Operating and alarm signals
General
Acoustic signal
Light ring
Meaning
Loud intermittent
Flashes rapidly
Local alarm -
signal 85 dB(A)
Smoke or heat
8 short signals
Flashes 8x
Fault/soiling - Cannot be
in 60-sec. cycle
in 8-sec. cycle
deactivated
2 short signals
Flashes 1x
Battery change due (local)
in 60-sec. cycle
in 5-sec. cycle
1-sec. continuous
Continously on
Function test (local),
signal 73 dB(A)
(previous event was activated by pressing the
an alarm)
function button for at least
4 s (Section 7)
1-sec. continuous
Flashes rapidly
Function test (local),
signal 73 dB(A)
(previous event was
activated by pressing the
not an alarm)
function button for at least
4 s (Section 7)
If using the 230 V base, please follow the
instructions in the corresponding
Installation and User Manual. Different
signals are used to indicate “Fault”,
“Soiling”, and “Battery change due”.