Dim up ramp
0 s … 24 h
Basic setting: 0 s
Time between switch-on and
reaching switch-on brightness.
The light is switched on at
minimum brightness and then
dimmed to the switch-on
brightness.
Only applies to switch-on with
transmitters (short operation).
If scenes are recalled or
switching uses logic modules,
the switch-on brightness is
approached using so-called
soft dimming (not
configurable).
Dim down ramp
0 s … 24 h
Basic setting: 0 s
Time until reaching minimum
brightness. The light is
dimmed to minimum
brightness and then switched
off.
Only applies to switch-off with
transmitters (short operation).
If scenes are recalled or
switching uses logic modules,
the system switches off
directly.
Run-on time
0 s … 24 h
Basic setting: 0 s
As soon as a run-on time has
been entered, the actuator will
no longer remain on
permanently, but only for the
length of the run-on time. The
run-on time is restarted if
actuation is repeated. This
parameter is directly
connected to the "Manual
switch-off of run-on time"
parameter.
Note: The set time apply to
operation using radio
transmitters. The device is
switched immediately when
the
Prog
button is pressed.
Manual switch-off of the run-
on time
On, Off
Basic setting: Off
Allows manual switch-off of a
running run-on time. If the
parameter is switched off, then
a switch-off command will also
switch the actuator on. Only
visible if a run-on time was
set.
Operating hours
0...65535
Basic setting: Current value
The time is counted during
which the load is physically
switched on.
This parameter can be reset to
"0", for example after
exchanging the load.
The Reset button is used to
reset the meter to "0". The
device must be programmed
to apply the change.
32582722
10864994
27.04.2017
7/15
Wireless switching/dimming top unit, 1-gang