7

LED display motion

The motion detection can be displayed via the LED.

Value range (Glamox Sensor-app)

No display of motion detection.

Off

The LED is switched on when motion is detected, otherwise it 

remains off.

On

Factory settings

The presence detector is delivered with the following parame-

ter values:

Parameter

Value

Detection zone

Z1 and Z2

Brightness setpoint value A

300 lux

Room correction factor A

0.3

Detection sensitivity (PIR)

Increment 3

Time delay A

10 min

Short presence A

On

Time delay H

10 min

Switch-on delay H

0 s

Configuration type

auto

Control input S

auto

Staircase light function

Off

Group address

I

LED display motion

Off

9.  Start-up

Switch-on behaviour

Every time the power supply is switched on, the presence 

detector runs through two phases that are shown by an LED:

9.1.  Start-up phase (30 s)

 

The red LED flashes at one second intervals, both switch 
contacts are closed (light and presence on).

 

The detector does not respond to push button com-

mands and remote control commands.

 

When no one is present, both contacts open after 30 s.

9.2.  Operation

The detector is ready for operation (LED off).

Presence test 

Presence test mode is used to test presence detection and 

wiring. Presence test mode can be activated with the app in 

combination with the app remote control or with the poten-

tiometer time delay light.

Setting the presence test mode via remote control

The detector goes directly into test mode when the test mode 

is set via the remote control:

Every movement is indicated by the LED.

 

When movement occurs, the light and presence switch 

contacts close.

¾

y

When no one is present, the light switch contact opens 

after 10 s.

¾

y

Brightness measurement deactivated, detector does 

not react to brightness.

¾

y

The detector reacts as in configuration type fully auto

-

matic device, even if semi-automatic is set.

¾

y

Teach-in cannot be activated in test mode.

 

 

Test mode ends automatically after 10 min. The detector 
restarts itself (see switch-on behaviour).

10. Technical data

Operating voltage

110–230 V AC +10 %/–15 %

Frequency

50–60 Hz

Upstream protection device:

13 A

Power consumption

approx. 0.1 W

Type of installation

Ceiling installation; flush/

surface mounted or ceiling 

installation

Recommended installation height

2.0–6.0 m

Minimum height

> 1.7 m

Detection area 

horizontal

360°

Maximum range

20 x 5 m (Mh. 3.5 m)/100 m

2

 

radially moving

30 x 5 m (Mh. 3.5 m)/150 m

2

 

tangentially moving

Setting range brightness setpoint value

30–3000 lux

Light time delay

10 s–60 min/pulse

Presence time delay

10 s–120 min

Switch-on delay "Presence"

0 s–10 min

Channel A light

Relay 230 V/10 A, µ-contact

Max. switching capacity cos 

j

 1 resistive

2300 W (max. 10 A)

Max. switching capacity cos 

j

 0.5

1150 VA

Max. switching capacity LED

LED lamp < 2 W

LED lamp > 2 W

see manufacturer concerning cos 

60 W

180 W

Guidance values max. switch-on current

800 A/200 µs

Maximum number EBs T5/T8

16 x 54/58 W, 24 x 35/36 W

8 x 2x 54/58 W

12 x 2x 35/36 W 

Channel H, presence

Relay, floating, base insulation

Maximum voltage

220 V DC/250 V AC

Maximum switching capacity

50 W/50 VA  (max. 2 A)

Recommended minimum load

10 mV/10 mA

Connection type

Screw terminals

Max. cable cross-section

Max. 2 x 2.5 mm²

Size of flush-mounted box

Size 1, Ø 55 mm (NIS, PMI)

Protection rating

IP 54 installed

Ambient temperature

–15 °C … +50 °C

CE Declaration of Conformity

This device conforms to the 

safety regulations of the EMC 

directive 2014/30/EU and of 

directive 2014/35/EU. 

Содержание B29004005

Страница 1: ...l app remote control LMS MG PROGRAM REMOTE BT B29012003 optional and the corresponding Glamox Sensor app iOS Android safety cover LMS SENSOR SAFETY COVER B29011001 optional 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electrical systems may only be carried out by qualified electricians or by instructed pe...

Страница 2: ...tact is closed the time delay will be restarted at every movement Push buttons or switches do not influence the contact Switch on delay The switch on delay prevents instantaneous switching on The contact closes only on expiry of the switch on delay provided that people are permanently present Time delay The time delay enables delayed switching off of HVAC devices and systems after the room is vaca...

Страница 3: ...h inrush current levels of the EBs and LED drivers The use of an external contactor helps with large loads Parallel switching enables allocation of load to several Masters All switched loads must be properly suppressed 6 Installation Flush mounted fitting The presence detector is flush mounted using a size 1 stan dard flush mounting installation socket Surface mounted installation with LMS MG SURF...

Страница 4: ... on presence Potentiometer Lighting time delay The following guidance values have proved themselves in practice and are recommended as settings Transit zones no work area approx 5 min Classroom approx 10 min Work areas office meeting room approx 10 min Pulse Control of staircase light timer switch 0 5 s on 10 s off Settings of switch contact H presence Potentiometer Presence time delay The contact...

Страница 5: ...of the different brightness measurements at the ceiling and on the work surface the brightness value depends on the ambient conditions Room correction factor Brightness value at the ceiling Brightness value on the floor The brightness measurement value at the ceiling is influenced by the installation location incidence of light position of the sun weather conditions the reflection properties of th...

Страница 6: ... to absence or brightness man Control input S Control input S for manual switch on off of channel A light automatically detects push buttons or switches Several push buttons can be connected to control input S Use light push button only with neutral conductor connector Value range Glamox Sensor app Automatic detection of push button or switch A signal that is present for less than 0 7 s is detecte...

Страница 7: ... light switch contact opens after 10 s y y Brightness measurement deactivated detector does not react to brightness y y The detector reacts as in configuration type fully auto matic device even if semi automatic is set y y Teach in cannot be activated in test mode Test mode ends automatically after 10 min The detector restarts itself see switch on behaviour 10 Technical data Operating voltage 110 ...

Страница 8: ...r Push button not fed to the Master Light cannot be swit ched off with the push button Push button not fed to the detector Check wiring to the push button Device does not respond Short circuit or several phases in parallel swit ching Disconnect detector from the power supply for 5 min thermal fuse Error flashing 4 x per second Error in self test device not functional LED display LED Description Fl...

Отзывы: