background image

Page 5

B

E

C

BoilerMate A-Class

SP SOL

300

*250

A

100

*500

D

F

Maintenance

access

Figure 1.2

*Minimum access /
maintenance access
above the appliance
case.

*If the F&E cistern is
fitted with a ballvalve,
this dimension will
need to increase to
350mm to comply with
the Water Regulations.

The minimum clear 

opening in front of 

the appliance to be 

at least the same as 

the depth of the 

appliance

plus 50mm.

The cupboard door 
opening will need to 
take into account the 
various sizes of 
appliances.

F&E cistern

BMA 200-220 SP SOL

BMA 240-300 SP SOL

Appliance Dimensions

Model

Height 

(A)

Width 

(B)

Depth 

(C)

BMA 200-SP SOL

1330

560

620

BMA 220-SP SOL

1330

560

620

BMA 240-SP SOL

1575

560

620

BMA 260-SP SOL

1575

610

670

BMA 280-SP SOL

1575

640

700

BMA 300-SP SOL

1485

710

770

The  above  dimensions  are  for  the  appliance 
only  and  do  not  include  the  100mm  high 
installation base.

Minimum Cupboard Dimensions

Model

Height 

(D)

Width 

(E)

Depth 

(F)

BMA 200-SP SOL

1980

660

630

BMA 220-SP SOL

1980

660

630

BMA 240-SP SOL

2175

660

630

BMA 260-SP SOL

2175

710

680

BMA 280-SP SOL

2175

740

710

BMA 300-SP SOL

2085

810

780

The  above  dimensions  include  the  100mm 
high  installation  base  and  allow  space  for 
installation/maintenance of the appliance only. 
The height shown for the 200-220 models also 
allows for the installation of the F&E cistern (with 
no ballvalve) as shown opposite.

Note:

 With the 240-300 models, additional space 

will  be  required  for  two  feed  and  expansion 
cisterns (each 280mm wide x 420mm deep x 
300 high). This is NOT included in the minimum 
cupboard  dimensions  shown  above.  Access 
and  maintenance  space  will  also  be  required 
for these cisterns.

Options at Extra Cost

•  Hot and cold water manifolds for use with 

plastic pipework.

•  Scale inhibitor for mains water services with 

hardness levels above 200ppm (mg/l).

•  Ballvalve/overflow connector for automatic 

fill model.

•  Primary  sealed  system  kit  for  fitting  near 

boiler comprising:

  -  Expansion vessel (size varies with model)
  -  15mm 3 bar pressure relief (safety) valve
  -  Pressure gauge and filling loop

DESIGN

TECHNIC

AL DA

TA

Содержание BMA 200 SP-SOL

Страница 1: ...ons before installation Model Numbers BMA 200 SP SOL BMA 220 SP SOL BMA 240 SP SOL BMA 260 SP SOL BMA 280 SP SOL BMA 300 SP SOL All models comply with the water heater manufacturers specification for integrated thermal stores A sealed system central heating and mains pressure hot water supply appliance with thermal store designed specifically for use with solar energy ISSUE 5 06 08 ...

Страница 2: ...eme as an option to notifying the Local Authority directly Similar arrangements will follow for Scotland and will apply in Northern Ireland from 1st January 06 CORGI operates a Self Certification Scheme for gas heating appliances These arrangements represent a change from the situation whereby compliance with theBuildingRegulationswasacceptediftheBenchmarkLogbookwascompletedand this was then left ...

Страница 3: ...S6 are connected to the appliance control PCB which operates all theheatingandhotwaterfunctionsasthebasic BoilerMate appliance Sensors T1 T2 and T3 are connected to the Danfoss controller and operate all the solar functions SensorT3providesahightemperatureinterlock to de activate the solar pump at a temperature of 90 C in the store Although sensors T3 and T2 are wired in to the solarcontrollerthec...

Страница 4: ...beorderedasanoptionalextrabut will need fitting on site by the installer Note If the summer towel rail circuit is required this willneedtobeaseparatezonedcircuitfromthe heating circuit complete with its own time and temperature controls The standard manual fill model BoilerMate A ClassSPSOLapplianceisshown Aballvalveand overflowareavailableasanoptionalextraatthe time of order If required these sho...

Страница 5: ...pth F BMA 200 SP SOL 1980 660 630 BMA 220 SP SOL 1980 660 630 BMA 240 SP SOL 2175 660 630 BMA 260 SP SOL 2175 710 680 BMA 280 SP SOL 2175 740 710 BMA 300 SP SOL 2085 810 780 The above dimensions include the 100mm high installation base and allow space for installation maintenance of the appliance only The height shown for the 200 220 models also allowsfortheinstallationoftheF Ecistern with no ball...

Страница 6: ...s easier if all pipes protrude vertically in the cut out area shown Compression or push fit connections can be used All pipe positions are approximate and subject to a tolerance of 20mm in any direction A 15mm cold water supply and a 22mm warning overflow pipe may also be required for the separate feed and expansion cisterns if these are located in the appliance cupboard Note All dimensions are sh...

Страница 7: ...rom any direction It is easier if all pipes protrude vertically in the cut out area shown Compression or push fit connections can be used All pipe positions are approximate and subject to a tolerance of 20mm in any direction A 15mm cold water supply and a 22mm warning overflow pipe may also be required for the separate feed and expansion cisterns if these are located in the appliance cupboard Note...

Страница 8: ...ude vertically in the cut out area shown Compression or push fit connections can be used All pipe positions are approximate and subject to a tolerance of 20mm in any direction A 15mm cold water supply and a 22mm warning overflow pipe may also be required for the separate feed and expansion cisterns if these are located in the appliance cupboard Note All dimensions are shown in mm and are to the ce...

Страница 9: ... flow collector connection from panel 28 Remote solar panel sensor T1 cable 29 Solar return sensor T2 30 Solar overheat sensor T3 31 Solar circuit pump UPS 15 60 high temp 32 Solar controller 33 User control panel clock 34 Appliance control board 35 Electrical DIN rail 36 Solar expansion vessel connection fitted with pressure gauge 37 100mm high installation base Optional Equipment Hot and cold wa...

Страница 10: ...licone 2 Bl Bl R 2 x 3kW Heating Elements R SL H E E PE IH 2 5 mm SID Silicone 2 2 5 mm SID Silicon 2 2 5 mm SID Silicone 2 4 0 mm SIF Silicone 2 2 5 mm SIF Silicone 2 2 5 mm SIF Silicone 2 2 5 mm SIF Silicone 2 2 5 mm SIF Silicone 2 2 5 mm SID Silicone 2 Dedicat Remove link to fit room stat 3 WAY BUS BAR C1 A1 A2 2 4 1 3 2 5 mm SID Silicone 2 2 5 mm SID Silicone 2 3 1 2 4 ISSUE No 4 APPROVED DATE...

Страница 11: ...Speed Y Br G Wh S5 S6 Duplex Sensor must fitted into S6 pocket i e above both V3 V2 valves Duplex Sensor must be fitted in top saftey overheat pocket and secured G Y Or Wh B B J34 J5 J30 J31 J9 1 Br Br B B R Or R Or Dedicated Solar Zone Sensor Solar Collector Sensor fitted in the panel sensor pocket provided by manufacturer Minimum pocket size 8mm 8 7 6 5 A B C D E DRG NAME DRG SIZE JOB NAME TITLE...

Страница 12: ...n Expansion Vessel PRV 0 20 100 120 40 80 60 0 2 10 4 8 6 Temperature Gauge and Check Valve This component arrangement is provided with the SOL appliance and must be mounted vertically on the connection provided No isolation valve should be installed between the solar circuit and the safety valve pressure reducing valve Note No valves should be fitted on the pipework between the solar collector an...

Страница 13: ... will not be affected by holding off the boiler and operates independently of channel 1 If a high hot water demand is expected or the appliance runs out of hot water due to poor solar gains the setting of Channel 1 can be overridden which will bring on the boiler and ensure hot water is made available Dependant on use weather the off times suggested above can be adjusted as necessary to ensure ade...

Страница 14: ...artonatemperaturedifferentialof5 Candthe pump will run until the temperature differential is below 2 C The controller will also exercise the pump for 1 minute every 14 days to help stop it sticking if it has not been used Solar Heat Output Gives the performance of the solar heat installation Thefigureiscalculatedonthebasis of the difference between the temperature in the solar collector and the te...

Страница 15: ...p model connections Set speed higher No alarm temperature flashes Pump runs indicates high temperature Pump does not run Set speed higher Pump or pump output defective For any further technical information assistance regarding this product please ring the Gledhill Technical helpline on 08449 310000 Solar collector Thermal Store 0 95 120 40 Operating range Sensor fault alarm Sensor fault alarm Sens...

Страница 16: ... to 4 bar WATCHING THE LEVEL OF FLUID IN YOUR BOTTLE and adding more antifreeze solution if required When a pressure of 4 bar is achieved close the filling point on the fill and flush valve at the SAME time switch off the power at the RCD safety device Now leave the system under this pressure for at least 30 minutes Check the system for leaks including the roof connections If after 30 minutes the ...

Страница 17: ...l valve Vemco FT206 All 11 1 x 6 kW switch immersion heater Wardtec XB468 All 12 Bottom store sensor Tasseron GT198 All 13 Middle store sensor Tasseron GT198 All 14 Top OHT store sensor Tasseron GT199 All 15 Main PCB controller Argus Vision XB442 All 16 Front panel user membrane All 17 Internal fuses circuit protection MCB Single Pole 6A x 1 XB449 All MCB Single Pole 16A x 2 XB450 All 18 Switch co...

Страница 18: ...Page 18 1 2 3 4 24 5 6 12 13 7 8 9 10 11 15 16 20 19 17 21 23 30 31 29 27 28 26 14 18 22 SHORT PARTS LIST INSTALLATION 34 ...

Страница 19: ...Page 19 ...

Страница 20: ...Page 20 ...

Страница 21: ...Page 21 ...

Страница 22: ...in materials or workmanship we will either repair or supply replacement at our option with the closest substitute in the case of any obsolete product to any address in Great Britain i free of all charge during the first year after delivery by us ii thereafter at a charge of one tenth of the then current list price and any copper price supplement and delivery charge during the second year after del...

Страница 23: ...ject to of any other contract between the Purchaser and us which at the time of payment of the full price of the goods sold under this contract have been delivered to the Purchaser but not paid for in full c until property in the goods supplied hereunder passes to the Purchaser in accordance with paragraph 2 above i the Purchaser shall hold the goods in a fiduciary capacity for us and shall store ...

Страница 24: ...Thecodeofpracticefortheinstallation commissioning servicingofcentralheatingsystems ...

Отзывы: