking, wrench slippage, or similar incidents, 

must be replaced.
The owner is responsible for the inspection, testing, and 

maintenance of their fire protection system and devices in 

compliance with this document, as well as with the appli-

cable standards of the National Fire Protection Association 

(e.g. NFPA 25), in addition to the standards of any other 

authorities having jurisdiction.
Refer to Globe’s Residential Installation Guide for further 

Care and Maintenance information.

TABLE B:  ESCUTCHEONS

DOMED COVER PLATE 

SIZE

WHITE 135°F (57°C)

P/N

CHROME 135°F (57°C)

P/N

BLACK 135°F (57°C)

P/N

CUSTOM 135°F (57°C)

P/N

3-5/16” DIA

.

326048

326046

326048-B

326049

FIGURE 2:  CONCEALED WRENCH 

P/N 325391

NOTICE

Do  not  install  any  bulb-type  sprinkler  if  the  bulb  is  cracked  or 

there is loss of liquid from the bulb. Sprinklers should be tightened 

enough to obtain a leak-tight joint when water pressure is applied 

and/or  hydrostatic  test  is  performed.  Sprinklers  should  not  be 

overtightened as this can result in distortion and subsequent leak-

age. It is recommended not to exceed 14 ft.-lb. (19.0 Nm) torque 

for 1/2 inch NPT sprinkler threads.