Metis micro user manual v1.6
17
6.6 Grouping
6.6 Grouping
6.6 Grouping
6.6 Grouping
All alarms are sent input-specificly to selected numbers. The phone numbers are defined
inside the parenthesis, separated by commas. In order to use grouping, one must know
which number is stored in which slot in the phonebook.
Setting format:
(61=a,b,c,...)
(61=a,b,c,...)
(61=a,b,c,...)
(61=a,b,c,...) ;input 1 grouping
(62=a,b,c,...)
(62=a,b,c,...)
(62=a,b,c,...)
(62=a,b,c,...) ;input 2 grouping
a,b,c,...
a,b,c,...
a,b,c,...
a,b,c,... = memory slot in the phonebook
Example: (62=4,5,6)
(62=4,5,6)
(62=4,5,6)
(62=4,5,6)
Alarms from input 2 are sent only to numbers 4,5 and 6 in the phonebook.
6.7 Restoring factory settings
6.7 Restoring factory settings
6.7 Restoring factory settings
6.7 Restoring factory settings
The factory defaults of me
me
me
me
tis
tis
tis
tis
Micro
Micro
Micro
Micro can be restored with a jumper block (see 9 –
Connectors)). When the device is started with the jumper block in place, the factory
settings are restored.
6
6
6
6....8
8
8
8 Alarm output
Alarm output
Alarm output
Alarm output
Alarm (siren) output is active for 20 seconds during an alarm as a default. This setting
determines the inputs that activate the siren output and also gives the possibility to change
the output active time.
Example:
(89=a,b
(89=a,b
(89=a,b
(89=a,b,...
,...
,...
,...))))
a
a
a
a = siren active time (0=20 seconds, 1-9=active time in minutes)
b
b
b
b = activating inputs (1-2)
Example: (89=5,2)
(89=5,2)
(89=5,2)
(89=5,2)
The siren output is active for 5 minutes during an alarm, but only the alarm of input 2.
Input 1 in this case won’t activate the output.