briefly. If the sent value is equal to or above the set parame

-

ter, the LED lights flickers for 2 s.

The following control commands can be triggered 

with the remote control:

Control command

Description

Can be trigge-

red by app

Teach-in channel A

Activation

x

Switching light

Lighting group can be switched on 

and off.

x

Presence test 

On/Off

x

Restart

Restart detector

x

Factory settings

Set all parameters and settings to 

factory setting.

x

Detection zone

The detection area is divided into two independent detection 

zones (see 5. Detection area). For a maximum range, zone 1 

and zone 2 are activated. If a limitation of the detection area 

is required, zone 1 or zone 2 can be deactivated.

Value range (Glamox Sensor-app)

Selection of detection area

Z1, Z2, Z1 and Z2

Brightness setpoint channel A light

Brightness setpoint A defines the minimum desired bright

-

ness. The currently prevailing brightness is measured under

-

neath the presence detector. If the prevailing brightness is 

below the setpoint value, the light is switched on when a 

presence is detected (in configuration type fully automatic 

device).

Value range (Glamox Sensor-app)

Min. brightness setpoint value

30–3000 Lux

Deactivation of brightness measurement (brightness 

measurement has no effect)

The lighting channels only switch according to presence 

and absence.

Measurement off

Teach-in channel A light

During teach-in, the currently measured brightness value is 

accepted as brightness setpoint value A. Values outside the 

permitted range will automatically be set to the appropriate 

limit value.

Value range (Glamox Sensor-app)

Teach-in channel A

Teach-in for channel A light

Brightness actual value A

The brightness actual value can be checked for monitoring 

purposes. To check, see the „Parameters ans commands via 

remote control“ table.

Room correction factor lighting A, Brightness 

measurement value lighting A

The room correction factor is a measure of the different 

brightness measurements at the ceiling and on the work 

surface (the brightness value depends on the ambient 

conditions).

Room correction factor = Brightness value at the ceiling 

 

 

 

Brightness value on the floor

The brightness measurement value at the ceiling is influenced 

by the installation location, incidence of light, position of the 

sun, weather conditions, the reflection properties of the room, 

and the furniture. In order to be able to adhere to the requi

-

red lux value in the desired area, a comparison of the bright-

ness measurements is necessary.

The measured lux meter value 

 below the presence detector 

is sent to the detector via the remote control.

When sending the brightness measurement value, the room 

correction factor of the corresponding lighting channel is 

automatically adjusted to the conditions inside the room.

Two different procedures can be selected in the app for the 

comparison (automatic/manual calibration).

¾

†

Connect the app remote control LMS MG PROGRAM 

REMOTE BT with the corresponding Glamox Sensor-app.

¾

†

Select the appropriate detector type <LMS MG PIR CLS 

SENSOR-R LONG> and load the parameter set.

¾

†

Select the <Brightness measurement value A> parameter.

Automatic calibration

¾

†

Set up the LMS MG PROGRAM REMOTE BT according to 

the drawing, and move a few steps away from the mea-

surement location, so the lux measurement will not be 

influenced.

¾

†

Press OK.

 

A new window with the measured brightness measu-

rement value is shown. If you would like to apply this 

value,

¾

†

Press OK.

¾

†

Important

: Press the send button (

). After this, the 

brightness measurement is calibrated.

Manuel calibration using the lux meter

¾

†

Set up or align the lux meter according to the drawing, and 

read the lux value.

¾

†

Press „Enter“ in the app.

 

▻ A new window opens. 

¾

†

Enter the lux value and press OK.

 

The brightness measurement value appears in the 

display. 

¾

†

Important

: Press the send button (

). After this, the 

brightness measurement is calibrated.

 

The calculated room correction factor is adopted. The 

room correction factor can be checked via the <Room 

correction factor A> parameter for monitoring purposes. 
The default value is 0.3.

Содержание B29004005

Страница 1: ...l app remote control LMS MG PROGRAM REMOTE BT B29012003 optional and the corresponding Glamox Sensor app iOS Android safety cover LMS SENSOR SAFETY COVER B29011001 optional 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electrical systems may only be carried out by qualified electricians or by instructed pe...

Страница 2: ...tact is closed the time delay will be restarted at every movement Push buttons or switches do not influence the contact Switch on delay The switch on delay prevents instantaneous switching on The contact closes only on expiry of the switch on delay provided that people are permanently present Time delay The time delay enables delayed switching off of HVAC devices and systems after the room is vaca...

Страница 3: ...h inrush current levels of the EBs and LED drivers The use of an external contactor helps with large loads Parallel switching enables allocation of load to several Masters All switched loads must be properly suppressed 6 Installation Flush mounted fitting The presence detector is flush mounted using a size 1 stan dard flush mounting installation socket Surface mounted installation with LMS MG SURF...

Страница 4: ... on presence Potentiometer Lighting time delay The following guidance values have proved themselves in practice and are recommended as settings Transit zones no work area approx 5 min Classroom approx 10 min Work areas office meeting room approx 10 min Pulse Control of staircase light timer switch 0 5 s on 10 s off Settings of switch contact H presence Potentiometer Presence time delay The contact...

Страница 5: ...of the different brightness measurements at the ceiling and on the work surface the brightness value depends on the ambient conditions Room correction factor Brightness value at the ceiling Brightness value on the floor The brightness measurement value at the ceiling is influenced by the installation location incidence of light position of the sun weather conditions the reflection properties of th...

Страница 6: ... to absence or brightness man Control input S Control input S for manual switch on off of channel A light automatically detects push buttons or switches Several push buttons can be connected to control input S Use light push button only with neutral conductor connector Value range Glamox Sensor app Automatic detection of push button or switch A signal that is present for less than 0 7 s is detecte...

Страница 7: ... light switch contact opens after 10 s y y Brightness measurement deactivated detector does not react to brightness y y The detector reacts as in configuration type fully auto matic device even if semi automatic is set y y Teach in cannot be activated in test mode Test mode ends automatically after 10 min The detector restarts itself see switch on behaviour 10 Technical data Operating voltage 110 ...

Страница 8: ...r Push button not fed to the Master Light cannot be swit ched off with the push button Push button not fed to the detector Check wiring to the push button Device does not respond Short circuit or several phases in parallel swit ching Disconnect detector from the power supply for 5 min thermal fuse Error flashing 4 x per second Error in self test device not functional LED display LED Description Fl...