Switching actuator / blind actuator 16 A Standard & Komfort

5.2 Commissioning

Commissioning the device

NOTICE!

Incorrect load control due to undefined relay state at delivery.

Risk of destruction of connected drive motors.

During commissioning, before switching on the load, ensure that all relay contacts
are open by applying the KNX bus voltage. Observe commissioning sequence!

Switch on the KNX bus voltage.

Wait about 10 s.

Switch on load circuits.

Delivery state: The outputs can be operated with manual control. Outputs are set as vene-
tion blind outputs.

Load physical address and application program

For switched loads, configure the outputs as a switching output.

For Venetian blind operation, configure the outputs as a Venetian blind output.

In Venetian blind operation: measure blind/shutter and slat travel times and enter them in
the parameter setting.

Press the programming button.
The programming LED lights up.

Load physical address and application program using the ETS.

Safe-state mode

The safe state mode stops the execution of the loaded application program.

Only the system software of the device is still functional. ETS diagnosis functions and pro-
gramming of the device are possible. Manual operation is not possible.

Activating the safe-state mode

Switch off the bus voltage or remove the KNX device connection terminal.

Wait about 15 s.

Press and hold down the programming button.

Switch on the bus voltage or attach the KNX device connection terminal. Release the pro-
gramming button only after the programming LED starts flashing slowly.
The safe-state mode is activated.

With a new brief press of the programming button, the programming mode can be
switched on and off as usual also in the safe-state mode. If Programming mode is active,
the programming LED stops flashing.

Deactivating safe-state mode

Switch off bus voltage (wait approx. 15 s) or carry out ETS programming.

Master reset

The master reset restores the basic device setting (physical address 15.15.255, firmware re-
mains in place). The device must then be recommissioned with the ETS. Manual operation is
possible.

During secure operation: A master reset deactivates device security. The device can then be re-
commissioned with the device certificate.

Performing a master reset

Precondition: The safe-state mode is activated.

7 / 9

82402612

23.09.2020

Содержание 5023 00

Страница 1: ...utside the technical specifications Danger of electric shock Device is not suitable for disconnection from supply voltage Danger of electric shock on the SELV PELV installation Do not connect loads fo...

Страница 2: ...out with the aid of the ETS version 5 7 3 and above Intended use Switching of electrical loads with potential free contacts Switching of electrically driven Venetian blinds roller shutters awnings and...

Страница 3: ...us manual mode active Flashing temporary manual control active 8 LED ON relay outputs closed manual operation active 9 Button Short switch on adjust slats or stop Long Move hanging upwards 10 Button S...

Страница 4: ...ey press the actuator returns automatically to bus operation Switching off temporary manual operation The device is in short term manual mode No button press for 5 s or Press 6 button briefly as many...

Страница 5: ...gs The device is in continuous manual mode Press the ALL OFF button 7 Switching outputs All outputs switch off NO operating mode relay output opened NC op erating mode relay output closed Venetian bli...

Страница 6: ...Mount device on DIN rail In secure operation The device certificate must be removed from the device and stored securely Connecting the device Figure 3 Device connection connection example Connect bus...

Страница 7: ...program Only the system software of the device is still functional ETS diagnosis functions and pro gramming of the device are possible Manual operation is not possible Activating the safe state mode S...

Страница 8: ...transport temperature 25 70 C KNX KNX medium TP256 Commissioning mode S mode Rated voltage KNX DC 21 32 V SELV Current consumption KNX Order no 5023 00 5028 00 5033 00 5038 00 5 18 mA Order no 5030 0...

Страница 9: ...stranded without conductor sleeve 0 5 4 mm Finely stranded with conductor sleeve 0 5 2 5 mm Connection torque screw terminals max 0 8 Nm 7 Warranty The warranty is provided in accordance with statuto...

Отзывы: