Air-to-water heat pump 16 kW with cooling and domestic hot water

The following points must be observed when filling the system:

Untreated filling water and make-up water must be of
drinking water quality
(colourless, clear, free of sediments)

Filling water and make-up water must be filtered (max.
pore size 5 µm).

Scale formation in domestic hot water heating systems cannot
be avoided, but in systems with flow temperatures below 60 °C,
the problem can be disregarded. With high-temperature heat
pumps and in particular with bivalent systems in the higher per-
formance range (heat pump + boiler combination), flow tem-
peratures of 60 °C and more can be achieved. The following
standard values should therefore be adhered to with regard to
the filling and make-up water according to VDI 2035, sheet 1:
The total hardness values can be found in the table.

Abb. 6.1:Guideline values for filling and make-up water in accordance with
VDI 2035

For systems with an above-average specific system volume of
50 l/kW, VDI 2035 recommends the use of fully demineralised
water and a pH stabiliser to minimise the risk of corrosion in the
heat pump and heating system.

!!

ATTENTION!

With fully demineralised water, it is important to ensure that
the minimum pH value of 7.5 (minimum permissible value for
copper) is complied with. Failure to comply with this value can
result in the heat pump being destroyed.

Minimum heating water flow rate

The minimum heating water flow rate through the heat pump
must be assured in all operating states of the heating system. If
the minimum heating water flow rate is not reached, the heat
pump is blocked.
The nominal flow rate is specified depending on the max. flow
temperature in the device information and must be taken into
account during planning. For return temperatures under 30 °C,
the flow must be designed for the nominal conditions.
The specified nominal flow rate (see “Device information”) must
be assured in all operating statuses. The installed flow rate
monitoring is used only for switching off the heat pump in the
event of an unusual and abrupt drop in the heating water flow
rate and not to monitor and safeguard the nominal flow rate.

Frost protection

A method of manual drainage should be provided for heat
pumps which are exposed to frost. The frost protection func-
tion of the heat pump manager is active whenever the heat
pump manager and the heat circulating pump are ready for op-
eration. The system must be drained if the heat pump is taken
out of service or in the event of a power failure. The heating cir-
cuit should be operated with a suitable frost protection if heat
pump systems are implemented in buildings where a power
failure can not be detected (holiday home).

6.4 Domestic hot water connection

Installation and commissioning must be performed by an au-
thorised specialist company. The entire system, including all
factory-assembled components, should be inspected to ensure
that everything is working properly and that there is no leakage.
The enamelled tank in accordance with DIN 4753 is suitable for
drinking water.
The following materials can be used in the consumer circuit in
the domestic hot water circuit:

 Copper

 Stainless steel

 Brass

 Plastic

The specifications of the Federal Environmental Agency (UBA)
(positive list) must also be observed during the installation of
the domestic water system. Depending on the materials used in
the domestic hot water system (customer installation), material
incompatibility may lead to corrosion damage. This especially
applies to zinc-plated materials and materials containing alu-
minium. If there is a risk of water contamination during opera-
tion, install a suitable filter.
The maximum permissible operating overpressure indicated on
the type plate must not be exceeded. It may be necessary to
mount a pressure reducer.
Ensure that the water supply is turned on and the cylinder is
filled before start-up. 
The domestic hot water cylinder must be equipped with a certi-
fied, spring-loaded membrane safety valve on-site. A shut-off
device must not be installed between the cylinder and the
safety valve. The operational reliability of the valve must be
checked at regular intervals.

The bare-tube heat exchanger needs to be flushed with
water prior to connecting the hot water pipeline.

The maximum permissible operating overpressure indi-
cated on the type plate must not be exceeded. It may be
necessary to mount a pressure reducer.

Electrical installations should only be connected by author-
ised electricians according to the corresponding circuit di-
agram. All relevant requirements of the utility company and
VDE regulations must be observed.

We recommend having an annual service inspection carried out
by a qualified specialist company.

!!

ATTENTION!

According to the specifications of the German Technical and
Scientific Association for Gas and Water (DVGW), the magne-
sium anode should initially be inspected by after-sales service
after 2 years of use and then at regular intervals and replaced
when necessary. (Renew anode when protective current less
than 0.3 mA)

Total heat 

output in 

kW

Total

Alkaline earths 

in mol/m³ and/

or mmol

Specific system volume

(VDI 2035) in l/kW

< 20



20  < 50



50

Total hardness in °dH

< 50



2.0



16.8



11.2

< 0.11

1

50 - 200



2.0

 11.2



8.4

200 - 600



1.5



8.4

< 0.11

1

 > 600

< 0.02

< 0.11

1

1. This value lies outside the permissible value for heat exchangers

in heat pumps.

Содержание 16CHCIAOC6

Страница 1: ...no DOK4x HCIAO CxDEN EN FD 9912 System M Comfort Plus C 16 kW Installation and Operating Instruction Air to Water Heat Pump in Integral Design Glen Dimplex Thermal Solutions Dimplex 16CHCIAOC6 16IHCI...

Страница 2: ......

Страница 3: ...rant line and electric wire 13 6 2 Condensate drain 13 6 3 Connection on heating side 13 6 4 Domestic hot water connection 14 6 5 Temperature sensor connection 15 6 6 Electrical connection 16 6 7 Refr...

Страница 4: ...domestic hot water 13 Diagrams 32 13 1 Characteristic curves heating 16 kW 32 13 2 Characteristic curves cooling 16 kW 33 14 Product information as per Regulation EU No 813 2013 Annex II Table 2 34 1...

Страница 5: ...tions must also be adhered to This unit can be used by children aged 8 and over and by per sons with limited physical sensory or mental aptitude or lack of experience and or knowledge providing they a...

Страница 6: ...working medium refrigerant in the evaporator The heat is pumped to a higher temperature level by increas ing its pressure with the aid of the electrically driven compres sors It is then transferred to...

Страница 7: ...pump 5 Switch box with heating controller 6 Electric additional heater 2 4 or 6 kW for higher domestic hot water temperatures and for heating support 7 Safety valve start to leak pressure 2 5 bar 8 Ex...

Страница 8: ...W with cooling and domestic hot water 3 2 Domestic hot water cylinder 3 2 1 MDHW 232 220 litres 1 Magnesium anode 2 Maintenance opening 3 Drainage domestic hot water cylinder 4 Purging pipe heat excha...

Страница 9: ...gnesium anode 2 Maintenance opening 3 Drainage domestic hot water cylinder 4 Purging pipe heat exchanger 5 Domestic hot water sensor pipe high output capacity 6 Connection kit included 7 Alternative d...

Страница 10: ...CxDEN FD 9912 www gdts one English Air to water heat pump 16 kW with cooling and domestic hot water 3 3 Outdoor unit 1 Evaporator 2 Fan 3 Expansion valve 4 Switch box 5 Connection for refrigerant lin...

Страница 11: ...ps can be passed directly underneath the pallet To lift from the pallet the indoor unit can be tilted back by up to 45 and lifted by the handles on the back at the top Tilting more than 45 is not perm...

Страница 12: ...transport fastening must be re moved 4 3 Domestic hot water cylinder A pallet should be used to transport the heat pump to its final installation location To lift from the pallet the cylinder can be t...

Страница 13: ...lways be fixed in place at the installation location Cap 12 1 on page 27 The responsibility for the heat pump in stallation lies with the specialist system construction company During the installation...

Страница 14: ...unit must be inserted in the designated immersion sleeve on the rear of the cylinder On domestic hot water cylinders MDHW 335 with an additional electric heater two immersion sleeves are located at d...

Страница 15: ...tions of the countries in question must be observed 6 3 Connection on heating side Before connecting the heating system to the heat pump the heating system must be flushed to remove any impurities res...

Страница 16: ...e operated with a suitable frost protection if heat pump systems are implemented in buildings where a power failure can not be detected holiday home 6 4 Domestic hot water connection Installation and...

Страница 17: ...ted in such a way that all weather conditions are taken into consideration and the meas ured value is not falsified Mount on the external wall on the north or north west side where possible Do not ins...

Страница 18: ...D 9912 www gdts one English Air to water heat pump 16 kW with cooling and domestic hot water 6 6 Electrical connection 6 6 1 Circuit diagram Symbol legend see cap 6 6 2 on page 17 Equipment marking se...

Страница 19: ...0 Domestic hot water A441 Bivalent A442 Renewable A451 Cooling active B3 domestic hot water thermostat B4 Swimming pool water thermostat E10 1 Electrical heater E10 2 3 Oil gas boiler H5 Remote fault...

Страница 20: ...ason it should be tapped upstream from the utility blocking con tactor or be connected to the household current because otherwise important protection functions could be lost during a utility block Ut...

Страница 21: ...ee device information 6 7 2 Pipe connection The connection points for the refrigerant lines must be estab lished using the brazing process All generally applicable instal lation and work steps must be...

Страница 22: ...vacuum is reached An absolute pressure of at least 0 2 mbar must be achieved during evacuation Pressures below 0 2 mbar are advisable however Close the vacuum pump and start filling immediately Step 4...

Страница 23: ...ely filled and purged Ensure that the condensate drain functions properly The outflow from the heating water pressure relief valve must also function correctly The system must be completely filled wit...

Страница 24: ...em must be cleaned by a heating technician Based on current information we recommend using a 5 phosphoric acid solution for cleaning purposes However if cleaning needs to be performed more frequently...

Страница 25: ...re discon nected from the power supply HINWEIS NOTE Personal protective equipment protective goggles safety shoes and gloves where necessary must be used when work ing on the device Components with pl...

Страница 26: ...18 23 m h Pa 1 6 33000 1 6 33000 Minimum cooling water flow rate m h Pa 1 6 33000 1 6 33000 3 4 Sound power level according to EN 12102 with A7 W55 outdoors Normal operation reduced operation3 dB A 55...

Страница 27: ...ency of the system other parameters in particular the defrosting capacity the bivalence point and regulation should also be taken into consideration These figures are only achieved with clean heat exc...

Страница 28: ...rating overpressure bar 10 10 10 5 Dimensions without connections H x W x L mm 1400 x 600 x 600 2100 x 600 x 600 10 6 Connections Cold water domestic hot water circulation inches R 1 external thread R...

Страница 29: ...intake 0 4 m 1 m 0 5 m 0 5 m Direction of air flow Minimum clearances 460 39 710 40 790 Hatched area footprint 850 1231 600 206 790 538 695 995 95 55 105 40 538 39 4x 17 5 Fixing holes base frame for...

Страница 30: ...lish Air to water heat pump 16 kW with cooling and domestic hot water 12 2 Dimension drawing indoor unit 2 8 2 9 2 1 2 10 2 3 2 2 2 7 2 12 2 11 600 1400 544 722 750 113 125 95 0 117 187 490 560 840 91...

Страница 31: ...N FD 9912 29 Air to water heat pump 16 kW with cooling and domestic hot water English 12 3 Dimension drawing domestic hot water cylinder MDHW 232 1360 600 1400 B 20 1305 410 37 38 600 70 70 240 56 3 3...

Страница 32: ...one English Air to water heat pump 16 kW with cooling and domestic hot water 12 4 Dimension drawing domestic hot water cylinder MDHW 335 600 2060 600 37 38 1265 410 2100 B 20 980 1400 230 70 70 240 5...

Страница 33: ...2 3 Feed through refrigerant line indoor unit 2 7 Flow heating G 1 1 4 2 8 Return heating G 1 1 4 2 9 Flow domestic hot water cylinder G 1 1 4 2 10 Return domestic hot water cylinder G 1 1 4 2 11 Flow...

Страница 34: ...0 15 20 25 30 35 40 max min 0 1 2 3 4 5 25 20 15 10 5 0 5 10 15 20 25 30 35 40 max min 10 15 20 25 30 35 40 45 50 55 60 65 25 20 15 10 5 0 5 10 15 20 25 30 35 40 at the specified minimum heating water...

Страница 35: ...15 20 25 30 35 40 45 50 max min 0 1 2 3 4 5 10 15 20 25 30 35 40 45 50 max min 0 5 10 15 20 25 10 15 20 25 30 35 40 45 50 Cooling capacity in kW Air intake temperature in C Air intake temperature in...

Страница 36: ...45 55 dB m h Emissions of nitrogen oxides NOx mg kWh Declared load profile XL Water heating energy efficiency wh 89 Daily electricity consumption Qelec 8 86 kWh Daily fuel consumption Qfuel kWh Contac...

Страница 37: ...xides NOx mg kWh Declared load profile XL Water heating energy efficiency wh 89 Daily electricity consumption Qelec 8 86 kWh Daily fuel consumption Qfuel kWh Contact details If Cdh is not determined b...

Страница 38: ...up plier are not covered by the warranty If it was not possible to remedy the defect the manufacturer shall either deliver a replacement free of charge or issue a reimburse ment for the reduced value...

Страница 39: ...g state of the art en cryption methods III Use of service providers Personal data required for maintenance purposes such as your address contact details and framework data on the contract is made avai...

Страница 40: ...CxDEN FD 9912 www gdts one English Air to water heat pump 16 kW with cooling and domestic hot water 17 Declaration of conformity You can find and download the current CE conformity declaration at htt...

Страница 41: ...www gdts one DOK4x HCIAO CxDEN FD 9912 39 Air to water heat pump 16 kW with cooling and domestic hot water English...

Страница 42: ...40 DOK4x HCIAO CxDEN FD 9912 www gdts one English Air to water heat pump 16 kW with cooling and domestic hot water...

Страница 43: ...www gdts one DOK4x HCIAO CxDEN FD 9912 41 Air to water heat pump 16 kW with cooling and domestic hot water English...

Страница 44: ...9 dimplex gdts one www gdts one Gesch ftsstelle sterreich Glen Dimplex Austria GmbH Hauptstra e 71 A 5302 Henndorf am Wallersee T 43 6214 20330 F 43 6214 203304 info dimplex at www dimplex at Office F...

Отзывы: