DESIGN CRITERIA

The Globe Series GL-RES/DC Sprinkler is cULus Listed for 

installation in accordance with this data sheet as well as the 

applicable installation Standard being utilized.

Globe Residential Sprinkler Installation Guide

When conditions exist that are outside the scope of the pro-

vided criteria, refer to the Globe Residential Sprinkler Instal-

lation Guide (Document GFS-380) for recommendations 

that may be acceptable to the authority having jurisdiction.

Hydraulic Design (NFPA 13D and 13R)

For systems designed to NFPA 13D or NFPA 13R, the min-

imum required sprinkler flow rate is given in Table A for the 

coverage areas shown. The sprinkler flow rate is the min

-

imum required discharge from each of the total number of 

“design sprinklers” as specified in NFPA 13D or NFPA 13R.

Hydraulic Design (NFPA 13)

The minimum required discharge from each design area 

sprinkler shall be the greater of the following:

 (1) 

In accordance with minimum flow rates indicated in 

TABLE A.

 (2)  In rooms or compartments greater than 800 ft

2

  

(74.3 m

2

), calculated based on delivering a minimum 

of 0.1 gpm/ft

2

 (4.1 mm/min) over the coverage area of 

each sprinkler, calculated in accordance with the 

S x L Rules for density area sprinklers.

 (3)  In rooms or compartments 800 ft

2

 (74.3 m

2

) or less 

(Defined as “Small Rooms”) calculated based on

 de-

livering a minimum of 0.1 gpm/ft

2

 (4.1 mm/min) over 

the room or compartment using the area of the room 

divided by the number of sprinklers in the room. (7 psi 

minimum)

SIN

K-FACTOR 

GPM/PSI

½

 

 (lpm/bar

½

)

MAX.AREA OF 

COVERAGE

 

FEET (m)

MINIMUM 

PRESSURE

 

PSI (bar)

MINIMUM 

FLOW

 

GPM (L/min.)

DEFLECTOR TO CEILING/ 

 MOUNTING SURFACE 

DISTANCE

 

INCHES (mm)

MINIMUM 

DISTANCE 

BETWEEN 

SPRINKLERS

 

FEET (m)

GL4147

4.1

(59)

12 (3.7) x 12 (3.7)

7.2 (.50)

11 (42)

Smooth Ceilings

1/8 (3) to 5/8 (16) Max.

Beamed Ceilings - Adjacent

 

Allowed in ceiling. 

 

Beamed Ceilings - In Beam

4” Maximum Beam Depth

1/8 (3) to 5/8 (16) Max.

8 (2.4)

14 (4.3) x 14 (4.3)

13.4 (.92)

15 (57)

16 (4.9) x 16 (4.9)

13.4 (.92)

15 (57)

GL4947

4.9

(70.6)

12 (3.7) x 12 (3.7)

7.0 (.48)

13 (49)

14 (4.3) x 14 (4.3)

8.2 (.57)

14 (53)

16 (4.9) x 16 (4.9)

8.2 (.57)

14 (53)

18 (5.5) x 18 (5.5)

12.0 (.83)

17 (64)

20 (6.1) x 20 (6.1)

16.7 (1.15)

20 (76)

TABLE A:  NFPA 13, 13R, AND 13D 

HYDRAULIC AND INSTALLATION DESIGN CRITERIA

FIGURE 1:  1/2” ADJUSTMENT DOMED PLATE 

CONCEALED PENDENT

NOTE:

  

Deflector-to-Ceiling Distance Criteria reflects 2019 Edition of NFPA 13D and 13R.