background image

7.0

SITE REQUIREMENTS

7.6

CONDENSATE DRAIN

NOTE: The appliance is fitted with a trap the depth of

which is >= 75mm, therefore no other traps are required in

the condensate run.

The condensation discharge pipe must not rise at any point

along its length. There MUST be a fall of AT LEAST 2.5° (50mm

per metre) along the entire run.

1. The condensate outlet will accept 21.5mm (

3

/

4

in) plastic

overflow pipe which should discharge internally into the

household drainage system, downstream of all other traps. if

this is not possible, discharge into an outside drain is

acceptable.

2. Ensure the discharge of condensate complies with any

national or local regulations in force.

BS 6798:2000 & Part HI of the Building Regulations give

further guidance.

3. Metal pipework is NOT suitable for use in condensate

discharge systems.

4. The pipe should be a minimum of 21.5mm diameter and

must be supported properly.

5. IIt is advisable to keep the condensate pipe internal.

6. E

External runs greater than 3 metres or runs in cold areas

should use 32mm waste pipe.

7. If the boiler is fitted in an unheated location the entire

condensate discharge pipe should be treated as an external

run.

8. In all cases discharge pipe must be installed to aid disposal

of the condensate.

9. When discharging condensate into a soil stack or waste pipe

the effects of existing plumbing must be considered. If soil

pipes or waste pipes are subjected to internal pressure

fluctuations when WC’s are flushed or sinks emptied then

back-pressure may force water out of the boiler trap and

cause appliance lockout.

Examples are shown of the following methods of

terminations:-

i) to an internal soil & vent pipe

ii) via and internal discharge branch (e.g. sink waste)

iii) to a drain or gully

iv) to a purpose made soakaway

10. In exceptional circumstances, such as when a boiler is

installed in a basement without drainage, it may be necessary

to install a condensate pump to carry condensate up to ground/

drain level. Such products are available from most plumbing

merchants. For help with selecting a condensate pump contact

Dimplex Boilers - Tel: 0844 3711121.

WARNING: There must be no air breaks in the condensate

pipework or drainage system.

16

© Dimplex Boilers 2008

50mm per metre of pipe r

un

2.5° Minimum fall

450mm min

Termination to an internal soil and vent pipe

50mm per metre of pipe r

un

2.5° Minimum fall

External termination via internal discharge branch

e.g sink waste - downstream

Sink

Pipe must terminate 
above water level but
 below surrounding surface.

50mm per metre of pipe r

un

2.5° Minimum fall

Termination to a purpose made soak-away

Holes in the soak-away must
face away from the building

500mm min

NOT ALLOWED

There should be 

no air gap

Fig. 14

Fig. 15

Fig. 17

Fig. 16

13.0

CHANGING COMPONENTS

13.3

GAS VALVE AND FAN

1. Disconnect the two leads to the fan and one lead to the gas

valve.

2. Undo the nut on the gas inlet pipe to the valve and retain

the sealing washer.

3. Remove the three securing screws holding the air/gas

Channel to the burner door plate and remove the valve and fan

assembly (Fig. 57).

4. Remove the three screws holding the valve and swirl plate

to the fan adaptor plate.

NOTE: Mark on the adaptor plate which holes are being

used by the screws. Using the wrong holes on 

re-assembly will cause mis-alignment of the gas valve.

Fan Only

6. Remove the three screws holding the fan adaptor to the fan.

7. Remove the four screws securing the fan to the air/gas

channel. Reassemble in reverse order ensuring all seals are in

place.

NOTE: The gas valve throttle should be adjusted in

accordance with the instructions supplied in the spares kit

See Section 10. 

© Dimplex Boilers 2008

33

NOTE: Dimplex Combi 38 will also be fitted with a black

plastic air cowl which encases the swirl plate.

Fig. 57

Swirl Plate

Fan

Fan Gasket

Burner Door

Air/Gas Channel

Fan Adaptor Plate

Injector Plate

Injector

Injector ‘O’ Ring

Gas Valve

48pp MANUAL SPREADS  19/10/10  08:36  Page 16

Содержание Combi 24

Страница 1: ...ES AND SERVICE HELPLINE 0844 371 1111 Glen Dimplex Boilers is continually improving its products and therefore reserve the right to change product specifications without prior notice Errors omissions excepted Glen Dimplex Boilers Stoney Lane Prescot Merseyside L35 2XW For all telephone enquiries call 0844 371 2222 website www glendimplexboilers com Part of the Glen Dimplex Group 48pp MANUAL SPREAD...

Страница 2: ...stem fully pumped Yes No Type of control system Y Plan S Plan Other 18 0 WARRANTY TERMS CONDITIONS 18 1 DIMPLEX 5YR WARRANTY 1 Registration must be completed within 30 days of installation Failure to return within 30 days will invalidate your warranty Registration if effected by returning the enclosed registration card to the commercial center of Dimplex at 5 Spartan Close Tachbrook Park Leamingto...

Страница 3: ...er Comments Signature SERVICE 6 Date Engineer Name Company Name Telephone Number Comments Signature SERVICE 7 Date Engineer Name Company Name Telephone Number Comments Signature SERVICE 8 Date Engineer Name Company Name Telephone Number Comments Signature SERVICE 9 Date Engineer Name Company Name Telephone Number Comments Signature SERVICE 10 Date Engineer Name Company Name Telephone Number Commen...

Страница 4: ...HECKLIST l l A installations in England and Wales must be notified to Local Authority Building Control LABC either directly or through a Competent Persons Scheme A Building Regulations Compliance Certificate will then be issued to the customer Heating and Hotwater Industry Council HHIC www centralheating co uk ALL SYSTEMS PRIMARY SETTINGS indirect heating only Is the primary circuit a sealed or open...

Страница 5: ...inhibitor see section 6 2 Codes of Practice refer to the most recent version In GB the following Codes of Practice apply Standard Scope BS 7967 Carbon monoxide in dwellings and the combustion performance of gas fired appliances BS 7967 2 Guide for using electronic portable combustion gas analysers in the measurement of carbon monoxide and the determination of combustion performance BS 7967 3 Guide...

Страница 6: ...the load as close to your body as possible 4 Asses the risks associated with handling and lifting according to the conditions on site If in doubt seek advice before proceeding Health and Safety is the responsibility of everyone 17 0 BENCHMARK Dimplex Boilers 2008 43 GAS BOILER SYSTEM COMMISSIONING CHECKLIST CONTROLS Tick the appropriate boxes Time and Temperature Control to Heating Room Thermostat...

Страница 7: ...t when fixed BCC s only fitted to replacement PCB s 36 BCC Error No flame Damaged BCC Replace BCC Auto Re start when fixed BCC s only fitted to replacement PCB s 37 BCC Error No flame Different BCC BCC and PCB software incompatible replace BCC Auto Re start when fixed BCC s only fitted to replacement PCB s 38 BCC Error No flame Different BCC Reset the appliance in accordance with BCC fitting instr...

Страница 8: ...w Primary Return CH flow Thermistor CH return Thermistor Plate Heat Exchanger Condensate Trap Pressure Gauge Flow Turbine DHW Cold Inlet CH Return 3 BAR Pressure Relief Valve DHW Hot Outlet Pump Hydroblock Automatic Air Vent CH Flow Flue Products DHW Mode Manual Bleed Valve Flow Rate Restrictor Flow Rate Restrictor Fig 2 Fig 3 15 0 SPARE PARTS 15 1 SHORT PARTS LIST Dimplex Boilers 2008 41 Key GC N...

Страница 9: ... 1 0 Min Mains Water Inlet Pressure for Operation Bar 0 3 0 3 0 3 Max Mains Water Inlet Pressure Bar 10 10 10 Min Domestic Hot Water Flow Rate for Operation Ltr min 2 0 2 0 2 5 Min Central Heating System Pressure Bar 0 5 0 5 0 5 Max Central Heating System Pressure Bar 2 5 2 5 2 5 Max Domestic Hot Water Temperature C 60 60 60 Min Domestic Hot Water Temperature C 40 40 40 Max Central Heating Flow Te...

Страница 10: ...Always double check the label on the BCC card to ensure it is the correct BCC for the boiler model to which it is being fitted Never fit an incorrect BCC as this is extremely dangerous and could result in serious injury or death 9 Reassemble in reverse order ensuring that the control knob are reset to their previous positions Dimplex Boilers 2008 39 13 19 BCC 1 Ensure supply voltage is fully isola...

Страница 11: ...and the IRNs Dimplex Boilers 2008 11 6 3 SYSTEM CONTROL 1 The boiler is fitted with an integral mechanical timer 2 It is recommended that external controls e g room thermostat are fitted to further improve the operating efficiency of the boiler and system 6 2 CENTRAL HEATING CIRCUIT 1 The appliance is suitable for fully pumped SEALED SYSTEMS ONLY Treatment of Water Circulating Systems Failure to f...

Страница 12: ...20 25 6 00 5 00 4 00 3 00 2 00 1 00 0 00 Dimplex Combi Fig 8 Fig 7 Expansion Vessel Pressure Relief Valve Vessel charge and initial system pressure Total water content of system using 8 litres capacity expansion vessel supplied with appliance For systems having a larger capacity multiply the total system capacity in litres by this factor to obtain the total minimum expansion vessel capacity requir...

Страница 13: ...se jumpered stopcock water meter water treatment device then an expansion vessel must be fitted e g Zilmet 160ml R1 2 15bar A single check valve must be fitted as shown in Fig 10 to prevent backflow to the supply pipe and to ensure the efficient operation of the expansion vessel which is required to accommodate the thermal expansion of the water If the hot water expansion is not provided for then ...

Страница 14: ...vertical area is required for the installation of the boiler 2 These dimensions include the necessary clearance around the boiler for case removal spanner access and air movement Additional clearances may be required for the passage of pipes around local obstructions such as joists running parallel to the front face of the boiler Zone 2 Zone 2 Zone 1 Zone 0 Zone 3 Zone 3 Window Recess Zone 2 Windo...

Страница 15: ... is used Flue kit B23 classification and the boiler is fitted in a compartment then high and low level ventilation is required BS 5440 2 2000 gives guidance on compartmental ventilation 2 When the boiler is installed in a cupboard or compartment and either flue kit A B C D or F Classification C13 C33 C53 is used then no compartmental ventilation is required Dimplex Boilers 2008 15 7 4 GAS SUPPLY 1...

Страница 16: ...inage it may be necessary to install a condensate pump to carry condensate up to ground drain level Such products are available from most plumbing merchants For help with selecting a condensate pump contact Dimplex Boilers Tel 0844 3711121 WARNING There must be no air breaks in the condensate pipework or drainage system 16 Dimplex Boilers 2008 50mm per metre of pipe run 2 5 Minimum fall 450mm min ...

Страница 17: ...ns O to S in the chart below is allowable per installation Under car ports we recommend the use of the plume displacement kit The terminal position must ensure the safe and nuisance free dispersal of combustion products Dimplex Boilers 2008 17 NOTE The minimum distance from a flue terminal to a boundary line is 300mm If fitting a plume diverter kit the air inlet should be a minimum of 100mm from a...

Страница 18: ...her buildings 60 100 flue accessories 0 5m flue extension duct 956092 1m flue extension duct 956093 93 flue extension elbow 956091 45 flue extension elbow 2x 956090 Vertical flue turret 956087 Ø60 100mm concentric standard horizontal wall terminal Max length 10 000mm Min length 250mm Standard telescopic horizontal flue kit Part no 956120 Horizontal terminal has a built in fall in the flue to allow...

Страница 19: ...s particular flue kit raises the flue gas outlet point to a higher elevation with the minimum amount of changes The flue gas duct is teed off from the concentric part and covered by an 80mm outer tube to protect the flue duct from freezing The air in take remains at the lower level see Fig 24 If choosing this option then the external flue duct length should be taken into account when calculating e...

Страница 20: ...e rooms within the same dwelling the flue pipe must be routed through vented ducts The flue resistance for the following accessories has to be considered Ø80mm flue extension 90 elbow 45 elbow Split pipe vertical flue outlet kit Part no 956080 Kit F Fig 27 Fig 28 12 0 SERVICING AND MAINTENANCE 12 1 ROUTINE SERVICING AND ALL MAINTENANCE THAT INVOLVES THE EXCHANGE OF PART OF THE COMBUSTION CIRCUIT 1...

Страница 21: ...0m 956111 20m Flexi tube 30m 956112 30m Straight duct 80 included in kit N A N A Chimney terminal included in kit N A N A Note Equivalent length information only required for coaxial flue parts The corrugated Flexi tube flue parts are fixed and all parts are required for every application Dimplex Boilers 2008 21 8 11 Additional Concentric Flue Kit Accessories The following additional concentric ki...

Страница 22: ...watch NOTE This boiler is supplied factory set for operation on natural gas No further adjustments of the air gas ratio valve or measurement of the combustion performance are necessary at the time of installation and commissioning This is provided the appliance has been installed according to these instructions and the inlet gas pressure is within our specification Dimplex Boilers 2008 27 NOTE If ...

Страница 23: ...16 5 17 6 18 7 19 8 20 9 21 10 22 11 23 12 24 0 1 0 1 2 bar 3 4 9 0 INSTALLATION 9 2 FITTING THE BOILER 1 Remove the sealing caps from the boiler connections NOTE A small amount of water may drain from the boiler once the caps are removed 2 Check the sealing washers are located correctly in the taps on the wall jig 3 Lift the boiler as indicated by the shaded areas The boiler should be lifted by T...

Страница 24: ...ure that the terminal is the correct way around 3 Loosely fit the internal wall sealing ring over the inside end of the flue 4 Assemble the flue system extension ducts as necessary referring to the flue kit instructions and fit to the elbow 5 Fit the flue terminal to the flue system ensuring that the duct joints are not disturbed and that the external sealing ring is seated against the outside wal...

Отзывы: