5.2 Commissioning 

Commissioning with DALI control unit 

Commissioning depends on the control unit being used. 
The system is fitted and connected. 

Switch on mains voltage. 
Transformer switches to maximum brightness. 

Perform commissioning (see instructions for control unit) 

Commissioning with installation button 

The system is fitted and connected. 

Switch on mains voltage. 
Transformer switches to maximum brightness. 

Press installation button until the transformer starts dimming. 
The transformer has detected the installation button and can now be operated. 

6 Appendix 

6.1 Technical data 

Rated voltage 

AC 230 / 240 V ~ 

Mains frequency 

50 / 60 Hz 

Rated voltage 

DC 230 / 240 V 

Battery voltage 

DC 176 ... 275 V 

Primary current 

0.16 ... 0.5 A 

Rated load 

35 ... 105 W 

Minimum connected load 

35 W 

Standby power 

max. 0.5 W 

Power loss 

max. 6 W 

Power factor 

0.95 

Output voltage 

AC 11.8 V~ eff. 

Ambient temperature 

-20 ... +50 °C 

Housing temperature 

75 °C (tc) 

Protection rating 

IP 20 

Safety class 

II 

Primary side connection 
Single stranded 

0.5 ... 1.5 mm² 

finely stranded with conductor sleeve 

0.5 ... 1.5 mm² 

finely stranded without conductor sleeve 

0.5 ... 1.5 mm² 

Secondary side connection 
Single stranded 

0.75 ... 2.5 mm² 

finely stranded with conductor sleeve 

0.75 ... 2.5 mm² 

single stranded without conductor sleeve 

0.75 ... 2.5 mm² 

Secondary cable length 

0.3 ... 2 m 

Dimensions W×H×D 

170×44×34 mm 

6.2 Troubleshooting 

Device switches off 

Cause: short-circuit protection has tripped. 

Eliminate short-circuit. 

The transformer switches on again after the short-circuit is eliminated 

Light becomes dimmer without being operated and brighter again after some time 

Cause: overheating protection adjusts the power downwards to allow the transformer to cool, 
and then raises it again. 

Check the installation situation. 

82575902 

13.05.2011 

6/7 

DALI Tronic transformer 105 W 

Содержание DALI Tronic Trafo 105 W

Страница 1: ...the device or load These instructions are an integral part of the product and must remain with the end customer 2 Device components Figure 1 1 Fastening screws for terminal cover 2 Mounting holes 3 Te...

Страница 2: ...ghtness value Adjusting brightness with installation button Light is switched on o Make a long press on the installation button Light becomes brighter or dimmer as far as the respective limit value i...

Страница 3: ...must not be exceeded Do not fit in the vicinity of heat sources e g lamps o Loosen screws 1 and remove terminal covers 3 o Fasten transformer with screws through mounting holes 2 Connection instructi...

Страница 4: ...V F 2 1 5mm2 H05VVH2 F 2 0 75mm2 H05VV F 2 2 5mm2 NYM J 3 1 5mm2 NYM J 3 1 5mm2 NYM O 2 1 5mm2 NYM O 2 1 5mm2 NYM J 3 2 5mm2 Figure 3 Stripping lengths o Strip connecting cables according to specifica...

Страница 5: ...ng transformer with installation button Figure 5 Connection diagram with installation button i Illuminated installation buttons may only be connected if they have a separate N terminal i Connect all t...

Страница 6: ...ower loss max 6 W Power factor 0 95 Output voltage AC 11 8 V eff Ambient temperature 20 50 C Housing temperature 75 C tc Protection rating IP 20 Safety class II Primary side connection Single stranded...

Страница 7: ...ease submit or send faulty devices postage paid together with an error description to your responsible salesperson specialist trade installation company electrical specialist trade They will forward t...

Отзывы: