Globe GL-RES/DC Series Скачать руководство пользователя страница 1

APRIL 2019

GFS-350

PAGE    1  of  4       

SERIES GL-RES/DC

RESIDENTIAL ADJUSTABLE

DOME CONCEALED PENDENT

K-FACTOR 4.1, 4.9

TECHNICAL DATA

Approvals

• 

cULus - EU

Temperature Rating

• 

Sprinkler: 155°F (68°C)

• 

Cover Plate: 135°F (57°C) 

K-Factor

• 

GL4147 K4.1 gpm/psi½    

(

59.0 lpm/bar½

)

• 

GL4947 K4.9 gpm/psi½    

(

70.6 lpm/bar½

)

Cover Plate Finishes

• 

Chrome/White Painted/Black Painted/Custom 

(For Custom Plates, contact Customer Service) 

Caution: Cover Plates must have factory applied finishes. 

Never paint/coat plates in field.

Thread Size

• 

1/2” NPT (15mm)

Length

• 

2-7/32” (5.6cm)

Maximum Working Pressure

• 

175 psi (12 bar)

Materials of Construction

• 

Frame - bronze 

 Deflector - brass 

 Screw - brass

• 

Lodgement Wire - stainless steel 

 Bulb seat - copper 

• 

Spring - nickel alloy 

 Seal - teflon

• 

Bulb (3mm) - glass 

• 

Cover Plate - brass 

 Upper Escutcheon Assy. - carbon-

steel 

4077 Airpark Dr. Standish, MI  48658 • 989-846-4583 • 

www.globesprinkler.com

Technical Support 

 989-414-2600

 

 

[email protected]

NOTE

:

 

Users should refer to Globe’s web site (www.globesprinkler.com) 
to assure that the most recent technical literature is being utilized.

GENERAL DESCRIPTION

The GL-RES/DC Domed Concealed pendent sprinkler is 

a decorative fast response glass bulb sprinkler specifically 

tested and Listed for use in residential applications such 

as homes, apartments, hotels, and dormitories to provide 

control  of  these  residential  type  fires  and  to  improve  the 

chance for occupants to escape. These sprinklers utilize 

a 3mm frangible glass bulb as its heat sensing operating  

element. The GL-RES/DC is available with a K-Factor of 4.1 

(GL4147) and a K-Factor of 4.9 (GL4947) and offer a further 

level of aesthetic appeal compared to semi-recessed type 

sprinklers.
These sprinklers provide a total vertical adjustment of a 

nominal 1/2”. This sprinkler may be installed within dwelling 

occupancies as allowed by NFPA 13, 13D, 13R and any 

other related documents as appropriate.

OPERATION

The soldered cover plate drops off the retainer assembly 

when  exposed  to  heat,  as  from  a  fire,  that  has  reached 

the plate’s Listed temperature rating, exposing the sprin-

kler above. As heat encompasses the glass bulb operating  

element of the sprinkler, the fluid in the bulb expands, com

-

pressing the air bubble within the bulb. When the air bubble 

can no longer compress, the fluid expansion causes break

-

age of the glass bulb, resulting in release of the water seat  

assembly and discharge of water from the sprinkler.

SERIES GL-RES/DC

GL4147, GL4947