D
ixell
D
igital
C
ontroller
o
peration
& D
iagnostiC
g
uiDe
Factory Settings
Range of Adjustment
Set Point
Operating
Range†
Minimum Set
Point
Maximum Set
Point
Standard Cooler Setting
34º F
34º F to 39º F
33º F
65º F
Two Zone Cooler Settings*
B = Beer
34º F
34º F to 39º F
33º F
65º F
W = White Wine
50º F
50º F to 55º F
33º F
65º F
R = Red Wine
60º F
60º F to 65º F
33º F
65º F
†
Adjusting the factory set point will also adjust the operating range by the same amount
*
To determine a Two Zone Cooler refrigeration configuration, refer to the 2 digits immediately preceding the
first hyphen of the model number found on the cooler data tag. These 2 digits will always be BW (Beer/
White Wine), BR (Beer/Red Wine), or WR (White Wine/Red Wine). Example:
MODEL: BB60
BR
-L1-
XS(LR)
.
The refrigerator is programmed to automatically
defrost four times daily for approximately twenty
minutes. During defrost, the fan inside the cooler
will remain on and the refrigeration system will
turn off. To initiate defrost manually, push and hold
the DEFROST button for more than two seconds.
The thermostat controller does not have an “OFF”
function. To turn refrigerator off, the unit must be
unplugged or power to the electrical branch circuit
has to be turned off via a circuit breaker or switch.
To change the set point
- push and hold the SET
button for more than two seconds. When the º F
display begins flashing, push the up arrow or down
arrow buttons to adjust the set point to the desired
value.
To save the new set point and return to the tem-
perature display mode
- push and release the SET
button or wait ten seconds.
The operating temperature range is preset at the
factory according to the table below and can be
adjusted up or down within the limits shown.
To see the set point
- push and immediately release
the SET button. The set point will be displayed.
To return to normal visualization
- Push and
immediately release the SET button or wait five
seconds.
Glastender, Inc. • 5400 North Michigan Road • Saginaw, MI • 48604-9780
800.748.0423 • 989.752.4275 • Fax 989.752.4444 • www.glastender.com
Rev. 11-11-14
Models BB, ND, LP, FV, MFV, UCR Self Contained
Coolers using Dixell digital thermostat controller
The thermostat control probe wire connector
may become disconnected when the compressor
compartment cover and/or grill are removed. This
will result in thermostat P1 code. While the P1 code is
flashing the compressor will cycle 5 minutes on and 5
minutes off and may cause icing of the evaporator coil.
Service calls to reconnect the probe wiring are not
covered by factory warranty.
Probe wire
connector