ECODAN AIR SOURCE HEAT PUMP

INST

ALL

A

TION MANU

AL

2

Contents

1. Safety precautions

Before installing the unit, make sure you read all the “Safety precau-
tions”.

After installation, perform the test run to ensure normal operation. Then explain 
your customer the “Safety Precautions,” use, and maintenance of the unit based 
on the information in the Operation Manual. Both the Installation Manual and the 
Operation Manual must be given to the user. These manuals must always be kept 
by the actual users.

 : Indicates a part which must be grounded.

 Warning:

Carefully read the labels attached to the unit.

 Warning:

Precautions that must be observed to prevent injuries or death.

 Caution:

Precautions that must be observed to prevent damages to the unit.

1.  Safety precautions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  2
2.  Installation location   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  3
3.  Installation procedures  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  4
4.  Drainage piping work  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  5

5.  Water piping work   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  5
6.  Electrical work  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  5
7.  Test run  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  6

 Warning:

• The unit must not be installed by the user. Ask an installer or an autho-

rized technician to install the unit. If the unit is installed improperly, water 
leakage, electric shock, or fi re may be caused.

• The unit must be installed according to the instructions in order to mini-

mize the risk of damages by earthquakes, typhoons, or strong winds. Im-
properly installed unit may fall down and cause damages or injuries.

• The unit must be securely installed on a structure that can sustain its 

weight. If the unit is mounted on an unstable structure, it may fall down 
and cause damages or injuries.

• If the air to water heat pump is installed in an enclosed area, measures 

must be taken to prevent the refrigerant concentration in the room in the 
event of refrigerant leakage. Consult an installer regarding the appropriate 
measures. Should the refrigerant leak and cause the concentration oxygen 
in the room may lack.

• Ventilate the room if refrigerant leaks during operation. If refrigerant comes 

into contact with a fl ame, poisonous gases will be released.

• All electric work must be performed by a qualifi ed technician according to 

local regulations and the instructions given in this manual. The units must 
be powered by dedicated power lines and the correct voltage and circuit 
breakers must be used. Power lines with insuffi cient capacity or incorrect 
electrical work may result in electric shock or fi re.

• Only the specified cables can be used for wiring. Connections must be 

made securely without tension on the terminals. If cables are connected or 
installed improperly, It may result in overheating or fi re.

• Terminal block cover panel of the outdoor unit must be fi rmly fi xed. If the 

cover panel is mounted improperly, dust and moisture may enter the unit, 
and it may cause electric shock or fi re.

• When installing or moving the air to water heat pump, make sure to use the 

specifi ed refrigerant (R410A) to charge the refrigerant lines. Do not either 
mix it with any other refrigerant or allow air to remain within the pipes. Air 
enclosed in the pipes can cause pressure peaks resulting in a rupture and 
other hazards.

• Make sure to use accessories authorized by Mitsubishi Electric and ask 

an installer or an authorized technician to install them. If accessories are 
improperly installed, it may cause water leakage, electric shock, or fi re.

• Do not remodel the unit. Consult an installer for repairs. If alterations or 

repairs are not performed correctly, it may cause water leakage, electric 
shock, or fi re.

• The user should never attempt to repair the unit or transfer it to another 

location. If the unit is installed improperly, it may cause water leakage, 
electric shock, or fi re. If the air to water heat pump needs to be repaired or 
moved, ask an installer or an authorized technician.

• After installation has been completed, make sure that refrigerant does not 

leak. If refrigerant leaks into the room and comes into contact with the 
fl ame of a heater or portable cooking range, poisonous gases will be re-
leased.

• Use clean enough water which meets water quality standards. The dete-

rioration of water quality may result in the system breakdown or the water 
leakage.

• Never use anything other than water as a medium. It may cause a fi re or an 

explosion.

• Do not use heated or cooled water that is produced by the air to water 

heat pump directly for drinking or cooking. There is a risk to damage your 
health. There is also a risk that installing the water heat exchanger may 
corrode if the necessary water quality for the air to water heat pump sys-
tem cannot be maintained. If you wish to use the heated or cooled water 
from the heat pump for these purposes, take measure such as to the sec-
ond heat exchanger within the water piping system.

1.1. Before installation 

 Caution:

• Do not use the unit in an unusual environment. If the air to water heat 

pump is installed exposed to steam, volatile oil (including machine oil), 
or sulfuric gas, or exposed to briny air, or covered with snow, the perfor-
mance can be signifi cantly reduced and the internal parts can be damaged.

• Do not install the unit where combustible gases may leak, be produced, 

flow, or accumulate. If combustible gas accumulates around the unit, it 
may cause fi re or explosion.

• The outdoor unit produces condensate during the heating operation. Make 

sure to provide drainage around the outdoor unit if such condensate is 
likely to cause damage.

• When installing the unit in a hospital or in a building where communica-

tion equipments are installed, you may need to take measures to noise and 
electronic interference. Inverters, home appliances, high-frequency medi-
cal equipment, and radio communications equipment can cause the air to 
water heat pump to malfunction or to breakdown. At the same time, the 
noise and electronic interference from the air to water heat pump unit may 
disturb the proper operation of medical equipment, and communications 
equipment.

1.2. Before installation (relocation) 

 Caution:

• Be fully careful when moving the units. The unit must be carried by at least 

2 people, as it weighs 20 kg or more. Do not hold the packaging bands. 
Wear protective gloves to unpack and to move it, in order to avoid your 
hands be injured by fi ns or other parts.

• Be sure to safely dispose of the packaging materials. Packaging materials, 

such as nails and other metal or wooden parts may cause injuries.

• The base of the outdoor unit must be periodically checked to ensure not 

being loose, cracked or damaged. If such defects are left untreated, the 
unit may fall down and cause damage or injuries.

• Do not wash the air to water heat pump unit. You may receive an electric 

shock.

Содержание BMA 240 SP-SOL

Страница 1: ...tic housing from an air source heat pump Air Source Heat Pumps Appliances These instructions also include wiring installation details for a special version of the BoilerMate HP appliance designed to work with the Mitsubishi PQFY VRF heat pump range BoilerMate Model Numbers BMA 180 HP PQFY BMA 210 HP PQFY BMA 240 HP PQFY Ecodan Air Source Heat Pump Model Number PUHZ W90VHA ...

Страница 2: ...ority Building Control Department From 1st April 2005 this can be achieved via a Competent Person Self Certification Scheme as an option to notifying the Local Authority directly Similar arrangements will follow for Scotland and will apply in Northern Ireland from 1st January 06 CORGI operates a Self Certification Scheme for gas heating appliances These arrangements represent a change from the sit...

Страница 3: ...e heat pump return to help protect the heat pump from any heating system contamination and provide an ongoing visual indication of the system water condition Interconnection Between Ecodan and BoilerMate A Class HP Aneightcoresignalcableisneededtoberunbetweenthe internal BoilerMate and the external Ecodan An 8 metre supply of this cable is provided with the BoilerMate if additional length is neede...

Страница 4: ... with a local external isolator fitted in accordance with IEE wiring regulations Incoming Water Supply As the performance of hot and cold water systems is totally reliant on the incoming mains cold water supply check that the pressure will be a minimum of 2 bar at times of maximum simultaneous use and that the flow rate is a minimum of 30 litres minute For optimum performance this will need to be ...

Страница 5: ...pliance must only be used with suitable heat pumps and is not suitable for use with any uncontrolled energy source such as solid fuel steam It should not be installed where the annual inspection is likely to be neglected The information in this manual is provided to assist generally in the selection of equipment The responsibility for the selection and specification of the equipment must however r...

Страница 6: ...ump is not sufficient to meet the demands The controls are set to provide hot water priority ie if there is a demand at S3 any heating demands will be suspended until the store temperature reaches the point where S3 is satisfied All models are designed to heat the domestic hot water indirectly up to the maximum temperature possible with the heat pump and then boost the temperature by means of a3kW...

Страница 7: ...s provided as part of the package Scale Protection The Building Regulations L1A New dwellings L1B Existingdwellingsandtherequirementsset out in the Domestic Heating Compliance Guide specify that where the mains water hardness exceeds 200ppm provision should be made to treatthefeedwatertowaterheatersandthehot water circuit of combination boilers to reduce the rate of accumulation of lime scale To c...

Страница 8: ...pump flow 24 S4 sensor central heating flow boost 25 Electrical temperature boost assembly central heating Zone 1 only 26 S3 sensor hot water boost 27 Primary system manifold 28 Electrical temperature boost hot water only 29 Flow to hot water coil unvented system 30 Return from hot water coil unvented store 31 Domestic hot water outlet connection 32 Secondary domestic hot water return connection 3...

Страница 9: ...erature boost assembly central heating Zone 1 only 26 S3 sensor hot water boost 27 Primary system manifold 28 Electricaltemperatureboost hotwateronly 29 Flow to hot water coil unvented system 30 Return from hot water coil unvented store 31 Domestic hot water outlet connection 32 Secondary domestic hot water return connection 33 Electrical control panel printed circuit boards and connection termina...

Страница 10: ...ircuit Please note This is a diagramatic representation all pipework should enter through base of appliance All connections are 22mm Primary System Pipework Connections for BoilerMate A Class HP 180 Model Only Zone 1 flow Zone 1 return Water in return Water out flow A B Ecodan rear ...

Страница 11: ... Either radiator or underfloor heating circuit Zone 2 Underfloor or other low temperature heating circuit Zone 1 flow Zone 2 flow Zone 1 return Zone 2 return Please note This is a diagramatic representation all pipework should enter through base of appliance All connections are 22mm Ecodan rear Water in return Water out flow A B ...

Страница 12: ...bitor at extra cost In this case the aerial is fitted on the 22mm cold inlet and the scale inhibitor PCB is fitted in the electrical panel PCB area Figure 1 7 Figure 1 8 Primary system expansion vessel available as an optional extra at the time of order as part of the Primary Sealed System kit Unvented store expansion vessel supplied separately with the appliance Expansion Vessels Model Primary Ex...

Страница 13: ...ontrol overheat safety thermostat temperature settings HW boost immersion heater S1 S2 safety sensors 3 P T valve 900 C CH boost immersion heater Control thermostat 5 650 C Overheat thermostat 4 850 C Control relief valve pressure set points Mains inlet pressure regulator 1 5 bar Expansion relief valve CW 3 0 bar Expansion relief valve CH 3 0 bar P T valve 4 0 bar Maximum hot water flow rate 25 35...

Страница 14: ... normal way using the criteria set out in BS 6700 NHBC for storage appliances Electricity Supply One mains supply rated at 32A 230V 50Hz is required Minimum external fuse rating and the main supply cable ratings are given inTable 1 2 Technical Data section of this manual This appliance MUST BE EARTHED All external wiring to the appliance must be in accordance with the latest I E E Wiring Regulatio...

Страница 15: ... are approximate and subject to a tolerance of 20mm in any direction Note All dimensions are shown in mm and are to the centre line of pipework gland 575 595 including the door clock 595 75 40 315 DHWS Expansion 440 Primary System Vent 300 545 180 Model Connection Details Dimensions Top DHWS Secondary Return Figure 1 9 575 595 including the door clock 440 Heat Pump Return 440 Heating Return Zone 1...

Страница 16: ...Dimensions Bottom 415 Heating Flow Zone 1 Expansion Relief Valve Discharge DESIGN TECHNICAL DATA 210 240ModelConnectionDetails Dimensions Diagram opposite show the connection details and dimensions for the BoilerMate A Class HP DEM 210 240 models The BoilerMate A Class HP DEM units are supplied on an installation base to allow the pipe runs to connect to the appliance from any direction Itiseasier...

Страница 17: ...ings and the requirements set out in the Domestic Heating Compliance Guide specify that where themainswaterhardnessexceeds200ppmprovisionshouldbemadetotreatthefeed water to water heaters and the hot water circuit of combination boilers to reduce the rate of accumulation of lime scale Tocomplywiththisrequirementthehardnessofthemainswatershouldbecheckedby theinstallerandifnecessarytheoptionalfactory...

Страница 18: ...d that a small expansion vessel 0 25 0 5 litre is fitted after the pressure regulator to accommodate the pressure rise caused by the increase in temperature of the balanced cold water SH WHB SCV SCV WC BATH 22 22 15 15 WHB WC M DC DCV DC DCV To External Tap 25mm MDPE Incoming Supply WM or DWM SINK Discharge Pipe BoilerMate HP DEM Ground Level mains cold hot discharge balanced cold Location of opti...

Страница 19: ...xed water outlets such as showers For this reason and because these are now no more expensive than a manual shower we strongly recommend the use of thermostatic showers with this appliance The shower head provided must also be suitable for mains pressure supplies If it is proposed to use a whole body or similar shower with a number of high flow pressure outlets please discuss with the Gledhill tec...

Страница 20: ...designed and sized using the parameters for plastic pipework Selection Heat Pump Sizing General model selection guidance is given in Table 1 2 Technical Data Heat Pump Primary Circuit Theflowandreturnfromtheheatpumpmustrundirectlytotheconnectionsprovided on the BoilerMate A Class HP DEM appliance A Fernox Boiler Buddy is provided as part of the package and this must be fitted internally on the ret...

Страница 21: ...volume allow 10 litres for the primary pipework coils within the appliance Sealed System Kit For The Central Heating System An optional sealed system kit as follows can be supplied with the BoilerMate A Class HP DEM Pressure gauge 0 4 bar Primary expansion vessel charged to 1 0 bar Size depends upon the model seeTable 1 1 WRAS approved primary system filling loop External Temperature Compensation ...

Страница 22: ...itch button below the display for at least 5 seconds The Normal will change to Switch and will flash Once the problem has been resolved the appliance can be returned to normal operation by pressing the Switch button for at least 5 seconds Fault Condition Display Window If a fault occurs with the BoilerMate A Class HP DEM appliance the window will automatically display the fault condition The windo...

Страница 23: ...d by ringing the Gledhill Technical Helpline 08449 310000 APPLIANCE CONTROL BOARD A C B Fuse T3 15L 250V 2 DIGIT ACB BOARD DISPLAY FLOW CHART Press S2 Press S2 Press S2 Press S2 Press S2 S2 S1 Press S1 Press S1 Press S1 Press S1 Appliance type Press S1 Press S1 Press S1 Press S1 Appliance type Press S1 Press S1 Press S1 Press S1 Fault code indicator block outs Press S1 Press S1 Press S1 Press S1 F...

Страница 24: ...istance allowed for a straight length of 28mm pipe from a G temperature relief valve equates to 18m Subtract the resistance for 4 No 28 elbows at 1 0m each 4m Therefore the maximum permitted length equates to 14m As the actual length is 7m a 28mm copper pipe will be satisfactory In apartment flat situations the discharge pipes can be connected into a single pipe which is discharged at low level In...

Страница 25: ...operate as quietly as practicable However some noise from pumps etc is inevitable in any heating system This will be most noticeable in cupboards formed on bulkheads or at the mid span of a suspended floor In these cases the situation can be improved by placing the appliance on a suitable sound deadening material i e carpet underlay or similar The appliance is very well insulated and no ventilatio...

Страница 26: ...oftheseinstructions Beforeinstallationthesiterequirementsshould be checked and confirmed as acceptable The plastic cover and protective wrapping should be removed from the appliance and the installation base provided placed in position Theappliancecanbethenbeliftedintoposition inthecupboardontopofthebaseandthefront panelremovedbyunscrewingthe2screwsand liftingthedoorupandoutreadyforconnection of t...

Страница 27: ... should be read in conjunction with this manual Runtheexternalwiringthroughtheserviceslot provided in the base of the appliance Make the connections as shown opposite on the terminal strip provided Theroomthermostatshouldbewiredasshown opposite The link in Z1RSL to Z1RSSL must be removed when the room thermostat is fitted The time and temperature controls for CH zone 2 should be wired as necessary...

Страница 28: ...0mA 12 VDC 20mm Fuse A2 A1 HW B CH Z1 B 3kW Room thermostat call for Zone 1 Only Programmable Room thermostat call for Zone 2 Only Z1 RS E V S1 2 5 mm SID Silicone 2 3kW 3 WAY BUS BAR 2 5 mm SID Silicone 2 Remove link to wire room thermostat F1 14 11 12 R1 CC 3 1 2 4 ISSUE No 4 APPROVED DATE NOV 2007 GLEDHI DO NOT SCALE FROM THIS DRAWING COPYRIGHT OF THIS DRAWING IS RESERVED IT IS NOT TO BE REPROD...

Страница 29: ...OUR LEGEND Black Orange Yellow White Red B Or Y Wh R S 3 S 4 S 5 S 6 Hot Water overheat sensors Hot Water Control sensor Zone 1 CH Flow Sensor Heat Pump Return sensor Outside Temperature Sensor Heat Pump Flow sensor S1 S2 SENSOR LEGEND S 7 3 Speed P2 P1 P3 R Bl Hot Water Valve V1 CH Zone 1 Valve V2 G Y Or Wh Bl J34 J5 J30 J31 J9 1 1 K 8 147MP_34 Wh Wh A1 B1 A5 A4 A3 A2 B2 B3 Br B 8 7 6 5 A B C D E...

Страница 30: ...ected to the heat pump by the installer as shown If any additional length is required please use RS Components stock code 482 6036 25 metres and replace the entire length DO NOT JOINT Maximum length is 30 metres If using alternative cable to the above the individual cores must be a minimum of 0 5mm2 External Temperature Compensation Sensor Thisissuppliedconnectedto10metresofcable which is coiled a...

Страница 31: ... corrosioninhibitor The heat pumpand external connecting pipework will also require protection against freezing For this reason a combined anti freeze and inhibitor product such as Fernox Alphi 11 must be used Thevolumes concentrationshouldbecalculatedinaccordancewiththemanufacturers instructions allowing 10 litres for the volume for the primary pipework coil in the BoilerMate A Class HP appliance...

Страница 32: ... anchored 4 Do ensure that the functioning and control of the system is explained to the occupant and explain the need and importance of periodic servicing These Instructions should be replaced along with the component manufacturers instructions in the pocket provided on the appliance and the front panel refitted NOTE With sealed heating systems air is released from the water during the first few ...

Страница 33: ...ddirectfrom Gledhill using the Speed Spares service or throughanyofthelargerplumbersmerchants specialist heating spares suppliers Help and advice is also available from the Technical Helpline on 08449 310000 However allcomponentsarereadilyaccessible and can be changed quickly and easily by the installer using common plumbing practice If it is necessary to replace any of the pumps fitted to the app...

Страница 34: ...xpansion Vessel 24 Litre GT004 10 Primary Expansion Relief Valve and Pressure Gauge Comap XG154 11 Relay Wago 12 Contactors Heater elements Telemecanique XB014 13 Primary System Pressure Relief Valve XG169 14 Sensor S1 S2 Tasseron XB183 15 Sensor S4 S5 S6 Tasseron GT198 16 Central Heating Temperature Boost Immersion Element 17 Main Control Board Argus Vision XB442 18 External Temperature Compensat...

Страница 35: ...hat the control overheat stat is replaced iii The motorised valve iv Checkthattheheatisbeingproducedbytheheatpumpandthepumpisrunning If the heat pump is running check replace the 100MA F1 fuse provided on the BoilerMate A Class HP DEM terminal strip to protect the main control board from a fault on the heat pump If for any reason heat is not being supplied to the appliance heating and or hot water...

Страница 36: ...tallation die vorliegende Bedienungsanleitung und die Installationsanleitung der Innenanlage gründlich durchlesen die Klimaanlage MANUEL D INSTALLATION Avant d installer le climatiseur lire attentivement ce manuel ainsi que le manuel d installation de l appareil intérieur pour une utilisation sûre et correcte English Deutsch Français For safe and correct use read this manual thoroughly before inst...

Страница 37: ...pplied pipe work must be connected to the heat pump boiler by using QTY2 600mm 1 bore steel braided rubber flexible hose one for flow and one for return which are supplied with the unit Pipe work between the unit and the Hot water tank shall be minimum 22mm Provision shall be taken to avoid this pipe work freezing during winter months 4 Anti Vibration Connections flexible hose supplied loose 5 Sys...

Страница 38: ...ories are improperly installed it may cause water leakage electric shock or fire Do not remodel the unit Consult an installer for repairs If alterations or repairs are not performed correctly it may cause water leakage electric shock or fire The user should never attempt to repair the unit or transfer it to another location If the unit is installed improperly it may cause water leakage electric sh...

Страница 39: ...itch can severely damage the internal parts Keep the main power switch turned on during the operating period Before starting operation check that all panels guards and other protec tive parts are correctly installed Make sure not to get injured by touching rotating hot or high voltage parts Do not touch any switch with wet hands There may be a risk to get an electric shock Do not touch the refrige...

Страница 40: ...such as a typhoon etc may directly blow to the air outlet Fig 2 3 Air outlet guide 3 Position the unit so that the outlet air can blow at right angle to the seasonal wind direction if possible Fig 2 4 Wind direction 2 4 NECESSARY SPACE TO INSTALL 2 4 1 When installing a single outdoor unit Refer to the last page Minimum dimensions are as follows unless Maximum dimensions are indicated Refer to the...

Страница 41: ...iring size must comply with the applicable local and national codes 2 Power supply cables and the cables between Controller and Outdoor unit shall not be lighter than polychloroprene sheathed flexible cables Design 60245 IEC 57 3 Be sure to connect the cables between Controller and Outdoor unit directly to the units no intermediate connections are allowed Intermediate connections may result in com...

Страница 42: ...ed below measure the insulation resistance again The insulation resistance drops due to the accumulation of refrigerant in the compressor The resistance will rise above 1 M after the compressor is warmed up for four hours The necessary time to warm up the compressor varies according to atmo spheric conditions and refrigerant accumulation If the refrigerant accumulates within the compressor the com...

Страница 43: ...e 43 Positioning the Air Source Heat Pump Fig 2 5 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 mm ECODAN AIR SOURCE HEAT PUMP INSTALLATION MANUAL ...

Страница 44: ...rliegende Bedienungsanleitung und die Installationsanleitung der Innenanlage gründlich durchlesen die Klimaanlage MANUEL D INSTALLATION Avant d installer le climatiseur lire attentivement ce manuel ainsi que le manuel d installation de l appareil intérieur pour une utilisation sûre et correcte English Deutsch Français For safe and correct use read this manual thoroughly before installing the unit ...

Страница 45: ...ecorrect BoilerMate HP PQFY type appliance BMA 180 HP PQFY BMA 210 HP PQFY BMA 240 HP PQFY See below for the hydraulic and electrical connections See next page for full electrical schematic diagram See previous sections of this BoilerMate HP manual for all other details Hydraulic Layout Electrical Layout BoilerMate HP Mitsubishi PQFY Water Out Heat Exchanger Water In Flow from heat pump Return to ...

Страница 46: ... mm SID Silicone 2 3kW 3 WAY BUS BAR 2 5 mm SID Silicone 2 Remove link to wire room thermostat D H W D H W U F H U F H U F C U F C Procon ACH1 DHW UFH UFC DHW UFH UFC PQFY Heatpump Terminals 2 core signal cable SELV Outside Temperature Sensor Sensor Select Com N O N C A2 A1 CC R1 3 1 2 4 ISSUE No 3 APPROVED DATE OCT 2007 GLEDHI DO NOT SCALE FROM THIS DRAWING COPYRIGHT OF THIS DRAWING IS RESERVED I...

Страница 47: ...en Grey Green Yellow G Gr G Y WIRE COLOUR LEGEND Black Orange Yellow White Red B Or Y Wh R S 3 S 4 S 5 S 6 Hot Water overheat sensors Hot Water Control sensor Zone 1 CH Flow Sensor Heat Pump Return sensor Outside Temperature Sensor Heat Pump Flow sensor S1 S2 SENSOR LEGEND S 7 3 Speed P2 P1 P3 R Comfort Cooling Call SL C G Y Or Wh BL J34 J5 J30 J31 J9 1 147MP_34 Wh Wh CH2 CH ZONE 1 GITAL CLOCK 6 5...

Страница 48: ... result in pumps or valves seizing and ultimate system failure The Boiler Buddy can be connected directly to 22 mm copper pipework using conventional pump connectors it is also compatible with 15 mm with the appropriate adapter It is not recommended for 28 mm systems as it will restrict the water flow Boiler Buddy can be installed vertically or horizontally The unit is designed to slot into the sp...

Страница 49: ...e is an indication that the system has not been treated correctly with Fernox Protectors Restorers and cleansers Boiler Buddy has a transparent body casing so that the build up of contamination on the core can be observed in service It has been designed to be fitted where it can be inspected and removed for cleaning and should be installed in the central heating return line as close to the boiler ...

Страница 50: ...fore removing the Boiler Buddy place a container underneath the pipework to retain any water that may drip 1 Isolate the Boiler Buddy from the system by simply closing the quarter turn valves on the pump service connector 2 Once the Boiler Buddy has been isolated it can be removed Undo the two 11 2 BSP union nuts Once these have been fully unscrewed the Boiler Buddy can be pulled out between the t...

Страница 51: ...h This will guard against accidental opening of the clamp 15 Using two new fibre washers place the Boiler Buddy back into the pipework between the two pump servicing valves 16 Tighten the union nuts until finger tight after which use a spanner to tighten 1 8th of a turn or until secure CAUTION The body casing is a plastic part and will fail if excessive force is used 17 The servicing valves can be...

Страница 52: ...Page 52 FERNOX alphi 11 product data ...

Страница 53: ...Page 53 FERNOX alphi 11 product data ...

Страница 54: ... Cylinders and Tanks The copper storage vessel is guaranteed for ten years and if it proves to be defective either in materials or workmanship we will either repair or supply replacement at our option with the closest substitute in the case of any obsolete product to any address in Great Britain i free of all charge during the first year after delivery by us ii thereafter at a charge of one tenth ...

Страница 55: ...ract ii all other goods the subject to of any other contract between the Purchaser and us which at the time of payment of the full price of the goods sold under this contract have been delivered to the Purchaser but not paid for in full c until property in the goods supplied hereunder passes to the Purchaser in accordance with paragraph 2 above i the Purchaser shall hold the goods in a fiduciary c...

Страница 56: ...Thecodeofpracticefortheinstallation commissioning servicingofcentralheatingsystems ...

Отзывы: