4-channel blind/shutter actuator 230 V~

Installation Instructions

4-channel blind/shutter actuator 230 V~

1/07

Page 7 of 10

Commisioning 

Measuring the blind/shutter and slat running 

times

The blind/shutter running time is important for posi-
tioning and scene moves. With Venetian blinds, the 
slat adjusting time is for technical reasons part of the 
overall running time of blinds/shutters.
The opening angle of the slats is therefore defined as 
the running time required between the „open“ and 
„closed“ positions.
The upward move is generally longer than the down-
ward move and is accounted for as running time pro-
longation in percent.

• Measure the „up“ and „down“ running times of the 

blind/shutter.

• Measure the slat adjusting time between „open“ 

and „closed“.

• Enter the measured values into the parameter set-

tings list. 

Loading the address and the application software

• Switch on the bus voltage.
• Allocate the physical address and load the applica-

tion software into the device.

Performing a reference run

The shutter actuator can move the blind/shutters into 
scene and other directly controlled positions only if 
the positions have been stored beforehand. For this 
purpose, every output must perform a reference run.

• Move the blinds/shutters to the upper limit-stop po-

sition.

• Wait until the output relay and the limit switch are 

off.      

Automatic running time detection: storing the 

running times

With the running time detection activated, the device 
can find positions and scenes only if the running times 
have been stored beforehand. The running times 
must be stored in undisturbed conditions, i.e. without 
any control operations being performed and in the ab-
sence of wind, snow and obstacles.   

The automatic running time detection function is acti-
vated in the software.

The N conductor terminals of the pertaining outputs 
are connected as shown (Fig. 5).              

• Move the blinds/shutters into the upper limit-stop 

position (perform a reference run).

The upper limit-stop position is reached.

• Move the blinds/shutters in the manual control 

mode into the lower limit-stop position.

• Move the blinds/shutters in the manual control 

mode into the upper limit-stop position.
The running times are now stored.

i

In case of automatic running time detec-
tion no measurement of the blind/shutter 
running times is required.
Automatic measurement of the slat adjust-
ing time is not possible.

i

The shutter actuator does not store the 
blind/shutter positions permanently. After 
each failure and return of the mains, a new 
reference run is performed. 
Without reference run, the shutter actuator 
sets for each output the internal flag 

‚Inva-

lid position‘ 

which can be read out.

i

For 230 V drives only.

i

Programming runs must be performed 
only in the manual control mode or with the 
commissioning software.

i

The shutter actuator stores the blind/shut-
ter positions permanently.

Without stored running times, the shutter 
actuator sets for each output the internal 
flag ‚Invalid position‘ which can be read 
out.

In operation, the shutter actuator can 
adapt itself to changes in the running times 
of the blinds/shutters that are due, for in-
stance, to ageing of the drives. The slat 
running time is taken into account.

The modified times are stored permanent-
ly only in the manual control mode.

Содержание 1039 00

Страница 1: ...run time detection with 230 V AC drives Direct control of blind shutter position Direct control of slat position Scene function Checkback of run status blind shutter position and slat position for bus...

Страница 2: ...Fig 2 5 indicate the out put states Off output is off On output is on up or down Flashing slowly output in manual control mode Flashing fast output disabled in permanent manual control mode Modes of o...

Страница 3: ...y for at least 5 s LED is on LEDs A1 are flashing permanent manual mode is activated Deactivating the permanent manual control mode The device is in the permanent manual control mode Press the key for...

Страница 4: ...5 s The selected output A1 A4 is enabled The LEDs of the selected output are flashing slow ly Activate the bus mode deactivate the permanent manual control mode Information for qualified electricians...

Страница 5: ...ation for qualified electricians The running time detection function is activated in the software The blinds shutters are not blocked Connect the bus line to the bus terminal Fig 3 Connect the mains v...

Страница 6: ...the label Fig 7 7 Sliding on the protective cap To protect the bus lines against dangerous voltages at the connecting terminal slide on the protective cap Lead out the bus line at the rear of the devi...

Страница 7: ...orehand The running times must be stored in undisturbed conditions i e without any control operations being performed and in the ab sence of wind snow and obstacles The automatic running time detectio...

Страница 8: ...ge temperature 25 C 70 C Mounting width 72 mm 4 modules Weight approx 300 g Help in case of trouble Manual control with keypad not possible Cause 1 Manual control mode not programmed Program the devic...

Страница 9: ...nic limit switches are being used Deactivate the automatic running time de tection Correct the electrical connection and re move the N conductor Blind shutter does not move to limit position po sition...

Страница 10: ...ee in accordance with the corresponding legal provisions Please return the unit postage paid to our central service department giving a brief description of the fault Gira Giersiepen GmbH Co KG Servic...

Отзывы: