7
LED display motion
The motion detection can be displayed via the LED.
Value range (Glamox Sensor-app)
No display of motion detection.
Off
The LED is switched on when motion is detected, otherwise it
remains off.
On
Factory settings
The presence detector is delivered with the following parame-
ter values:
Parameter
Value
Detection zone
Z1 and Z2
Brightness setpoint value A
300 lux
Room correction factor A
0.3
Detection sensitivity (PIR)
Increment 3
Time delay A
10 min
Short presence A
On
Time delay H
10 min
Switch-on delay H
0 s
Configuration type
auto
Control input S
auto
Staircase light function
Off
Group address
I
LED display motion
Off
9. Start-up
Switch-on behaviour
Every time the power supply is switched on, the presence
detector runs through two phases that are shown by an LED:
9.1. Start-up phase (30 s)
•
The red LED flashes at one second intervals, both switch
contacts are closed (light and presence on).
•
The detector does not respond to push button com-
mands and remote control commands.
•
When no one is present, both contacts open after 30 s.
9.2. Operation
The detector is ready for operation (LED off).
Presence test
Presence test mode is used to test presence detection and
wiring. Presence test mode can be activated with the app in
combination with the app remote control or with the poten-
tiometer time delay light.
Setting the presence test mode via remote control
The detector goes directly into test mode when the test mode
is set via the remote control:
Every movement is indicated by the LED.
•
When movement occurs, the light and presence switch
contacts close.
¾
y
When no one is present, the light switch contact opens
after 10 s.
¾
y
Brightness measurement deactivated, detector does
not react to brightness.
¾
y
The detector reacts as in configuration type fully auto
-
matic device, even if semi-automatic is set.
¾
y
Teach-in cannot be activated in test mode.
•
Test mode ends automatically after 10 min. The detector
restarts itself (see switch-on behaviour).
10. Technical data
Operating voltage
110–230 V AC +10 %/–15 %
Frequency
50–60 Hz
Upstream protection device:
13 A
Power consumption
approx. 0.1 W
Type of installation
Ceiling installation; flush/
surface mounted or ceiling
installation
Recommended installation height
2.0–6.0 m
Minimum height
> 1.7 m
Detection area
horizontal
360°
Maximum range
20 x 5 m (Mh. 3.5 m)/100 m
2
radially moving
30 x 5 m (Mh. 3.5 m)/150 m
2
tangentially moving
Setting range brightness setpoint value
30–3000 lux
Light time delay
10 s–60 min/pulse
Presence time delay
10 s–120 min
Switch-on delay "Presence"
0 s–10 min
Channel A light
Relay 230 V/10 A, µ-contact
Max. switching capacity cos
j
1 resistive
2300 W (max. 10 A)
Max. switching capacity cos
j
0.5
1150 VA
Max. switching capacity LED
LED lamp < 2 W
LED lamp > 2 W
see manufacturer concerning cos
j
60 W
180 W
Guidance values max. switch-on current
800 A/200 µs
Maximum number EBs T5/T8
16 x 54/58 W, 24 x 35/36 W
8 x 2x 54/58 W
12 x 2x 35/36 W
Channel H, presence
Relay, floating, base insulation
Maximum voltage
220 V DC/250 V AC
Maximum switching capacity
50 W/50 VA (max. 2 A)
Recommended minimum load
10 mV/10 mA
Connection type
Screw terminals
Max. cable cross-section
Max. 2 x 2.5 mm²
Size of flush-mounted box
Size 1, Ø 55 mm (NIS, PMI)
Protection rating
IP 54 installed
Ambient temperature
–15 °C … +50 °C
CE Declaration of Conformity
This device conforms to the
safety regulations of the EMC
directive 2014/30/EU and of
directive 2014/35/EU.