Global Fire Equipment //
globalfire.pt
ma_orionbcmlsc_01_010001_en_180711
FAULTS
SUPPLY FAULT
- This LED will be ON whenever the Main Supply has been removed or has dropped below 20 Volts.
BATTERY FAULT
- Indicates that there is low voltage level on the batteries or the battery charger circuit has failed.
AUX SUPPLY FAULT
- Indicates that the Auxiliary Supply has a fault.
EARTH FAULT
- When this indicator is ON there is leakage current flowing from the earth connection/ wiring and any
conductor incoming into the panel.
CONTROLS
(1) BUZZER SILENCE
- At Access Level 1 this button is used to silence the panel's internal buzzer.
To access Level 2 the
Buzzer must be silenced
(2) RESET
- Press this button to reset the panel at access Level 2.
(3) LAMP TEST
- Press this button at access level 1 or 2 to test all LED indicators and the panel's internal buzzer. Release
when test is finished.
(4) SOUNDERS
- Only on Level 2 access, press once to activate/silence sounders. If sounders are active (previously
pressed), by pressing this button again will stop the sounders. Auxiliary Fault Relays is not affected by this action.
NOTE:
When reset, all LEDs will flash and relays will pulse.
DISABLEMENTS
These buttons are only active at Level 2 access.
These buttons have a toggle action. One press will disable the particular action and another press will re-enable it.
When a particular function is disabled, its associated LED will be activated.
OUTPUTS AUXILIARY
- Use this button to disable or re-enable auxiliary relays (Fire and Fault).
DISABLE SOUNDER
- Use this button to disable or re-enable Conventional sounder circuit (S1).
Internal Addressable Interface (ADLI-BCM)
ORION-BCM LSC occupies two consecutive addresses on the addressable loop, each one reporting as follow:
-
Address programmed in DIL switch is recognized as a SOUNDER
-
Addressing range must be between 94 and 125.
-
Previous address is automatically assigned as an I/O.
Example: If DIL-Switches are all set to OFF (address 94), address 93 will be automatically assigned as an I/O unit, while
address 94 will be recognized as a SOUNDER.
Addressable Connection LED Status Information (ADLI-BCM)
LED
DESCRIPTION
RED
Indication of Sounder Circuit activation or Fault
YELLOW
Indication of Fault presence
GREEN
Indication (pulsing) each time address is pooled
7