Switching actuator / blind actuator 16 A Standard & Komfort
5.2 Commissioning
Commissioning the device
NOTICE!
Incorrect load control due to undefined relay state at delivery.
Risk of destruction of connected drive motors.
During commissioning, before switching on the load, ensure that all relay contacts
are open by applying the KNX bus voltage. Observe commissioning sequence!
■
Switch on the KNX bus voltage.
■
Wait about 10 s.
■
Switch on load circuits.
Delivery state: The outputs can be operated with manual control. Outputs are set as vene-
tion blind outputs.
Load physical address and application program
■
For switched loads, configure the outputs as a switching output.
■
For Venetian blind operation, configure the outputs as a Venetian blind output.
■
In Venetian blind operation: measure blind/shutter and slat travel times and enter them in
the parameter setting.
■
Press the programming button.
The programming LED lights up.
■
Load physical address and application program using the ETS.
Safe-state mode
The safe state mode stops the execution of the loaded application program.
Only the system software of the device is still functional. ETS diagnosis functions and pro-
gramming of the device are possible. Manual operation is not possible.
Activating the safe-state mode
■
Switch off the bus voltage or remove the KNX device connection terminal.
■
Wait about 15 s.
■
Press and hold down the programming button.
■
Switch on the bus voltage or attach the KNX device connection terminal. Release the pro-
gramming button only after the programming LED starts flashing slowly.
The safe-state mode is activated.
With a new brief press of the programming button, the programming mode can be
switched on and off as usual also in the safe-state mode. If Programming mode is active,
the programming LED stops flashing.
Deactivating safe-state mode
■
Switch off bus voltage (wait approx. 15 s) or carry out ETS programming.
Master reset
The master reset restores the basic device setting (physical address 15.15.255, firmware re-
mains in place). The device must then be recommissioned with the ETS. Manual operation is
possible.
During secure operation: A master reset deactivates device security. The device can then be re-
commissioned with the device certificate.
Performing a master reset
Precondition: The safe-state mode is activated.