background image

KNX
Product documentation

Last edited:
25/03/2019

Alarm control unit Connect

Order No. 5201 00

Содержание 5201 00

Страница 1: ...KNX Product documentation Last edited 25 03 2019 Alarm control unit Connect Order No 5201 00...

Страница 2: ...10 4 2 1 KNX connection 10 4 2 2 Secure remote access with Gira S1 11 4 3 KNX functions 11 4 4 Topology 12 4 4 1 Alarm control unit Connect in main line 12 4 4 2 Alarm control unit Connect in area lin...

Страница 3: ...ay unit Connects landline phone for remote alarming optional GSM module In the event of mains failure internal rechargeable battery pack takes over power supply for at least 12 hours 1 3 Device compon...

Страница 4: ...electrical outputs Per output max 200 mA Total outputs 1 A Wireless Frequency band 868 0 868 6 MHz 868 7 869 2 MHz Range 100 m free field Device general Connections LAN RJ45 Phone Analog via terminal...

Страница 5: ...stallation may result in serious injury e g from electrical shock or fire as well as equipment damage Do not open the device housing Always observe the device s technical specifications This product c...

Страница 6: ...cover closed operating mode Position 1 Push the housing cover up until the screws of the hinged cover are exposed and the housing cover is noticeably blocked Loosen the two screws in the hinged cover...

Страница 7: ...er devices unsuit able metal doors or cabinets or direct vicinity of fuse boxes and electricity meters Mounting methods other than wall mounting are not allowed Select the installation location so tha...

Страница 8: ...put plug terminals 12V DC 12 V max 200 mA GND Ground OUT1 OUT2 Open Drain Max switching current DC 12 V 200 mA 1 Connect the Ethernet cable to the LAN port 2 Connect the battery pack and switch on the...

Страница 9: ...ed via ETS 5 or higher Notes You can find the KNX product database and the technical documentation on the internet at www download gira de KNX IP uses Multicast to mirror KNX bus group communication o...

Страница 10: ...n The Gira Alarm Connect security system with Gira G1 alarm client and smartphone app to act as addi tional operating and display devices Connected to KNX via KNX IP router 868 MHz LAN WLAN AC 230 V K...

Страница 11: ...ital certificates for details see Gira S1 operating instructions Smartphone and app then use encrypted direct access to the alarm control unit Connect through the Gira device portal 4 3 KNX functions...

Страница 12: ...it Connect is operated in the main line together with the Gira G1 in this case the KNX IP router is used as a line coupler Topology example Alarm control unit Connect in main line IP Network Alarm con...

Страница 13: ...ng KNX functions Order No 5201 00 Page 13 When installing the alarm control unit Connect in the main line the configuration in ETS 5 would be as follows ETS 5 screenshot Alarm control unit Connect in...

Страница 14: ...area coupler and the area line coupler is used as a line coupler Topology example Alarm control unit Connect in area line IP Network Bus device 1 1 1 Bus device 1 1 2 Alarm control unit Connect GIRA...

Страница 15: ...ng KNX functions Order No 5201 00 Page 15 When installing the alarm control unit Connect in the area line the configuration in ETS 5 would be as follows Topology example Alarm control unit Connect in...

Страница 16: ...ring and starting up the alarm control unit Connect requires ETS 5 or higher and the Gira Pro ject Assistant version 4 or higher The required product database is available in knxprod format The corres...

Страница 17: ...ple a KNX communication object or a data point If you activate this option you will also need to activate the alarms that you want the external detec tors in this security area to trigger The KNX comm...

Страница 18: ...PA data points select the desired alarms here Notes ETS always shows the alarm control unit s communication objects However they can for security reasons only be used if the Use KNX communication obje...

Страница 19: ...to the device will be through IP Notes You can only program the physical address and application software when the housing cover is open Important When you open the housing cover a tamper alarm trigge...

Страница 20: ...elect the GIALRMKXIP device data point 5 Open KNX programming mode 6 Enter value 1 and hit enter to confirm Programming mode activates 7 Program the physical address using the ETS 8 Note the physical...

Страница 21: ...254 254 255 is issued after a certain waiting time You can also issue a static IP address via the ETS or the Gira Project Assistant You can set IP address IP subnet mask and IP standard gateway here N...

Страница 22: ...h Shutting down The alarm control unit Connect will reboot 03h Configuring The alarm control unit Connect is currently being con figured 04h FFh Reserved Object Name Function Type DP type Flags 6 Alar...

Страница 23: ...ctivated Object Name Function Type DP type Flags 1025 Alarm control unit Test mode 1 bit 1 011 status C R T Object for transmitting test mode 1 means test mode is activated and 0 means that test mode...

Страница 24: ...g C W Object for writing burglar alarm 1 sends an alarm 0 resets the alarm the system can be secured again Object Name Function Type DP type Flags 1122 1222 1322 1422 Main security area security area...

Страница 25: ...urity area 4 Panic alarm status 1 bit 1 011 status C R T Object for reading whether a panic alarm has been triggered 1 means yes 0 means no Object Name Function Type DP type Flags 1132 1232 1332 1432...

Страница 26: ...atus C R T Object for reading whether a service call has been triggered 1 means yes 0 means no Object Name Function Type DP type Flags 1138 1238 1338 1438 Main security area security area 2 security a...

Страница 27: ...rea 4 Urgent techni cal alarm 1 bit 1 001 switching C W Object for writing urgent technical alarm 1 sends an alarm 0 resets the alarm Object Name Function Type DP type Flags 1144 1244 1344 1444 Main s...

Страница 28: ...this case NTP is deactivated Only one time server may be assigned to the alarm control unit Display KNX statuses Checkbox active This option enables the communication objects for programming mode and...

Страница 29: ...Page 29 Gira Giersiepen GmbH Co KG Electrical installation systems Industriegebiet Mermbach Dahlienstrasse 42477 Radevormwald Germany PO Box 12 20 42461 Radevormwald Germany Tel 49 0 21 95 602 0 Fax 4...

Отзывы: