Ordering
Specification
SERIES:
SIZE (mm width x Height or Dia)
CONDITION MICROSWITCH
OPTIONS:
Fail Safe...................................FC
Normal......................................NC
Fa Normal...............FC/NC
(Modes 5 & 6 only.
Standard on Mode 9 & 10)
STANDARD POWER SUPPLIES:
6 Way.....................................................................G6
6 Way c/w output relay...........................................G6R
12 Way...................................................................G12
12 Way c/w/ output relay........................................G12R
REMOTE INDICATORS:
Single unit.........................................................SR1
SMOKE DETECTORS:
24V DC wire ionisation......................................SD2
MASTER MONITOR:
1 - 12 unit..........................................................SMM1 -12
plus per damper
UNINTERRUPTIBLEPOWER SUPPLIES:
6 Way.....................................................................UPS6
6 Way c/w output relay...........................................UPS6R
12 Way...................................................................UPS12
12 Way c/w/ output relay........................................UPS12R
TYPE:
Square/Rectangular:..............S
Circular...................................C
Oval........................................O
MODE: 5, 6, 9 & 10
CONTROL OPTION: A or B
INSTALLATION FRAME OPTION:
Standard................................IF
Dry Wall Partition...................DF
CABLE TERMINATION BOX...TB
(Modes 9,10)
ACCESS PANEL..........................AP
NUMBER REQUIRED
DUC
450 x 200
9
A
15
IF
TB
FC/NC
AP
S
Outer Casing
Components for the outer casing are
manufactured from 1.2mm galvanised
steel. BS EN 10142:1991:FEP02G
formed into sections of average
dimensions 120 x 50mm with spigot
ends for connection to system
ductwork. Outer casing sections are
fully welded.
Inner Cassette
Components to form the inner cassette
on all four sides are from 1.5mm
galvanised mild steel. Components are
formed into a channel section of size
120mm x 50mm. The inner casing is
mechanically joined at the corners The
vertical components contain holes for
blade spindles. The horizontal
components are complete with return
edge channels for retaining the top and
bottom seals.
Damper Blades
The damper blades are made from
0.45mm thick (.018”) BS 1449 stainless
steel. Blades are formed into a hollow
sectional profile. The blade ends are
formed into individual circular drive
shafts and located on brass bushes
through the side channels.
Side seals of 0.25mm stainless (as per
blade specification) are formed and
pierced to accept blade drive shafts
and are assembled between frame and
blade ends. Top and bottom seals are
manufactured in the same material but
are retained on top and bottom frames
by returned channels fixed on in the
frame inner surface.
The blades are actuated by a 2mm
thick x 58mm steel channel located in
the side frame and acting on steel
pinions attached to blade ends. The
rack and pinions are galvansied and
are contained in the side frame.
Half gears as rack specification transfer
the sideways rack movement to circular
blade drive shafts. A drive bar moves
the rack up or down and is either hand
or motor controlled via a electro thermal
fuse.
DUCTGARD
Duct Mounting Smoke and Fire Control Dampers
Gilberts (Blackpool) Ltd reserve the right to alter the specification without notice. The information contained in this leaflet is correct at time of going to press
©
2012.
For our latest product data please visit www.gilbertsblackpool.com.
GILBERTS
Head Office and Works
GILBERTS (BLACKPOOL) LTD
Gilair Works, Clifton Road,
Blackpool.
Lancashire FY4 4QT.
Telephone: (01253) 766911
Fax:
(01253) 767941
e-mail:
Web:
www.gilbertsblackpool.com