SMA5005 & SMA5015 MANUAL
MANUAL # 5005-2040-000-F UPDATED: 6/1/2021
H. Calibration Setup Record (SMA5015 Series)
It is good practice to keep a record of all the pot settings. Doing so will facilitate calibration on
future units and repair on this unit. Although not a substitute for the calibration procedure, it will at
least get you "in the ballpark." Remove the power and allow all capacitors to discharge before
taking measurements. Note: The balance pot should not be measured in this fashion, set per step
3 in the calibration procedure.
Note: Tach. voltage is measured at J1-5. Common for all measurements is at J1-4.
Date data taken:
/
/
Serial number S/N:
_________________________________
Model number:
SMA5015_________________________
Note any changes to components or any special features in the space below:
Pot/Dip-Switches
Drive
Differential Gain pot wiper
TP1 to common (ohms):
Signal Gain pot wiper
TP2 to common (ohms):
Tach. Gain pot wiper
TP4 to common (ohms):
Compensation pot wiper
TP5 to common (ohms):
Current Limit pot wiper
TP6 to common (ohms):