41
Model: FSH-5
&
FSH-6
Hood Cleaning & Maintenance
5.
Hood Cleaning & Maintenance
This Section describes the steps to generally maintain and clean
FSH-5 & FSH-6 Hoods
. Attention to these
procedures will help ensure the Hood remains in satisfactory operating condition and continues to run efficiently
and safely.
A
Maintenance & Service Log
is provided, see
Section 5.06
.
The Hood design incorporates various interlock switches to ensure that the unit will shutdown if certain conditions exist
that are not consistent with safe and effective operation. The interlocks should be tested
MONTHLY
as described
below. Use the
Maintenance & Service Log
to record completion of testing. If problems are detected, contact
GILES
or an authorized service provider.
1.
Door Interlock Test:
Start Hood. With Hood running, unlatch and slightly open the Filter Access Doors, on
at a time. With each Door confirm Hood powers
OFF
when opened and all appliances under the Hood turn
OFF
, or will not turn
ON
.
2.
Baffle Filter Test:
Remove Baffle Filter from one side then turn
ON
Hood power. Verify that the red
[FILTER
MISSING]
light turns
ON
. Check to ensure that all appliances under Hood will not turn
ON
. Reinstall the
Baffle Filter and repeat test with the other Filter. See
Sections 4.02.2 & 4.02.3, Removal & Installation
.
3.
Pre-Filter/Charcoal Filter Test:
Same procedure as
[#2]
except perform for each of the Pre-Filters and
Charcoal Filters, one at a time in succession. Reinstall the Charcoal Filter. See
Sections 4.02.4, 4.02.5, 4.02.8
& 4.02.9, Removal & Installation
.
3.
E.A.C. Filter Test:
Same procedure as
[#2 & #3]
except remove each E.A.C. Filter Collector Cell, one at a
time, close and latch Door. Turn
ON
Hood power. Verify that
all three (3)
small E.A.C. Status Lights come
ON
for the side without Cell in place. Wait approx. two (2) minutes. A beeping tone alarm should begin
sounding. Check to ensure that all appliances under Hood will not turn
ON
. Reinstall the E.A.C. Cell, repeat
for other side. See
Section 4.02.6. & 4.02.7, Removal & Installation
.
5.
Filter Clogged Test:
Perform this test ONLY after installing new Charcoal Filter
.
Start Hood normally and
allow to run. Use cardboard or other material to completely block Hood exhaust outlet, holding it firmly in
place so that no air is escaping
.
Within a few seconds, a continuous tone alarm should begin sounding.
Check to ensure that all appliances under Hood will not turn
ON
. Remove the obstruction; the alarm should
silence and the appliances should be powered again.
Should any of these tests fail to yield the described results, contact a factory-authorized service company and have
the unit evaluated and repaired. Any Giles Manufacturer’s Representative can provide information about nearby
authorized service providers, or call
GILES Services
at 800-554-4537
for assistance in locating a Representative or
service provider.
5.01
Monthly Hood Interlock Inspection (Can be Performed by User)
Содержание FSH-5
Страница 2: ......
Страница 4: ......
Страница 30: ...Model FSH 5 FSH 6 Overview 20 5 2 1 ILS Option Only 3 4 3 01 Control Panel ...
Страница 32: ...22 Model FSH 5 FSH 6 Overview 3 02 Filter Chamber Exhaust Not shown 2 7 8 1 5 3 4 6 9 9 ...
Страница 36: ...26 Model FSH 3 5 FSH 4 Overview ...
Страница 38: ...28 Model FSH 5 FSH 6 Operation Filter Maintenance 4 02 2 Baffle Filter Removal Place in OFF position ...
Страница 50: ...40 Model FSH 5 FSH 6 Operation Filter Maintenance ...
Страница 62: ...52 Model FSH 5 FSH 6 Parts List Not shown 7 04 Under Hood Filters Lights 4 5 2 1 3 1 3 ...
Страница 64: ...54 Model FSH 5 FSH 6 Parts List Not shown 7 05 Doors Front Panel Ceiling Suspended Model 7 9 4 2 1 3 6 5 8 10 ...
Страница 68: ...58 Model FSH 5 FSH 6 Parts List ...
Страница 69: ......