6 Device Set-up
Allows specific settings to be selected for individual Analogue Loop devices.
6-1 General
Settings common to all types of Analogue Loop devices.
6-1-1 Disable Loops
Allows a specific Analogue Loop to be disabled or enabled. The default is enabled.
All devices on the disabled loop will cease to operate with the exception of the (audible) output from loop
sounders.
If the loop is disabled it will be indicated when programming mode is exited. It can be reviewed using the
DISABLED (QUEUE REVIEW) button.
6-1-2 Device Disable
Allows a specific device to be disabled or enabled. The default is enabled.
Disabled devices have both inputs and outputs disabled.
This function does not disable the (audible) output from loop sounders.
Any devices that are disabled will also be indicated when programming mode is exited. They can then be
reviewed using the DISABLED (QUEUE REVIEW) button.
6-1-3 Set Selective Disablement
Allows a specific device to be set up for selective disablement.
The device is only disabled when the SELECTED DETECTORS (DISABLEMENTS) button on the front panel
is activated.
This function is intended for use when certain detectors regularly need disabling but are not necessarily in
the same Zone.
Outside programming mode any devices that are currently disabled can then be reviewed using the
DISABLED (QUEUE REVIEW) button.