Switching actuator / blind actuator 16 A Standard & Komfort

5.1 Fitting and electrical connection

Fitting the device

In secure operation (preconditions):

Secure commissioning is activated in the ETS.

Device certificate entered/scanned or added to the ETS project. A high resolution camera
should be used to scan the QR code.

Document all passwords and keep them safe.

Observe ambient temperature. Ensure adequate cooling.

Mount device on DIN rail.

In secure operation: The device certificate must be removed from the device and stored
securely.

Connecting the device

Figure 3: Device connection (connection example):

Connect bus line with KNX connecting terminal according to their correct polarity.

Attach the cover cap to the KNX connection as protection against hazardous voltages.

Connect load as shown in the connection example. Two adjacent relay outputs form a
Venetian blind output.

The total current capacity of neighbouring outputs is a maximum of 20 A.

Figure 4: Total current capacity of neighbouring outputs

6 / 9

82402612

23.09.2020

Содержание 5023 00

Страница 1: ...utside the technical specifications Danger of electric shock Device is not suitable for disconnection from supply voltage Danger of electric shock on the SELV PELV installation Do not connect loads fo...

Страница 2: ...out with the aid of the ETS version 5 7 3 and above Intended use Switching of electrical loads with potential free contacts Switching of electrically driven Venetian blinds roller shutters awnings and...

Страница 3: ...us manual mode active Flashing temporary manual control active 8 LED ON relay outputs closed manual operation active 9 Button Short switch on adjust slats or stop Long Move hanging upwards 10 Button S...

Страница 4: ...ey press the actuator returns automatically to bus operation Switching off temporary manual operation The device is in short term manual mode No button press for 5 s or Press 6 button briefly as many...

Страница 5: ...gs The device is in continuous manual mode Press the ALL OFF button 7 Switching outputs All outputs switch off NO operating mode relay output opened NC op erating mode relay output closed Venetian bli...

Страница 6: ...Mount device on DIN rail In secure operation The device certificate must be removed from the device and stored securely Connecting the device Figure 3 Device connection connection example Connect bus...

Страница 7: ...program Only the system software of the device is still functional ETS diagnosis functions and pro gramming of the device are possible Manual operation is not possible Activating the safe state mode S...

Страница 8: ...transport temperature 25 70 C KNX KNX medium TP256 Commissioning mode S mode Rated voltage KNX DC 21 32 V SELV Current consumption KNX Order no 5023 00 5028 00 5033 00 5038 00 5 18 mA Order no 5030 0...

Страница 9: ...stranded without conductor sleeve 0 5 4 mm Finely stranded with conductor sleeve 0 5 2 5 mm Connection torque screw terminals max 0 8 Nm 7 Warranty The warranty is provided in accordance with statuto...

Отзывы: