NOTE:
Verify panel software version by looking at number on the sticker placed on the SIMM card.
SAM's cannot operate or be programmed when installed within loops associated with old
Sub-Panel versions (i.e. that do not include a SIMM card and socket)
54
INSTALLATION & COMMISSIONING MANUAL - REVISION 1.0 - 19.FEB.2007
CONTENTS
6-4 Automatic Address Setting (ASET) -
Wizmart Protocol only
Introduction
Automatic Address Setting (ASET) is a special install and commissioning mode that can be activated
on a per loop basis whilst in INSTALLATION mode. ASET mode is only required if Soft Addressable
Modules (SAM's) are used in the fire protection system. Soft Addressable Modules (SAM's) do not
have their addresses set using switches. They automatically assign their own addresses and ASET
mode is used to achieve this.
Because ASET mode requires manual triggering of each device (using the standard test procedure for
each one) the installer can effectively choose the address for each detector and simultaneously program
and test each device.
SAM'S CAN BE MIXED WITH OTHER TYPES OF DEVICES ON THE SAME LOOP. Each time a SAM is
programmed it takes the next free address on its loop.
General Guidelines
SAM's can only be used in conjunction with the following Wizmart Protocol panels:
a) Juno Net
b) Junior
c) Sub panel (incorporating SIMM module & socket).
Before starting the programming procedure, care should be taken with the following:
a) Supply OK.
b) Auxiliary Supply (Batteries) OK.
c) Loop Supply OK.
d) Verify the non-existence of earth current leakage.
e) Verify the cable lengths for the loop.
f) Confirm the non-existence of short or open circuits within the loop.
g) Verify communications with standard analogue addressable devices is OK.
h) Verify communications between Panel, and Repeaters with integrated Sub-Panel.
Verify that all SAM connections, both to the loop and the associated conventional device (i.e. smoke
sensor/ detector, call point, etc.) are properly made and that the conventional device connections follow
the manufacturer's instructions, in particular those regarding polarity. Reversal of the supply polarity can
cause failure or malfunction and prevent a SAM from being programmed.
CAUTION
Reset to normal operation all devices before applying power to the panel, in
particular manual call points
Verify that there are no faults or fire conditions in the loop or system.
Clear all fault and fire conditions first.