Dim up ramp

0 s … 24 h
Basic setting: 0 s

Time between switch-on and
reaching switch-on brightness.
The light is switched on at
minimum brightness and then
dimmed to the switch-on
brightness.
Only applies to switch-on with
transmitters (short operation).
If scenes are recalled or
switching uses logic modules,
the switch-on brightness is
approached using so-called
soft dimming (not
configurable).

Dim down ramp

0 s … 24 h
Basic setting: 0 s

Time until reaching minimum
brightness.  The light is
dimmed to minimum
brightness and then switched
off.
Only applies to switch-off with
transmitters (short operation).
If scenes are recalled or
switching uses logic modules,
the system switches off
directly.

Run-on time

0 s … 24 h
Basic setting: 0 s

As soon as a run-on time has
been entered, the actuator will
no longer remain on
permanently, but only for the
length of the run-on time. The
run-on time is restarted if
actuation is repeated. This
parameter is directly
connected to the "Manual
switch-off of run-on time"
parameter.
Note: The set time apply to
operation using radio
transmitters. The device is
switched immediately when
the 

Prog

 button is pressed.

Manual switch-off of the run-
on time

On, Off
Basic setting: Off

Allows manual switch-off of a
running run-on time. If the
parameter is switched off, then
a switch-off command will also
switch the actuator on. Only
visible if a run-on time was
set.

Operating hours

0...65535
Basic setting: Current value

The time is counted during
which the load is physically
switched on.
This parameter can be reset to
"0", for example after
exchanging the load.
The Reset button is used to
reset the meter to "0". The
device must be programmed
to apply the change.

32582722

10864994

27.04.2017

7/15

Wireless switching/dimming top unit, 1-gang

Содержание 5490 Series

Страница 1: ... suitable for disconnection from supply voltage Depending on the insert used the load is not electrically isolated from the mains even when the device is switched off These instructions are an integral part of the product and must remain with the end customer 2 Device components Figure 1 Device components 1 FM insert 2 Frame 3 Radio button 4 Status LED 3 Function Intended use Manual and radio cont...

Страница 2: ...ace with radio transmitters please observe the radio transmitter instructions Switch light o Press button for less than 0 4 seconds The light is switched on or off In combination with inserts for dimming switch on takes place at the saved switch on brightness Status LED 4 lights up output is switched on Status LED 4 off output is switched off i In the case of the HVAC insert only the output Kanal ...

Страница 3: ...from any possible sources of interference e g metallic surfaces microwave ovens hi fi and TV systems ballasts or transformers The flush mounted insert is correctly fitted and connected see instructions for flush mounted insert o Fit radio button 3 and frame 2 on flush mounted insert 1 o Switch on mains voltage o Carry out commissioning see Commissioning chapter 5 2 Commissioning DANGER Electrical ...

Страница 4: ...adio transmitter are disconnected automatically as soon as the last connection to the radio transmitter is disconnected Manual disconnection is not possible Resetting button to the default setting All connections to radio transmitters are disconnected and parameters are reset to default setting i The connections in the radio transmitters are preserved and must be deleted separately Load is switche...

Страница 5: ... Continuous off Basic setting Normal Operation Normal operation The output can be operated with radio transmitters and the Prog button Continuous on The output switches to continuously On All operations of radio transmitters and the Prog button are ignored Continuous off The output switches to continuously Off All operations of radio transmitters and the Prog button are ignored Advanced device set...

Страница 6: ...60 s Basic setting 4 s Time from minimum brightness until reaching maximum brightness dimming speed Switch on delay 0 s 24 h Basic setting 0 s The load switches on after a delay Repeated switch on commands restart the delay time If the load has not yet been switched on due to the delay when a switch off command comes then the load will remain off Note The set time apply to operation using radio tr...

Страница 7: ...actuator will no longer remain on permanently but only for the length of the run on time The run on time is restarted if actuation is repeated This parameter is directly connected to the Manual switch off of run on time parameter Note The set time apply to operation using radio transmitters The device is switched immediately when the Prog button is pressed Manual switch off of the run on time On O...

Страница 8: ...the output after voltage return Brightness on voltage return 0 100 Basic setting 100 Brightness value set by the output after voltage return mains voltage The parameter Behaviour after voltage return must be set to Configured brightness Note If the value is above the set maximum brightness or below the minimum brightness then the system will switch to the appropriate limit value Behaviour after th...

Страница 9: ... 0 100 Basic setting 0 Defines the behaviour of the output on activating the lock out protection Deactivate lock out protection brightness value 0 100 Basic setting 0 Defines the behaviour of the output on deactivating the lock out protection Only visible when the priority for the lock out protection is 0 Priority restraint 0 4 Basic setting 2 Specifies the priority for recalling and removing a sc...

Страница 10: ...utput on activating the twilight function Deactivate twilight brightness value 0 100 Basic setting 0 Defines the behaviour of the output on deactivating the twilight function Only visible when the priority for the twilight function is 0 Switch off brightness overshoot On Off Basic setting On Allows automatic switch off according to the brightness If the parameter is On then the light controller sw...

Страница 11: ...s switched immediately when the Prog button is pressed Switch off delay 0 s 24 h Basic setting 0 s The load switches off after a delay Repeated switch off commands restart the delay time If the load has not yet been switched off due to the delay when a switch on command comes then the load will remain on Note The set time apply to operation using radio transmitters The device is switched immediate...

Страница 12: ...uous on Continuous off Basic setting Normal Operation see Device and channels Manual commissioning On Off Basic setting On Blocks manual commissioning for the device channel Note In the Off setting the device cannot be reset to the factory setting Local Operation On Off Basic setting On Blocks the output for operation using the Prog button Behaviour on voltage return On Off Last value Basic settin...

Страница 13: ...ff Basic setting Off Defines the behaviour of the output on activating the lock out protection Deactivate lock out protection switching state On Off Basic setting Off Defines the behaviour of the output on deactivating the lock out protection Only visible when the priority for the lock out protection is 0 Priority restraint 0 4 Basic setting 2 Specifies the priority for recalling and removing a sc...

Страница 14: ...Off Basic setting Off Defines the behaviour of the output on deactivating the twilight function Only visible when the priority for the twilight function is 0 Information window In the Information window the load can be controlled and the information about the device can be displays Channel control channel information Display value Explanations Current dimming value The load can be dimmed using the...

Страница 15: ... specialist trade installation company electrical specialist trade They will forward the devices to the Gira Service Center Gira Giersiepen GmbH Co KG Elektro Installations Systeme Industriegebiet Mermbach Dahlienstraße 42477 Radevormwald Postfach 12 20 42461 Radevormwald Deutschland Tel 49 0 21 95 602 0 Fax 49 0 21 95 602 191 www gira de info gira de 32582722 10864994 27 04 2017 15 15 Wireless sw...

Отзывы: