4-channel blind/shutter actuator 230 V~

Installation Instructions

4-channel blind/shutter actuator 230 V~

1/07

Page 8 of 10

Technical data

KNX medium: 

TP1

Mode of commissioning: 

S-Mode

Instabus KNX/EIB supply:  21...32 V DC

Instabus KNX/EIB power
consumption: 

max. 150 mW

Mains supply: 

AC 230/240 V ±10%

Mains frequency: 

50/60 Hz

Total dissipated power: 

max. 4.5 W

Connection
Instabus KNX/EIB: 

connecting terminal

230 V supply and outputs:  screw terminals
Single-wire: 0.5...4 

mm²

Stranded wire 
without ferrule: 

0.5...4 mm²

Stranded wire with ferrule:  0.5...2,5 mm²

Screw terminal tightening 
torque: 

max. 0.8 Nm

Switching voltage AC: 

AC 230/240 V ±10%,

 50/60 

Hz

Switching capacity 
AC 230/240 V: 

6 A AC1

Switching voltage DC: 

12...48 V DC

Switched current DC: 

12/24 V 6 A

Switched current DC: 

48 V 3 A

max. blind/shutter 
running time: 

20 min

Automatic running 
time detection: 

max. 20 % of blind/shutter
running time

Ambient temperature: 

-5 °C ... +45 °C

Storage temperature 

-25 °C ... +70 °C

Mounting width: 

72 mm (4 modules)

Weight: approx. 

300 

g

Help in case of trouble

Manual control with keypad not possible

Cause 1:

Manual control mode not programmed.

Program the device for manual control.

Cause 2: 

Manual control mode disabled from bus.

Enable the manual control mode.

Output control not possible

Cause 1: Output 

disabled.

Re-enable the output.

Cause 2: 

Forced-control position, safety function

 

or sun protection active for the output

 concerned.

No control operation possible for this output as

 

long as primary functions are active.

No output operational

Cause 1: 

All outputs are disabled.

Re-enable the outputs.

Cause 2: 

Permanent manual control mode active.

Deactivate the permanent manual control

 

mode (switch this mode off).

Cause 3: 

Forced-control position, safety function

 

or sun protection active for all outputs.

No control operation possible as long as pri-
mary functions are active.

Cause 4: 

Application software stopped, program-
ming LED flashing.

Make a reset: disconnect the device from the

 

bus, reconnect after 5 seconds.

Cause 5: 

No or faulty application software.

Check programming and rectify.

Содержание 1039 00

Страница 1: ...run time detection with 230 V AC drives Direct control of blind shutter position Direct control of slat position Scene function Checkback of run status blind shutter position and slat position for bus...

Страница 2: ...Fig 2 5 indicate the out put states Off output is off On output is on up or down Flashing slowly output in manual control mode Flashing fast output disabled in permanent manual control mode Modes of o...

Страница 3: ...y for at least 5 s LED is on LEDs A1 are flashing permanent manual mode is activated Deactivating the permanent manual control mode The device is in the permanent manual control mode Press the key for...

Страница 4: ...5 s The selected output A1 A4 is enabled The LEDs of the selected output are flashing slow ly Activate the bus mode deactivate the permanent manual control mode Information for qualified electricians...

Страница 5: ...ation for qualified electricians The running time detection function is activated in the software The blinds shutters are not blocked Connect the bus line to the bus terminal Fig 3 Connect the mains v...

Страница 6: ...the label Fig 7 7 Sliding on the protective cap To protect the bus lines against dangerous voltages at the connecting terminal slide on the protective cap Lead out the bus line at the rear of the devi...

Страница 7: ...orehand The running times must be stored in undisturbed conditions i e without any control operations being performed and in the ab sence of wind snow and obstacles The automatic running time detectio...

Страница 8: ...ge temperature 25 C 70 C Mounting width 72 mm 4 modules Weight approx 300 g Help in case of trouble Manual control with keypad not possible Cause 1 Manual control mode not programmed Program the devic...

Страница 9: ...nic limit switches are being used Deactivate the automatic running time de tection Correct the electrical connection and re move the N conductor Blind shutter does not move to limit position po sition...

Страница 10: ...ee in accordance with the corresponding legal provisions Please return the unit postage paid to our central service department giving a brief description of the fault Gira Giersiepen GmbH Co KG Servic...

Отзывы: