Detection sensitivity

The detector has 5 sensitivity increments. The basic setting is 

the middle increment (3). With the app in combination with 

the app remote control, the increments 1 to 5 can be selected 

and sent to the detector.

Increment Sensitivity
1

very insensitive

2

insensitive

3

Standard

4

sensitive

5

very sensitive

By selecting the test presence operating mode, the set sensi-

tivity increment is not changed.

Time delay channel A light

Value range (Glamox Sensor-app)

Time delay for channel A

10 s–60 min

Control for staircase light timer switch  

(0.5 s "on"/10 s "off")

Pulse

Short presence channel A light

The time delay of channel A light can be switched off sooner 

if a room is occupied only for a short time. (In fully automatic 

device and semi-automatic device configuration type).

Value range (Glamox Sensor-app)

The time delay is applied according to the set time delay.

Off

Short-term presence is active.

On

Time delay channel H presence

Channel H presence always switches in case of a presence, 

regardless of whether configuration type is set to fully auto

-

matic device or semi-automatic. The relay contact opens if the 

room is vacated only after the set time delay has expired.

Value range (Glamox Sensor-app)

Presence time delay

10 s–120 min

Switch-on delay channel H presence

The relay contact only closes when someone is present after 

expiry of the set switch-on delay.

Value range (Glamox Sensor-app)

Adjustable values

0 s (no switch-on delay),

30 s, 1–10 min

Configuration type

Value range (Glamox Sensor-app)

Fully automatic device: the lighting switches on and off auto-

matically (depending on presence, absence and brightness)

auto

Semi-automatic: Lights must always be switched on manually.

Lights are automatically switched off by the presence detector 

(due to absence or brightness)

man

Control input S

Control input S for manual switch on/off of channel A light 

automatically detects push buttons or switches.

Several push buttons can be connected to control input S.

¾

†

Use light push button only with neutral conductor 

connector.

Value range (Glamox Sensor-app)

Automatic detection of push button or switch. A signal that 

is present for less than 0.7 s is detected as a push button. 

Longer signals are evaluated as a switch.

 auto

To adapt to user behaviour, the type of 

the used signal transmitter can have 

a fixed setting. Automatic detection is 

deactivated.

When selecting the push button, ope-

ning contact or NO contact can also be 

specified.

Switch

Push button (NO 

contact)

Push button (ope-

ning contact)

  Switch

  Push button 

S

  Push button 

O

Staircase light function

Value range (Glamox Sensor-app)

The lighting can be switched on and off manually.

Off

The lighting can be switched on, but not switched 

off manually. It only switches off after the set time 

delay.

On

Group address

This parameter is applied when using the LMS MG USER 

REMOTE or the app remote control LMS MG PROGRAM 

REMOTE BT user remote control.

A group address can be assigned to each lighting channel. 

The group addresses in the detector can be programmed with 

the app remote control/App or the user remote control.

Value range (Glamox Sensor-app)

Adjustable values LMS MG PROGRAM REMOTE BT

I, II, III

Adjustable values LMS MG PROGRAM REMOTE BT/

App

I–VIII, all

Adjustable values LMS MG USER REMOTE

I, II

Using the user remote control, the group addresses can be 

assigned as follows:

Press the   and 

 buttons simultaneously for at least 5 s

I

Press the   and 

 buttons simultaneously for at least 5 s

II

With the app remote control, the group address can be  

assigned without the app as follows:

Press the   and 

 buttons at the same time for at least 5 s

I

Press button A and the 

 button at the same time for at least 5 s

II

Press the   and 

 buttons at the same time for at least 5 s

III

Содержание B29004005

Страница 1: ...l app remote control LMS MG PROGRAM REMOTE BT B29012003 optional and the corresponding Glamox Sensor app iOS Android safety cover LMS SENSOR SAFETY COVER B29011001 optional 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electrical systems may only be carried out by qualified electricians or by instructed pe...

Страница 2: ...tact is closed the time delay will be restarted at every movement Push buttons or switches do not influence the contact Switch on delay The switch on delay prevents instantaneous switching on The contact closes only on expiry of the switch on delay provided that people are permanently present Time delay The time delay enables delayed switching off of HVAC devices and systems after the room is vaca...

Страница 3: ...h inrush current levels of the EBs and LED drivers The use of an external contactor helps with large loads Parallel switching enables allocation of load to several Masters All switched loads must be properly suppressed 6 Installation Flush mounted fitting The presence detector is flush mounted using a size 1 stan dard flush mounting installation socket Surface mounted installation with LMS MG SURF...

Страница 4: ... on presence Potentiometer Lighting time delay The following guidance values have proved themselves in practice and are recommended as settings Transit zones no work area approx 5 min Classroom approx 10 min Work areas office meeting room approx 10 min Pulse Control of staircase light timer switch 0 5 s on 10 s off Settings of switch contact H presence Potentiometer Presence time delay The contact...

Страница 5: ...of the different brightness measurements at the ceiling and on the work surface the brightness value depends on the ambient conditions Room correction factor Brightness value at the ceiling Brightness value on the floor The brightness measurement value at the ceiling is influenced by the installation location incidence of light position of the sun weather conditions the reflection properties of th...

Страница 6: ... to absence or brightness man Control input S Control input S for manual switch on off of channel A light automatically detects push buttons or switches Several push buttons can be connected to control input S Use light push button only with neutral conductor connector Value range Glamox Sensor app Automatic detection of push button or switch A signal that is present for less than 0 7 s is detecte...

Страница 7: ... light switch contact opens after 10 s y y Brightness measurement deactivated detector does not react to brightness y y The detector reacts as in configuration type fully auto matic device even if semi automatic is set y y Teach in cannot be activated in test mode Test mode ends automatically after 10 min The detector restarts itself see switch on behaviour 10 Technical data Operating voltage 110 ...

Страница 8: ...r Push button not fed to the Master Light cannot be swit ched off with the push button Push button not fed to the detector Check wiring to the push button Device does not respond Short circuit or several phases in parallel swit ching Disconnect detector from the power supply for 5 min thermal fuse Error flashing 4 x per second Error in self test device not functional LED display LED Description Fl...

Отзывы: