background image

GFE-AD SERIES, 

Addressable Photoelectric Smoke, ROR & Fixed 
Temperature Heat Detector and Combined Smoke + Heat 
Detector 

Installation Wiring Diagram

TYPICAL WIRING DIAGRAM

When installed, terminals 4 and 6 are for connection of remote LED 

THE  GFE-AD  SERIES DETECT

THE  GFE-AD  SERIES DETECTORS  MUST BE CONNECTED 

TO A COMPATIBLE ANALOGUE ADDRESSABLE FIRE ALARM 

CONTROL PANEL.

THE  INSTALLATION  MUST  BE  IN  COMPLIANCE  WITH  THE 

CONTROL PANEL SYSTEM INSTALLATION MANUAL. 

WARNING 

TO 

PREVENT 

DETECTOR 

CONTAMINATION

AND

SUBSEQUENT

COVERED UNTIL THE AREA IS CLEAN AND DUST FREE

GENERAL DESCRI

TPTION 

GFE-AD series consists of: Photo electric smoke detectors, Rate of 

Rise and Fixed temperature detectors and combined smoke / heat 

detectors with advanced analogue addressable communications. DIP 

switches are provided for setting the detector’s address. 

GFE-AD-S:

Analogue addressable smoke detector

GFE-AD-S-L:

Analogue addressable smoke detector with remote LED

output 

GFE-AD-SH:

Analogue addressable smoke and rate-of-rise and fixed 

temperature heat detector

GFE-AD-SH-L:

Analogue addressable smoke and rate-of-rise and 

fixed temperature heat detector with remote LED output

GFE-AD-H:

 Analogue addressable rate-of-rise and fixed temperature 

heat detector

GFE-AD-H-L:

Analogue addressable rate-of-rise and fixed 

temperature heat detector with remote LED output

Note: The base model no. for GFE-AD-S, GFE-AD-SH and GFE-AD-H 

is P/N772912. The base model no. for GFE-AD-S-L, GFE-AD-SH-L and 

GFE-AD-H-L is P/N774912. 

INSTALLING THE BASE 

1.  To  insure  proper  fit  of  the  detector  head  to  the  base,  all  wires 

should be properly dressed at installation: 

(A) Position all the wires flat against terminals. 

(B) Fasten the wires away from connector terminals. 

2.  The  detectors  are  intended  for ceiling  or  wall  mounting  in 

accordance with 

local Fire authority recommendations. 

3. 

The  base  of  the  smoke  detector  can  be  mounted  directly  onto 

most standard electrical junction boxes without using any type of 

mechanical  adaptor.  For  surface  wired  installations  the  base 

adaptor P/N 882912 for two wire, P/N 

884912 for four wire

.

has cable entry points to accept standard 

electrical conduit.     

INSTALLING THE HEAD 

1. Set the desired address via DIP switch on the back of the detector, 

see ADDRESS SETTING section. 

2. Align the components as shown in Figure 2. 

3. Fit the detector head onto the base and twist clockwise to secure 

it. 

4. After all detectors have been installed, apply power to the  control

unit and activate the detection Loop. 

5. Test the detector(s) as described in the TESTING section of this 

manual.

Note: Do  not  install  the  detector  head  until  the  area  is 

thoroughly  cleaned  of  construction  debris, dusts, etc. Please 

refer to  control  panel  technical  information  regarding  the 

maximum number of detectors installed on the same loop

Fig. 2 Fitting detec

tor head onto base. 

Note Alignment marks

TESTING 

All  remote  signaling  systems,  releasing  devices  and  extinguishing 

systems  should  be  disconnected  during  the  test  period  and 

reconnected at the conclusion of testing. 

SMOKE SENSOR TESTING 

Allow  smoke  from  a  cotton  wick  or  a  test  smoke  aerosol  to  enter  the 

detector-sensing  chamber  for  at  least  10  seconds.  When  sufficient 

smoke  has  entered  the  chamber,  the  detector  will  signal  an  alarm,  this 

being indicated by illumination of the red LED. Make sure to clear smoke 

out

 of 

the chamber before resetting in order to keep the detector 

at its current sensitivity setting. 

HEAT SENSOR TESTING

The detector to be tested should be subject to a flow of warm air at 

a temperature of between 65°C and 80°C. (This requirement can 

be met by some domestic hair dryers). 

Proceed as follows: 

1. Switch on the warm airflow and check that temperature is 

LOOP