VIRTUAL PUSH BUTTON
SAFETY-DURING-OPENING
Install 1 or 2 virtual push buttons as activation zone(s) to open the door «manually».
Configure a second detection field to secure the door during opening.
Make sure the white and yellow wires are connected to the corresponding inputs before you choose one of the
following two configurations.
Apply the vitual push button sticker(s)
within the opening field.
After setting the mounting side, the safety and the
optional field will have the same dimensions.
Adjust the size of the field by remote control.
Launch a PB teach-in to configure the detection
zone(s). Launch a new PB teach-in each time the
sensor position is changed or new objects are
added to or changed in the detection zone.
ATTENTION! This PB teach-in is different from the
safety field teach-in.
When the red LED flashes very slowly after 3
seconds, hold your hand in front of the sticker to
learn the detection zone. The green LED flashes 3x
to confirm the selection.
When the red LED flashes again, learn a second
(max. 2) detection zone or wait until the LED
switches to green.
OPTIONAL FIELD CONFIGURATIONS
WIDTH
0.5 m
9.9 m
0.5 m
5.0 m
HEIGHT
0.5 m
9.9 m
0.5 m
5.0 m
no field
no field
same as
safety
field
same as
safety
field
3 s
OR
Change the output redirection if needed.
Change the output redirection if needed.
In order to cancel the virtual push button function, you have to launch a new PB teach-in without any
movement in the detection field. Only then the safety-during-opening can be configured.