FAULTS 

 

SUPPLY FAULT

 - This LED will be ON whenever the Main Supply has been removed or has dropped below 20 Volts.  

BATTERY FAULT

 - Indicates that there is low voltage level on the batteries or the battery charger circuit has failed.  

AUX SUPPLY FAULT

 - Indicates that the Auxiliary Supply has a fault.  

EARTH FAULT

 - When this indicator is ON there is leakage current flowing from the earth connection/ wiring and any 

conductor incoming into the panel. 
 

CONTROLS 

 

(1) BUZZER SILENCE

 - At Access Level 1 this button is used to silence the panel's internal buzzer.  

To access Level 2 the 

Buzzer must be silenced 

(2) RESET

 - Press this button to reset the panel at access Level 2.  

(3) LAMP TEST

 - Press this button at access level 1 or 2 to test all LED indicators and the panel's internal buzzer. Release 

when test is finished.  

(4) SOUNDERS

 - Only on Level 2 access, press once to activate/silence sounders. If sounders are active (previously 

pressed), by pressing this button again will stop the sounders. Auxiliary Fault Relays is not affected by this action.  
 

NOTE: 

When reset, all LEDs will flash and relays will pulse. 

 

DISABLEMENTS 

 
These buttons are only active at Level 2 access.  
 
These buttons have a toggle action. One press will disable the particular action and another press will re-enable it.  
 
When a particular function is disabled, its associated LED will be activated. 
 

OUTPUTS AUXILIARY

 - Use  this button to disable or re-enable auxiliary relays (Fire and Fault).  

 

DISABLE SOUNDER

 -  Use this button to disable or re-enable Conventional sounder circuit (S1). 

 

Internal Addressable Interface (ADLI-BCM) 

 
ORION-BCM LSC occupies two consecutive addresses on the addressable loop, each one reporting as follow: 
 

-

Address programmed in DIL switch is recognized as a SOUNDER 

-

Addressing range must be between 94 and 125.   

-

Previous address is automatically assigned as an I/O. 

 
Example: If DIL-Switches are all set to OFF (address 94), address 93 will be automatically assigned as an I/O unit, while 
address 94 will be recognized as a SOUNDER. 
 
 

Addressable Connection LED Status Information (ADLI-BCM) 

 

LED 

DESCRIPTION 

RED 

Indication of Sounder Circuit activation or Fault 

YELLOW 

Indication of Fault presence 

GREEN 

Indication (pulsing) each time address is pooled  

 

 

Содержание ORION-BCM LSC

Страница 1: ...ault detection and notification listed below In addition to local notification status is also reported to addressable system Sounder Circuit Integrity Fault Battery Charger Fault voltage level and cha...

Страница 2: ...voltage detector and sounder cabling The panel should be fixed to the wall using the 4 mounting holes provided and No 8 10 countersunk screws Any dust created during the fixing process must be kept o...

Страница 3: ...ng If a sounder circuit is not used the EOL resistor should be fitted in the control panel sounder output The sounder circuits are protected against short circuits the electronic fuse will reset when...

Страница 4: ...Connect it to C input for activation NOTE EV always activate S1 even if sounders are disabled CONNECTING THE PANEL The mains supply should be routed away from the other cables and enter the control pa...

Страница 5: ...re Relay and EV Sounder direct activation non monitored E Auxiliary Supply Output monitored Addressable Interface ADLI BCM Connections The following board is placed inside the box A DIL Switch for add...

Страница 6: ...indicate any FAULT condition present on panel DISABLED Used to indicate that the panel has features that have been disabled in Access Level 2 SUPPLY Used to indicate the presence of supply In Access...

Страница 7: ...unders Auxiliary Fault Relays is not affected by this action NOTE When reset all LEDs will flash and relays will pulse DISABLEMENTS These buttons are only active at Level 2 access These buttons have a...

Страница 8: ...Level 1 General user controls This lower level allows the user to Perform a lamp test Silence Internal buzzer Put the panel into Access Level 2 if in possession of the required access code Level 2 Aut...

Страница 9: ...test and confirm LEDs and internal buzzer operation 4 Test each key for correct functioning 5 Test all sounders relays etc for proper operation TESTING FIELD EQUIPMENT Testing Sounders 1 Introduce th...

Страница 10: ...fault is present when there is a voltage below 20 V DC at the battery terminals or if there is a battery charger problem Charger problems can be caused by panel s hardware failure or batteries that h...

Страница 11: ...y using two external independent switches on the inputs overlap the addressable order the Sounder Output or the Fire Alarm Relay state Example of application Door Holder This implementation has the ab...

Страница 12: ...ER CIRCUIT NUMBER OF CIRCUITS 1 END OF LINE RESISTOR VALUE 10K Ohms MONITORING Open and Short Circuit ALARM VOLTAGE 27 5V DC SOUNDER CIRCUIT FUSE 1 1 Amp resettable Electronic Fuse MAX CURRENT AVAILAB...

Страница 13: ...lsc_01_010001_en_180711 GLOBAL FIRE EQUIPMENT S A S tio dos Barrab s Armaz m Nave Y Caixa Postal 908 Z 8150 016 S o Br s de Alportel PORTUGAL Tel 351 289 896 560 Sales sales globalfire pt Technical Su...

Отзывы: