background image

Ordering
Specification

SERIES:

SIZE (mm width x Height or Dia)

CONDITION MICROSWITCH
OPTIONS:
Fail Safe...................................FC
Normal......................................NC
Fa Normal...............FC/NC
(Modes 5 & 6 only. 
Standard on Mode 9 & 10)

STANDARD POWER SUPPLIES:
6 Way.....................................................................G6
6 Way c/w output relay...........................................G6R
12 Way...................................................................G12
12 Way c/w/ output relay........................................G12R

REMOTE INDICATORS:
Single unit.........................................................SR1

SMOKE DETECTORS:
24V DC wire ionisation......................................SD2

MASTER MONITOR:
1 - 12 unit..........................................................SMM1 -12
                                                                 plus per damper

UNINTERRUPTIBLEPOWER SUPPLIES:
6 Way.....................................................................UPS6
6 Way c/w output relay...........................................UPS6R
12 Way...................................................................UPS12
12 Way c/w/ output relay........................................UPS12R

TYPE:
Square/Rectangular:..............S
Circular...................................C
Oval........................................O

MODE: 5, 6, 9 & 10

CONTROL OPTION: A or B

INSTALLATION FRAME OPTION:
Standard................................IF
Dry Wall Partition...................DF

CABLE TERMINATION BOX...TB
(Modes 9,10)

ACCESS PANEL..........................AP

NUMBER REQUIRED

DUC

450 x 200

9

A

15

IF

TB

FC/NC

AP

S

Outer Casing

Components for the outer casing are
manufactured from 1.2mm galvanised
steel. BS EN 10142:1991:FEP02G
formed into sections of average
dimensions 120 x 50mm with spigot
ends for connection to system
ductwork. Outer casing sections are
fully welded.

Inner Cassette

Components to form the inner cassette
on all four sides are from 1.5mm
galvanised mild steel. Components are
formed into a channel section of size
120mm x 50mm. The inner casing is
mechanically joined at the corners The
vertical components contain holes for

blade spindles. The horizontal
components are complete with return
edge channels for retaining the top and
bottom seals.

Damper Blades

The damper blades are made from
0.45mm thick (.018”) BS 1449 stainless
steel. Blades are formed into a hollow
sectional profile. The blade ends are
formed into individual circular drive
shafts and located on brass bushes
through the side channels.

Side seals of 0.25mm stainless (as per
blade specification) are formed and
pierced to accept blade drive shafts
and are assembled between frame and

blade ends. Top and bottom seals are
manufactured in the same material but
are retained on top and bottom frames
by returned channels fixed on in the
frame inner surface.

The blades are actuated by a 2mm
thick x 58mm steel channel located in
the side frame and acting on steel
pinions attached to blade ends. The
rack and pinions are galvansied and
are contained in the side frame.

Half gears as rack specification transfer
the sideways rack movement to circular
blade drive shafts. A drive bar moves
the rack up or down and is either hand
or motor controlled via a electro thermal
fuse.

DUCTGARD

Duct Mounting Smoke and Fire Control Dampers

Gilberts (Blackpool) Ltd reserve the right to alter the specification without notice. The information contained in this leaflet is correct at time of going to press 

©

2012.

For our latest product data please visit www.gilbertsblackpool.com.

GILBERTS

Head Office and Works

GILBERTS (BLACKPOOL) LTD

Gilair Works, Clifton Road,
Blackpool.
Lancashire FY4 4QT.
Telephone: (01253) 766911
Fax:

(01253) 767941

e-mail:

[email protected]

Web:  

www.gilbertsblackpool.com

Содержание DUCTGARD

Страница 1: ...and frame side seals Unique patented precision blade linkage mechanism 8 Different modes of operation Connections to suit most proprietary duct work Extensive range of external control facilities DUCTGARD Duct Mounting Smoke and Fire Control Dampers Dampers 1 NOV 2012 ...

Страница 2: ...f HVAC ductwork Developed from our well proven door mounting smokegard damper over 40 years of engineering experience in the industry and considerable ingenuity has been applied in the design and construction of this product to produce a damper of high efficiency reliability durability and ease of use INTRODUCTION ...

Страница 3: ...ailable as standard upon request Mode Description Page 5A Fully automatic electronic 24v DC opening with fail safe spring 4 closure via 72 C electro thermal link release 5B Fully automatic electronic 240v AC opening with fail safe spring 4 closure via 72 C electro thermal link release 6A Fully automatic electronic 24v DC closure with fail safe spring 4 opening via 72 C electro thermal link release...

Страница 4: ...incorporate a fishtail edge detail which with the help of the precision single rack operation enables the blades to close and interlock extremely tightly This provides a tough effective screen against smoke and flames for its maximum 4 hour rating Stainless Steel Edge Seals These provide effective barriers to cold smoke penetration and allow the blades to expand under fire conditions minimising le...

Страница 5: ...dication L E D and test facility The test key facility allows local checks to be made on the damper operation The L E D provides the following diagnostic checks GREEN DISPLAY Power supply ON unit set RED DISPLAY Power supply ON but unit in fail safe mode NO DISPLAY Power supply failure unit in fail safe mode The control box also provides an interface for remote status indication smoke detectors an...

Страница 6: ...ectro thermal fusible link which will fail at a pre determined temperature 72 C standard and close the damper irrespective of the status of the motor An integral test pushbutton on the electro thermal fuse housing allows for the local testing of the damper operation Motor Control Options A 24V AC or DC supply B 240V AC supply Note All options are complete with position microswitches as standard Re...

Страница 7: ...r self tapping into ductwork system List Size Range 200 1000 Diameter in 100mm increments For other circular duct sizes overall sizes as next size up standard size For example 315 duct has 312 spigots and 432 high casing Dim A Modes 9 10 140 Above with terminal box 240 Modes 5 6 240 Square and Rectangular Spigots Ref S Smaller and intermediate sizes available Circular Spigots Ref C Smaller and int...

Страница 8: ...ation where a damper larger than 1000mm x 1000mm is required multiple unit assemblies can be provided These can take the form of either a two pack horizontal or vertical assembly or a full 4 pack assembly i e two double assemblies Each module of the assembly is provided with its own control unit and fusible link Note Before installation of any multiple assembly proposed arrangements should be agre...

Страница 9: ...may be provided and fitted to a double module assembly not exceeding an overall size of 1524 x 1016mm split on the larger dimension Adjacent frame assemblies must be separated by builders work of a minimum distance of 225mm between installation frame upstand flanges unless approval has been previously obtained from the appropriate authority Where two fire dampers or two double module assemblies ar...

Страница 10: ...ding extra feature options Removal of the lid on the damper control box provides access to an internal terminal block for the following wiring connections If in doubt ask Modes 5 6 Control Option A Modes 5 6 Control Option B Standard Wiring Arrangement with Remote Indicator Option O G R L G R N 240VAC 9VA Supply 24VDC 300MA Supply O G R G R switch or volt free contacts O G R L G R N 240VAC 9VA Sup...

Страница 11: ...e available upon request 1 2 M Control Option A 1 2 M Control Option B S1 S2 S3 S4 S5 S6 5 80 S1 S2 S3 S4 S5 S6 5 80 L N E M N L 1 2 3 4 5 6 S S 1 2 3 4 5 6 2 Core Screened Communication Cable Belimo Damper Motor DCM Damper Control Module 240V 50HZ Fused Spur option 24V DC 24 V WIRING DIAGRAM Power Supply 24V AC 20 50 60 Hz 24V DC 20 Current Rating 380mA AC max POWER CONSUMPTION Opening 5 watts Ho...

Страница 12: ...ressable module has been designed to provide independent operation of individual or groups of dampers in accordance with a pre programmed logic sequence of events Individual dampers are controlled and have there status constantly monitored by the module in response to signals from the pre programmed controller Maximum length of communications 2km In the event of communications failure dampers assu...

Страница 13: ...oke Detectors Smoke Detectors are available for in duct or ceiling mounting and can link directly into Modes 5 6 or the output relay of the Power Supply units Detectors are 24v DC Ionisation type Ref In duct 4 wire SD3 4 wire SD2 RED LIGHT SYSTEM TRIPPED GREEN LIGHT SYSTEM SET UNIT No AIIFA No OUTLINE OF PCB NOTE When damper is open yellow is VE When damper is closed blue is VE O R G YELLOW BLUE V...

Страница 14: ...time there were not any significant gaps in or around the assembly to permit the passage of flames Air Velocity Against Pressure Drop The graph opposite has been formulated to give an indication of the pressure drop expected through a fully open damper in relation to duct air velocity Airflow Blade Leakage Against Differential Pressure The graph opposite illustrates the maximum leakage obtainable ...

Страница 15: ...ve linkage motors and electronic components on the ductgard units are sealed for life there should be no requirement for periodic maintenance and spares are not normally required Items such as reset levers and test keys however can be misplaced over time In this event replacements are readily available from Head Office Trouble Shooting Gilberts Damper Smoke and Fire Control Range All Ductgard unit...

Страница 16: ...h return edge channels for retaining the top and bottom seals Damper Blades The damper blades are made from 0 45mm thick 018 BS 1449 stainless steel Blades are formed into a hollow sectional profile The blade ends are formed into individual circular drive shafts and located on brass bushes through the side channels Side seals of 0 25mm stainless as per blade specification are formed and pierced to...